HomeMy WebLinkAboutM001MECHANICAL LEGEND
SECTION (DUCT RISER) - SUPPLY AIR DUCT
E100 FIRE / SMOKE DAMPER
0 SECTION (DUCT RISER) - RETURN AIR DUCT
TO ROOM TEMPERATURE SENSOR / THERMOSTAT
SECTION (DUCT RISER) - EXHAUST AIR
HO HUMIDISTAT SENSOR
-'' SECTION (DUCT RISER) - OUTSIDE AIR
(02) OXYGEN SENSOR
0 SECTION (DUCT RISER) - ROUND SUPPLY DUCT
I............I SECTION (DUCT RISER) - ROUND RETURN DUCT
SECTION (DUCT RISER) - ROUND EXHAUST DUCT
0 SECTION (DUCT RISER) - ROUND OUTSIDE AIR DUCT
® SUPPLY AIR DIFFUSER
RETURN AIR GRILLE
® EXHAUSE AIR GRILLE
M MANUAL BALANCE DAMPER
FLEXIBLE DUCT
® POINT OF CONNECTION
® POINT OF REMOVAL
MECHANICAL GENERAL NOTES
NOTE NUMBER
NOTE
1
DUCT FABRICATION AND INSTALLATION SHALL CONFORM TO THE "HVAC DUCT CONSTRUCTION STANDARDS AS PUBLISHED BY S.M.A.C.N.A. LATEST EDITION.
2
ALL BRANCHED TO DIFFUSERS AND REGISTERS SHALL BE SUPPLIED WITH MANUAL VOLUME DAMPERS. ALL DAMPERS THAT ARE INACCESSIBLE SHALL BE PROVIDED WITH
REMOTE OPERATORS SIMILAR TO VENTLOK 677-PLAIN FINISH
3
ALL MISCELLANEOUS METAL, ANGLES, BRACING OR SUPPORTS EXPOSED TO THE WEATHER SHALL BE GALVANIZED IRON OR BLACK IRON PAINTED WITH ONE COAT OF RUST
INHIBITING PAINT AND ONE COAT OF GRAY PRIMER.
4
PENETRATIONS IN FIRE -RESISTIVE WALLS, PARTITIONS AND FLOORS WHERE PROTECTED OPENINGS ARE REQUIRED SHALL BE FIRE STOPPED USING APPROVED
MATERIALS, INTEGRITY AND PREVENTING THE MOVEMENT OF HOT FLAMES OR GASES THROUGH THE VOID SPACES BETWEEN PENETRATING MATERIALS AND WALLS,
PARTITIONS AND FLOORS WHEN TESTED IN ACCORDANCE WITH ASTM STANDARD E-814 OR U.L. STANDARD 1479.
5
ALL SUPPLY AND RETURN DUCTWORK AND PIPING SHALL BE INSULATED. INSULATION SHALL HAVE A FLAME SPREAD OF NOT MORE THAN 25 AND A SMOKE DEVELOPED
RATING OF NOT MORE THAN 50 WHEN TESTED AS A COMPOSITE INSTALLATION INCLUDING INSULATION FACING MATERIALS, TAPE, AND ADHESIVE.
6
FLEXIBLE DUCTS SHALL BE SUPPORTED AT OR NEAR MID -LENGTH WITH 2" WIDE 28 GUAGE STEEL HANGER COLLAR ATTECHED TO THE STRUCTURE WITH AN APPROVED
DUCT HANGER. INSTALLATION SHALL MINIMIZE SHARP RADIUS TURNS OR OFFSETS. THE MAXIMUM LENGTH CONNECTING TO TERMINAL OUTLETS SHALL BE 6'-011.
7
CONSTRUCTION PRESSURE CLASSIFICATION: SUPPLY AND RETURN DUCT TO BE 1" STATIC PRESSURE CONSTRUCTION. DUCT LEAKAGE TEST NOT REQUIRED. RETURN AND
EXHAUST DUCT TO BE 1" STATIC PRESSURE CONSTRUCTION, UNLESS OTHERWISE NOTED. DUCT LEAKAGE TEST NOT REQUIRED UNLESS OTHERWISE NOTED.
8
DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
9
FOR AV ROOMS THE REFRIGERANT SUPPLY AND SUCTION LINES, THE POWER AND CONTROL CABLES AND THE CONDENSATE DRAIN PIPING SHALL BE CONTAINED IN A
SINGLE CONDUIT PENETRATION.
10
ALL ADHESIVES AND SEALANTS SHALL MEET THE REQUIREMENTS OF THE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD) RULE #1168. AEROSOL ADHESIVES
SHALL MEET GREEN SEAL STANDARD FOR COMMERCIAL ADHESIVES GS-36 REQUIREMENTS.
11
ALL EQUIPMENT SHALL BE PROVIDED WITH MANUFACTURER'S HIGHEST EFFICIENCY MOTOR OPTION.
12
ROUND DUCT MAY BE USED IN PLACE OF SQUARE OR RECTANGULAR DUCT. ROUND DUCT SHALL BE SIZED USING A DUCTULATOR WITH FRICTION LOSS OF 0.08" TO 0.10" PER
100 FEET OF DUCT.
13
ALL WORK SHALL CONFORM TO THE LATEST INDIANA MECHANICAL CODE AND ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES.
FLEX DUCT SCHEDULE
MAX AIRFLOW (CFM)
SIZE
100
6"
150
7"
200
8"
300
9"
400
10"
600
12"
1000
14"
1500
16"
RELEASED FOR CONSTRUCTION
Subjeut to cont••••..pfi@xe with alll redulhtluns
of State and local Codes
City of camel
DATE: 11/26/18
William Hohlt
AIRFLOW PATTERN
1. TYPICAL ROOM AIRFLOW PATTERN.
2. VERIFY CEILING TYPE BEFORE ORDERING DIFFUSERS,
GRILLES OR REGISTERS
MECHANICAL ABBREVIATIONS
ABBREVIATION
DESCRIPTION
ABBREVIATION
DESCRIPTION
A
AMPS
LDB
LEAVING DRY BULB
AC
AIR CONDITIONER
Ips
LITERS PER SECOND
AMB
AMBIENT
LVG
LEAVING
APD
AIR PRESSURE DROP
LWB
LEAVING WET BULB TEMPERATURE
APPROX.
APPROXIMATE
LWT
LEAVING WATER TEMPERATURE
ATFP
ANTI TERRORISM FORCE PROTECTION
MAX
MAXIMUM
BTUH
BRITISH THERMAL UNIT'S PER HOUR
MBH
1,000 BRITISH THERMAL UNITS PER HOUR
C
CENTIGRADE
MCA
MAXIMUM CURRENT AMPS
CAP
CAPACITY
MERV
MINIMUM EFFICIENCY REPORTING VALUE
CC
COOLING COIL
MFG
MANUFACTURER
CFM
CUBIC FEET PER MINUTE
MIN
MINIMUM
CHW
CHILLED WATER
MM
MILLIMETER
CHWR
CHILLED WATER RETURN
MOCP
MAXIMUM OVERCURRENT PROTECTION
CHWS
CHILLED WATER SUPPLY
MPS
MEDIUM PRESSURE STEAM
COP
COEFFICIENT OF PERFORMANCE
MTD
MOUNTED
CR
CONDENSATE RETURN
MU
MAKE-UP
CU
CONDENSING UNIT
NC
NOISE CRITERION
CW
COLD WATER
NEMA
NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
DDC
DIRECT DIGITAL CONTROL
NFPA
NATIONAL FIRE PROTECTION
ASSOCIATION
D/L
DOOR LOUVER
NMCI
NAVY MARINE CORPS INTRANET
DSD
DUCT SMOKE DETECTOR
0 & M
OPERATION AND MAINTENANCE
DX
DIRECT EXPANSION
OBD
OPPOSED BLADE DAMPER
(E)
EXISTING
OSA
OUTSIDE AIR
EA
EXHAUST AIR
Pa
PASCALS
EAT
ENTERING AIR TEMPERATURE
PD
PRESSURE DROP
EDB
ENTERING DRY BULB TEMPERATURE
PH
PHASE
EER
ENERGY EFFICIENCY RATIO
PRV
PRESSURE REDUCING / RELIEF VALVE
EF
EXHAUST FAN
PSI
POUNDS PER SQUARE INCH
EL
EXPANSION LOOP
QTY
QUANTITY
ENT
ENTERING
RA
RETURN AIR
EQUIP
EQUIPMENT
REF
REFERENCE
ESP
EXTERNAL STATIC PRESSURE
READ
REQUIRED
EWB
ENTERING WET BULB TEMPERATURE
RF
RETURN FAN
EWT
ENTERING WATER TEMPERATURE
RLA
RUNNING LOAD AMPS
F
FAHRENHEIT
RP
RECIRCULATING PUMP
FC
FAN COIL
RPM
REVOLUTIONS PER MINUTE
FLA
FULL LOAD AMPS
SA
SUPPLY AIR
FT HD
FOOT HEAD
SEER
SEASONAL ENERGY EFFICIENCY RATIO
GAL
GALLON
SF
SUPPLY FAN
GALV
GALVANIZED
Si
SEISMIC JOINT
GLYR
GLYCOL RETURN
SMACNA
SHEET METAL AND AIR CONDITIONING
CONTRACTORS' NATIONAL ASSOCIATION
GLYS
GLYCOL SUPPLY
SQ FT
SQUARE FOOT
GPM
GALLONS PER MINUTE
T
TRAP
HHW
HEATING HOT WATER
TAB
TEST AND BALANCE
HHWR
HEATING HOT WATER RETURN
TSP
TOTAL STATIC PRESSURE.
HHWS
HEATING HOT WATER SUPPLY
T'STAT
THERMOSTAT
HP
HEAT PUMP
TYP
TYPICAL
HP
HORSEPOWER
U/C
UNDERCUT
HR
HOUR
U/G
UNDERGROUND
HSPF
HEATING SEASONAL PERFORMANCE FACTOR
UFC
UNIFIED FACILITIES CRITERIA
HV
HEAT VENTILATOR
UON
UNLESS OTHERWISE NOTED
HW
HOT WATER
V
VOLTAGE / VOLTS
HX
HEAT EXCHANGER
VAV
VARIABLE AIR VOLUME
Hz
HERTZ
VE
VEHICLE EXHAUST SYSTEM
in-wg
INCHES WATER GAUGE
VFD
VARIABLE FREQUENCY DRIVE
in (")
INCHES
W/
WITH
IPLV
INTEGRATED PART LOAD VALUE
WB
WET BULB
IRH
INFARED HEATER
WPD
WATER PRESSURE DROP
LAT
LEAVING AIR TEMPERATURE
LBS
POUNDS
W
Z
Lij Q
UZ
Q
� W
� z
�U
C-0LU
v
� J
U)
a
Q
�
W
0�
>
U
�
ti
DISCLAIMER:
This is an original design, created by KJG Architecture, Inc. The
concepts, ideas, plans and details are the sole property of KJG
Architecture, Inc. None of the aforementioned shall be used by or
disclosed to any person, firm or organization for any purpose without the
prior written permission of KJG Architecture, Inc.
PROFESSIONAL SEAL:
Q ,OFESS/O
ti
D� 91��
NO. PE10910442 z
m
m
s�gTF
OF
PROJECT DATE:
09/ 14/2018
No.
DESCRIPTION:
DRAWN
BY:
DATE
ISSUED:
PROJECT NUMBER:
DRAWN BY:
DRAWING TITLE:
MECHANICAL
LEGEND
SHEET NUMBER: