HomeMy WebLinkAboutP001FIXTURE CALCULATIONS
TYPE OF FIXTURE
CW SUPPLY
HW SUPPLY
SEWER
QTY
FU
TOTAL
FU
TOTAL
FU
TOTAL
WATER CLOSET (TANK)
2
5
10
-
-
4
8
LAVATORY
3
2
6
1.5
4.5
1
3
SINKS
1
3
3
2.25
2.25
2
2
HOSE BIBBS
2
2
4
-
-
-
-
HOSE REEL
1
3
3
3
3
-
-
FLOOR DRAINS
5
-
-
-
-
2
10
FLOOR SINKS
2
-
-
-
-
2
4
TRENCH DRAIN
2
-
-
-
-
2
4
FIXTURES
ZAMBONI FILL
TOTAL
LINE SIZE
26
FU / 23 GPM
7 GPM
30 GPM
1-1/2" MAIN
9.75
FU / 15 GPM
7 GPM
22 GPM
1-1/4" MAIN
31 FU
4" MAIN
RELEASED FOR CONSTRUCTION
Subjeut to cont••••..pfi@xe with alll mgulhtiuns
of State and local Codes
City of camel
DATE: 11/26/18
William Hohlt
PLUMBING FIXTURE SCHEDULE
SYMBOL
TYPE
MANUFACTURER
MODEL
DESCRIPTION
WC-1
WATER CLOSET - ADA
AMERICAN STANDARD
CADET
ADA, FLOOR MOUNTED, FLUSH TANK, 1.1 GPF, VITREOUS CHINA, WITH EVERCLEAN, ELONGATED, SYPHON JET
WC-2
WATER CLOSET
AMERICAN STANDARD
CADET
FLOOR MOUNTED, FLUSH TANK, 1.1 GPF, VITREOUS CHINA, WITH EVERCLEAN, ELONGATED, SYPHON JET
L-1
LAVATORY
AMERICAN STANDARD
AQUALYN
ADA, DROP IN, SELF RIMMING, 4" CENTER HOLES, AMERICAN STANDARD COLONY PRO, 0.5 GPM, SINGLE HANDLE FAUCET, TEMPERING VALVE FOR 110 F MAX. DHW
S-1
SINK
AMERICAN STANDARD
COLONY - 22SB.6332284S.075
ADA, 25"x22"4", SINGLE BOWL, 20 GAUGE STAINLESS STEEL, 4 HOLE, WITH COLONY SOFT - 4275.550115 - 1.5 GPM TWO HANDLE FAUCET
SH-1
SHOWER HEAD
AMERICAN STANDARD
FLOWISE SUITE 1662.143
ADA,1.5 GPM HANDHELD SHOWER HEAD, WITH 59" HOSE, 25" SLIDE BAR, THERMOSTATIC MIXING VALVE AND SINGLE HANDLE
HB-1
HOSE BIBB
WOODFORD
MODEL 19
FREEZELESS, ANTI BURST, ANTI -SIPHON
HB-2
HOSE BIBB
WOODFORD
MODEL 24
ANTI -SIPHON, WALL FLANGE AND METAL HANDLE
HR-1
HOSE REEL
COXREELS
SH SERIES
CEILING MOUNTED WITH SPRING DRIVEN AUTO REWIND BRASS NPT SWIVEL INLET, WITH 150' HOSE
FD-1
FLOOR DRAIN
WATTS
FD-100-A
ROUND, 2" DRAIN, EPDXY COATED CAST IRON, ADJUSTABLE STRAINER
FD-2
FLOOR DRAIN
WATTS
FD-100-A
ROUND, 4" DRAIN, EPDXY COATED CAST IRON, ADJUSTABLE STRAINER
FS-1
FLOOR SINK
WATTS
FS-710
8" SQUARE, 4" DRAIN, 6" DEEP, ACID RESISTANT ENAMEL COATED, BOTTOM DOME STRAINER
TD-1
TRENCH DRAIN
WATTS
DEAD LEVEL BK
PRE -SLOPED POLYPROPYLENE TRENCH WITH DUCTILE IRON FRAME; LENGTH AS SHOWN; DRAIN IN CENTER
PLUMBING EQUIPMENT SCHEDULE
SYMBOL
TYPE
MANUFACTURER
MODEL
DESCRIPTION
WM-1
WATER METER
-
-
PER WATER COMPANY REQUIREMENTS; 31 GPM @ 4 PSIG
BFP-1
BACKFLOW PREVENTER
WILKENS
375 XL
REDUCE PRESSURE ASSEMBLY; 31 GPM @ 14 PSIG; LEAD FREE VALVES FOR POTABLE WATER
WH-1
TANKLESS WATER HEATER
NORITZ
NC380-SVASME
8.9 GPM; GAS CONSUMPTION RANGE 22.5 - 380 MBH; CATEGORY III SS 5" POWER VENT
MV-1
MIXING VALVE
BRADLEY CORPORATION
S59-2045
STANDARD THERMOSTATIC MIXING VALVE (TMV45) WITH OPTIONAL CABINET
GM-1
GAS METER
-
-
PER GAS COMPANY REQUIREMENTS; 1,235 CFH @ 7" WC
CP-1
CIRCULATION PUMP
BELL & GOSSET
ECOCIR 19-16
HIGH EFFICIENCY WET ROTO CIRCULATION WITH ECM; 5 GPM @ 10' LEAD; POTABLE WATER; 115V, 60 HZ; CONSTANT PRESSURE
PIPE SIZING CHART
PIPE SIZE
GPM
FIXTURE UNITS
VELOCITY
FLUSH VALVE
FLUSH TANK
1/2"
2
--
1
4
3/4"
7
--
3
5
1"
16
--
12
6
1-1/4"
22
8
25
6
1-1/2"
31
15
60
6
2"
58
70
160
6
NOTES:
1) PIPING NOT SIZED ON FLOOR PLANS SHALL BE SIZED IN ACCORDANCE
WITH PIPE SIZING CHART.
2) PIPE SIZING CHART BASED ON 6 PSI/100 FT MAXIMUM FRICTION LOSS.
3) MAXIMUM VELOCITIES SHALL BE: BRANCHES- 6 FT/SEC
PLUMBING LEGEND
SYMBOL
ABBREV.
DESCRIPTION
SS
SANITARY SEWER OR WASTE B/G
V
VENT
DCW
DOMESTIC COLD WATER
DHW
DOMESTIC HOT WATER
DHWR
DOMESTIC HOT WATER RETURN
CD
CD
CONDENSATE DRAIN
DE
DE
DEIONIZED WATER
DER
DER
DEIONIZED WATER RETURN
DS
DS
DOWNSPOUT
F
F
FIRE MAIN
SPK
SPK
FIRE SPRINKLER
IW
IW
INDIRECT WASTE
G
G
NATURAL GAS (LOW PRESSURE)
MPG
MPG
NATURAL GAS (MEDIUM PRESSURE)
HPG
HPG
NATURAL GAS (HIGH PRESSURE)
ODS
ODS
OVERFLOW DOWNSPOUT
ORW
ORW
OVERFLOW RAIN WATER
RW
RW
RAIN WATER
SD
SD
STORM DRAIN
TP
TP
TRAP PRIMER
FCO
FLOOR CLEAN -OUT
COTG
CLEAN -OUT TO GRADE
WCO
WALL CLEAN -OUT
HB
HOSE BIBB
O
PIPE RISING
PIPE DOWN
S.O.V.
SHUT-OFF VALVE
SHUT-OFF VALVE ON RISE OR DROP
GLV
GLOBE VALVE
CV
CHECK VALVE
BALANCING VALVE
GAS COCK
WHA
WATER HAMMER ARRESTOR
FD
FLOOR DRAIN
FSK
FLOOR SINK
CB
CATCH BASIN
Do
RD
ROOF DRAIN
ORD
OVERFLOW ROOF DRAIN
®
P.O.C.
POINT OF CONNECTION
ABBREV. DESCRIPTION
AFF
ABOVE FINISHED FLOOR
A/G
ABOVE GRADE
B/F
BELOW FLOOR
B/G
BELOW GRADE
CONC.
CONCRETE
CONN.
CONNECTION
CONT.
CONTINUATION
DN.
DOWN
DF
DRINKING FOUNTAIN
FF ELEV.
FINISHED FLOOR ELEVATION
FG
FINISHED GRADE
FH
FIRE HYDRANT
FU
FIXTURE UNIT
FT
FLUSH TANK
FV
FLUSH VALVE
GPM
GALLONS PER MINUTE
HC
HANDICAPPED
I/A
IN ATTIC OR ABOVE CEILING
I.E.
INVERT ELEVATION
LAV
LAVATORY
MH
MANHOLE
MS
MOP SINK
PIV
POST INDICATOR VALVE
RI & C
ROUGH -IN & CONNECT
SS
SERVICE SINK
SH
SHOWER
S
SINK
TYP.
TYPICAL
U/G
UNDERGROUND
U
URINAL
VTR
VENT THRU ROOF
WC
WATER CLOSET
WH
WATER HEATER
W/
WITH
PLUMBING GENERAL NOTES
NOTE NUMBER
NOTE
1
FOR FIRE RATED WALLS AND CEILINGS, SEE ARCHITECTURAL DRAWINGS.
2
FOR FIXTURE HEIGHT AND ACCESSIBILITY REQUIREMENTS, SEE ARCHITECTURAL DRAWINGS
3
ALL INVERT ELEVATIONS REPRESENTED BY - X.XX FT, ARE BELOW FINISHED FLOOR ELEVATION.
4
ALL WORK SHALL CONFORM TO INDIANA PLUMBING CODE.
5
ALL PENETRATIONS THROUGH WALLS, ROOFS, AND FLOORS SHALL BE FIRE STOPPED
LU
Z
LU Q
�
� Z
Q
� W
� z
�U
C-0LU
v
� J
U)
a
Q
�
W 0�
>
U
�
ti
DISCLAIMER:
This is an original design, created by KJG Architecture, Inc. The
concepts, ideas, plans and details are the sole property of KJG
Architecture, Inc. None of the aforementioned shall be used by or
disclosed to any person, firm or organization for any purpose without the
prior written permission of KJG Architecture, Inc.
PROFESSIONAL SEAL:
Q ,OFESS/O
ti
NO. PE10910442 z
m
m
s�gTF
OF
PROJECT DATE:
09/ 14/2018
No.
DESCRIPTION:
DRAWN
BY:
DATE
ISSUED:
PROJECT NUMBER:
DRAWN BY:
DRAWING TITLE:
PLUMBING NOTES
AND SCHEDULES
SHEET NUMBER: