Interior Lighting Compliance Certificate
Project Title:
90.1 (2007) Standard
Project Type: New Construction
Construction Site:
13590 N. MERIDIAN ST.
CARMEL, IN 46302
Owner/Agent:
AVON CARMEL, LLC
106 FINNELL DR.
UNIT 1
WEYMOUTH, MA 02188
Designer/Contractor:
Keith A. Pharis, PE LEED AP
FORZA ARCHITECTURE
654 S. SHELBY ST
SUITE 301
LOUISVILLE, KY 40202
502-471-7963
ka.pharis@pharisengineering.com
Project Information
Energy Code:
LANDMARK RECOVERY OF CARMEL
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Detox Facility (Office) 15600 1.00 15600
Total Allowed Watts = 15600
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1-Detox Facility (Office)
LED 1: D1: LED Other Fixture Unit 16W: 1 96 15 1440
LED 2: D2: LED Other Fixture Unit 36W: 1 27 35 945
LED 3: D3: LED Other Fixture Unit 25W: 1 8 25 200
LED 4: DW: LED Other Fixture Unit 28W: 1 8 30 240
LED 5: T1: LED Panel 44W: 1 35 47 1645
LED 6: T2: LED Panel 36W: 1 22 36 792
LED 7: T3: LED Panel 60W: 1 3 64 192
Name - Title Signature Date
Project Title:
Data filename:
LANDMARK RECOVERY OF CARMEL
C:\Users\Keith\OneDrive\Engineering\2018\18250 Carmel IN
Forza\Calcs\CARMELDETOXashrae.cck
Report date: 07/13/18
Page 2 of 8
Keith A. Pharis, PE LEED AP Electrical Engineer 07/13/2018
COMcheck Software Version 4.1.0.0
Exterior Lighting Compliance Certificate
Project Title:
90.1 (2007) Standard
Project Type: New Construction
Construction Site:
13590 N. MERIDIAN ST.
CARMEL, IN 46302
Owner/Agent:
AVON CARMEL, LLC
106 FINNELL DR.
UNIT 1
WEYMOUTH, MA 02188
Designer/Contractor:
Keith A. Pharis, PE LEED AP
FORZA ARCHITECTURE
654 S. SHELBY ST
SUITE 301
LOUISVILLE, KY 40202
502-471-7963
ka.pharis@pharisengineering.com
Project Information
Energy Code:
LANDMARK RECOVERY OF CARMEL
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Main entry/exit 6 ft of door 30 Yes 180
Other entry/exit 3 ft of door 20 Yes 60
Other entry/exit 3 ft of door 20 Yes 60
Other entry/exit 3 ft of door 20 Yes 60
Other entry/exit 6 ft of door 20 Yes 120
Other entry/exit 6 ft of door 20 Yes 120
Other entry/exit 6 ft of door 20 Yes 120
Illuminated length of wall or surface 150 ft 5 No 750
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
720
1470
74
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 74 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Illuminated length of facade wall or surface (150 ft): Non-tradable Wattage
LED 2: OL2: Ext LED Flood: LED Other Fixture Unit 46W: 1 6 45 270
Total Tradable Proposed Watts = 165
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 4.1.0.0 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 79% better than code
Project Title:
Data filename:
LANDMARK RECOVERY OF CARMEL
C:\Users\Keith\OneDrive\Engineering\2018\18250 Carmel IN
Forza\Calcs\CARMELDETOXashrae.cck
Report date: 07/13/18
Page 4 of 8
Keith A. Pharis, PE LEED AP Electrical Engineer 07/13/2018
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.0.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 90.1 (2007) Standard
Section
#
& Req.ID
Plan Review Complies? Comments/Assumptions
4.2.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the lighting and
electrical systems and equipment and
document where exceptions to the
standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
8.4.1.1,
8.4.1.2
[PR6]2
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
LANDMARK RECOVERY OF CARMEL
C:\Users\Keith\OneDrive\Engineering\2018\18250 Carmel IN
Forza\Calcs\CARMELDETOXashrae.cck
Report date: 07/13/18
Page 5 of 8
X
X Requirement is met.
Requirement is met.
Section
#
& Req.ID
Rough-In Electrical Inspection Complies? Comments/Assumptions
9.4.1.1
[EL1]2
Automatic controls to shut off all
building lighting installed in buildings
>5,000 ft2.
Complies
Does Not
Not Observable
Not Applicable
9.4.1.2
[EL2]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
9.4.1.3
[EL3]2
Automatic lighting controls for exterior
lighting installed.
Complies
Does Not
Not Observable
Not Applicable
9.4.1.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
9.4.2
[EL5]3
Ballasted one and three lamp fixtures
with >30 W/lamp have two lamp
tandem wired ballasts when >=2
fixtures in same space on same
control.
Complies
Does Not
Not Observable
Not Applicable
9.4.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
9.4.4
Section
#
& Req.ID
Final Inspection Complies? Comments/Assumptions
8.7.1
[FI16]3
Furnished as-built drawings for
electric power systems within 30 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
8.7.2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
9.2.2.3
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
9.4.5
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
LANDMARK RECOVERY OF CARMEL
C:\Users\Keith\OneDrive\Engineering\2018\18250 Carmel IN
Forza\Calcs\CARMELDETOXashrae.cck
Report date: 07/13/18
Page 7 of 8
Will be provided at project completion
X
X
Project Title:
Data filename:
LANDMARK RECOVERY OF CARMEL
C:\Users\Keith\OneDrive\Engineering\2018\18250 Carmel IN
Forza\Calcs\CARMELDETOXashrae.cck
Report date: 07/13/18
Page 8 of 8
X
X
Will be installed per plans and specs
Will be installed per plans and specs
Will be provided at project completion
[EL7]1
Exterior grounds lighting over 100 W
provides >60 lm/W unless on motion
sensor or fixture is exempt from scope
of code or from external LPD.
Complies
Does Not
Not Observable
Not Applicable
9.6.2
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
LANDMARK RECOVERY OF CARMEL
C:\Users\Keith\OneDrive\Engineering\2018\18250 Carmel IN
Forza\Calcs\CARMELDETOXashrae.cck
Report date: 07/13/18
Page 6 of 8
X
X
X
X
X
X
X
X
Requirement is met.
Will be installed per plans and specs
Will be installed per plans and specs
Will be installed per plans and specs
Requirement is met.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Main entry (6 ft of door width): Tradable Wattage
LED 1: OL1: LED Wall Sconce: LED Other Fixture Unit 13W: 1 2 15 30
Other door (not main entry) (3 ft of door width): Tradable Wattage
LED 2: OL1: LED Wall Sconce: LED Other Fixture Unit 13W: 1 1 15 15
LED 1: OL1: Ext LED Wall Sconce: LED Other Fixture Unit 13W: 1 1 15 15
LED 1: OL1: Ext LED Wall Sconce: LED Other Fixture Unit 13W: 1 1 15 15
Other door (not main entry) (6 ft of door width): Tradable Wattage
LED 1: OL1: Ext LED Wall Sconce: LED Other Fixture Unit 13W: 1 2 15 30
LED 1: OL1: Ext LED Wall Sconce: LED Other Fixture Unit 13W: 1 2 15 30
LED 1: OL1: Ext LED Wall Sconce: LED Other Fixture Unit 13W: 1 2 15 30
Project Title:
Data filename:
LANDMARK RECOVERY OF CARMEL
C:\Users\Keith\OneDrive\Engineering\2018\18250 Carmel IN
Forza\Calcs\CARMELDETOXashrae.cck
Report date: 07/13/18
Page 3 of 8
LED 8: T4: LED Panel 44W: 1 18 45 810
LED 9: T5: LED Panel 33W: 1 51 28 1428
LED 10: T6: LED Panel 54W: 1 8 54 432
LED 11: T7: LED Panel 33W: 1 23 28 644
LED 12: LED Linear 33W: 1 4 33 132
Total Proposed Watts = 8900
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 4.1.0.0 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Interior Lighting PASSES: Design 43% better than code
Project Title:
Data filename:
LANDMARK RECOVERY OF CARMEL
C:\Users\Keith\OneDrive\Engineering\2018\18250 Carmel IN
Forza\Calcs\CARMELDETOXashrae.cck
Report date: 07/13/18