TRAP SUCTION LINE PER MANUFACTURER RECOMMENDATION.
HARD START KIT INSTALLED ON OUTDOOR UNIT.
ON GRADE
SUCTION LINE
LIQUID AND SUCTION REFRIGERANT
LINES (INSULATE LINES)
DUCTLESS
SPLIT
OUTDOOR
(DSO)
LIQUID LINE
SIGHT GLASS
REFRIGERANT PIPING DIAGRAM
NO SCALE
3/8"x2-1/2" ANCHOR
BOLT (4 MIN READ)
EQUIPMENT MOUNTING
TAB OR 1/8"x2x3x3"
LONG BENT ANGLE
GRADE
CONDENSING
UNIT
FILTER DRIER
PROVIDE 5/16" WAFFLE PAD
UNDER MOUNTING FEET
CONDENSING UNIT MOUNTING DETAIL
NO SCALE
NOTES:
UNITS SHALL BE INTERNALLY ISOLATED AND BOLTED TO CURB.
OSALOUVER
0-100%
ECONOMIZER
EXHAUST LOUVER
EQUIPMENT CURB
MUST BE LEVEL &
DIMENSIONALLY
COMPATIBLE
WITH UNIT
DUCTLESS
SPLIT
INDOOR
(DSI)
20' DIFFERENCE IN
HEIGHT OR >80' IN
TOTAL EQUIVALENT
LENGTH = LONG -LINE
APPLICATION
TYP
4" CONCRETE EQUIPMENT PAD
6" LARGER THAN UNIT ALL AROUND
EXPAND AS NEEDED FOR MULTIPLE
UNITS. PROVIDE MANUFACTURER"S
RECOMMENDED CLEARANCES
BETWEEN UNITS.
TYP
FILTER SECTION
COIL & BLOWER SECTION
DISCHARGE SECTION
CONDENSING SECTION
HOUSEKEEPING
PAD ON GRADE
PACKAGED AIR CONDITIONER DETAIL"ADD ALTERNATE"
SCALE: NONE
RELEASED FOR CONSTRUCTION
Subjeutto can pfi@ ce with alll redullatiuns
of State and local Codes
City of camel
DATE: 11/26/18
William Hohlt
NOTES:
1. ALL BRANCH TAKE -OFFS TO BE INSTALLED PER SMACNA DUCT CONSTRUCTION STANDARDS.
2. ALL MANUAL BALANCING DAMPERS ON SUPPLY AIR DUCT SERVING VAV BOXES TO BE LOCKED IN OPEN
POSITION WITH SCREW THROUGH HANDLE.
DUCT TAKE -OFFS
NO SCALE
EXHAUST FAN
HOUSING
BLOCKING, BOTH SIDES -
OF FAN AS REQUIRED
CEILING JOIST
GYPSUM BOARD
CEILING
EXHAUST GRILLE
1
I
ifI
EXHAUST DUCT
NOTES:
FLEXIBLE CONNECTION SHALL HAVE A FLAME SPREAD INDEX
OF 75 OR LESS AND A SMOKE -DEVELOPED RATING OF 150.
CEILING MOUNTED EXHAUST FAN
NO SCALE
FLEXIBLE DUCT (TYP)
(MAXIMUM LENGTH 6')
CLAMP (TYP)
MANUAL BALANCING DAMPER
WITH LOCKING QUADRANT
ROUND DUCT TAKE -OFF
TO MATCH FLEXIBLE DUCT
ROUND DUCT
3RANCH DUCT
MANUAL BALANCING DAMPER
KITH LOCKING QUADRANT
SPIN -IN DUCT TAKE -OFF
WITH EXTRACTOR
RECTANGULAR
OR ROUND DUCT
MANUAL BALANCING DAMPER
WITH LOCKING QUADRANT
RECTANGULAR DUCT
INSTALL PER
MANUFACTURER'S
INSTRUCTION
TYP
FLEXIBLE CONNECTION
EXHAUST DUCT
TYP
SHEET METAL SCREW -
(4 PER COLLAR MIN)
COLLAR FACTORY
INSTALLED
CLAMP
FLEXIBLE DUCT
(MAX LENGTH 6')
II I
I
0
CEILING
SURFACE MOUNTED
NOTE:
FLEXIBLE DUCT MUST BE SEALED TO COLLAR.
COLLAR FACTORY -
INSTALLED
SPIN -IN FITTING
DISTRIBUTION BOX
24 GAGE MINIMUM
----- OR -----
FLEXIBLE DUCT (MAXIMUM LENGTH 6')
CLAMP
SHEET METAL SCREW
(4 PER COLLAR MIN)
TURN UP
1" MINIMUM
CEILING
SURFACE
MOUNTED
NOTES:
FLEXIBLE DUCT MUST BE SEALED TO COLLAR.
AIR DISTRIBUTION CONNECTION
NO SCALE
NOTES:
FAN & PRE-FAB CURB SHALL SIT LEVEL. PROVIDE LEVEL BASE IF ROOF IS PITCHED.
EXHAUST FAN
PRE-FAB CURB
WITH CANT
RIGID INSULATI
SUPPORT ELBOW FROM
STRUCTURE W/SHEET METAL
STRAP WRAPPED AROUND
DUCT AS INDICATED
EXTERNAL INSULATE UP TO
BACK OF DIFFUSER, REGISTER
OR GRILLE (NOT READ FOR
EXHAUST DUCTS)
HARD
CONNECTION
CEILING
INLAY
DIFFUSER, REGISTER
OR GRILLE
SUPPORT BOX FROM
STRUCTURE W/ (2)
SHEET METAL STRAPS
EXTERNAL INSULATE ENTIRE
BOX UP TO BACK OF DIFFUSER,
REGISTER OR GRILLE (NOT
READ FOR EXHAUST DUCTS)
CEILING
INLAY
DIFFUSER,
REGISTER
OR GRILLE
ROOFING
ROOF
BACKDRAFT DAMPER
EXHAUST DUCT
ROOF MOUNTED EXHAUST FAN INSTALLATION DETAIL
NO SCALE
TYP
TYP
W
Z
Uj Q
Z
Q
� W
� z
�U
C-0_
v
LU
� J
U)
a
Q
�
W
0�
>
U
�
ti
DISCLAIMER:
This is an original design, created by KJG Architecture, Inc. The
concepts, ideas, plans and details are the sole property of KJG
Architecture, Inc. None of the aforementioned shall be used by or
disclosed to any person, firm or organization for any purpose without the
prior written permission of KJG Architecture, Inc.
PROFESSIONAL SEAL:
Q ,OFESS/O
D.
NO. PE10910442 z
m
m
s�gTF
O
PROJECT DATE:
09/ 14/2018
No.
DESCRIPTION:
DRAWN
BY:
DATE
ISSUED:
PROJECT NUMBER:
DRAWN BY:
DRAWING TITLE:
MECHANICAL
DETAILS
SHEET NUMBER: