HomeMy WebLinkAboutE70.6 Elec SchedulesJ FEEDER AND BRANCH CIRCUIT C NOTE'. SEE DRAWINGS SCHEDULE FOR NHgER OF WIRES IN E D U L EMERUN FEEDERIBRANCH CIRCUIT DESIGNATION CONDUCTOR SIZE TYPE CABLE CONDUIT PHASE B NEUTRAL EQUIPMENT GROUND ALUMINUM COPPER F20 12 12 X NM F30 10 10 X NM F40 50 8 10 X NM F60 6 10 X MC F70 80 4 8 X MC F90 3 8 X MC F100 3 8 X MC F125 110 4 X MC F150 310 4 X 2 112" F175 410 4 X 2 112" F200 250 4 X 3" F225 300 2 X 3" F250 350 2 X 3" F300 Soo 2 X 3-112" F350 2 RUNS OF 410 1 X 2.112" F400 2 RUNS OF 250 1 X Y EACH F600 2RUNS OF 500 210 X 3.1121EACH FB00 3RUNS OF 400 310 X 3 112 EACH F1000 3 RUNS OF 600 410 X 4" EACH F1200 4 RUNS OF 500 250 X 3 112" EACH F1600 5 RUNS OF 600 350 X 4" EACH F2000 6 RUNS OF 600 400 X 4" EACH F2500 7 RUNS OF 750 600 X 5" EACH F3000 8RUNS OF 750 600 X 5" EACH NOTES'. 1. 20 A BRANCH CIRCUITS SHALL BE SIZED FOR VOLTAGE DROP. WIRE SIZES ARE NOT INDICATED ON THE DRAWINGS TO COMPENSATE FOR VOLTAGE DROP, FOR THESE CIRCUITS, CONTRACTOR SHALL UTILIZE WIRE SIZE SHOWN ABOVE FOR DISTANCES LISTED ABOVE. 2. VOLTAGE DROP WIRE SIZES WILL BE STRICTLY ENFORCED. CONTRACTOR SHALL SUBMIT A LIST OF CIRCUITS THAT WILL EXCEED THE DISTANCES ALLOWED AND INDICATE WIRE SIZE TO BE USED PRIOR TO ANY WIRE BEING INSTALLED. 3. DO NOT SHARE NEUTRAL CONDUCTORS FOR ANY BRANCH CIRCUITS. ALL BRANCH CIRCUIT SHALL HAVE SEPARATE, INDEPENDENT NEUTRAL CONDUCTORS. 4, ALL BRANCH CIRCUIT WIRING SHALL BE NM AND MC CABLE WITH THE FOLLOWING EXCEPTIONS'. a. ALL WIRING THAT IS INSTALLED IN AREAS THAT DO NOT HAVE CEILINGS OR WHERE WIRING WOULD BE EXPOSED SHALL BE INSTALLED IN CONE LIT COMPLETE. 5, ALL CONDUIT PENETRATIONS THRU THE FLOOR SLAB SHALL BE MADE WITH CAUTION, CONTRACTOR SHALL COORDINATE ALL HOLE LOCATIONS WITH STRUCTURAL ENGINEER PRIOR TO CUTTING ANY NEW HOLES. NEW HOLES SHALL BE ADJUSTED AS REQUIRED TO MISS REBAR AS DETERMINED BY THE STRUCTURAL ENGINEER. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Carmel (� �VT�t2'�DetiYWMr_ DATE: \ 02/12/19 Branch Panel: LOT70A Location: GARAGE 104 Supplied From: TOWNHOME METER CENTER MouN Suface Enclosure Type: Type General Panel Comments: PROVIDE WITH HIOA SUB FEED BREAKER Voltage: Phase: Wlre: Ground: 120240 Single 1 3 Yes Branch: Normal A.I.C.Ratlni TBD Marge'. MCB MNn Ratlne: 400A Cimult Number Circuit Description Trip Poles A B Poles Trip Circuit Description Cimuit Number 1 LET (SHUNT TRIP) 30A 3 0 0 1 20A BASEMENT LIGHTING (1 2 3 0 0 1 2DA 1ST FLOOR LGHTING III 4 5 0 0 1 20 A 2ND FLOOR UGHTWG (AFCI) 6 7 LET LIGHTING AND CONTROLS III I GFCO 2DA 1 0 0 1 ZIA WATER HEATER( GFCI I AFCO 8 9 TESU+CHARGING OUTLET ZIA 2 0 0 1 20 A ALARM PANEL (AFCI) 10 77 0 0 1 ID q LOW VOLTAGE PANEL (AFCI) 72 13 SUMP PUMP(G FCI I AFCI) 20A 1 0 0 1 20A DATA RACK 111 14 15 SUMP PUMP(G FCI I AFCI) 2DA 1 0 0 1 ZIA DATA RACK 111 16 17 GARAGE HEATER 30 A 2 0 0 1 20 A BASEMENT MECHANICAL RECS (AFCI) 18 19 0 0 1 1 ZI A BASEMENT FURNACE 111 20 27 RANGE 50 A 2 0 0 1 20A BASEMENT WIC PECS(AFCCD 22 P3 0-1 0 1 2D A BASEMENT STUDY RECS Mi 24 25 27 OVEN 30 A 2 0 0 1 20 A BASEMENT HALL RECS (gFCI) 26 0 0 1 2D A GARAGE DOOR OPENER (GFCI I AFCO 28 29 2ND FLOOR REFRIGERATOR III 20A 1 0 0 1 20A GARAGE FEDERTACIES(GFCI I AFCO 30 31 2ND FLOOR UIC REFRIGERATOR (I 2DA 1 0 0 1 2DA I 1ST FLOOR BATH GFCI I AFCI) 32 33 GAD FLOOR UIC WINE REFRIGERATOR III 20A 1 0 0 1 20A 1ST FLOOR FAMILY ROOM PECS 111 34 35 2ND FLOOR ICE MACHINE(GFCI I AFCO 2DA 1 0 0 1 ZIA 1ST FLOOR FAMILY ROOM RECS 111 36 37 GAD FLOOR HOOD AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR FAMILY ROOM DID REF 111 38 39 2ND FLOOR DISHWASHER(GFCI I AFCO 2DA 1 0 0 1 ZIA 1-3 FRONT EXTERIORRECEPTACLES (GFCIIAFCI) 40 41 GAD FLOOR GARBAGE DISPOSAL(GFCI I AFCO 20A 1 1 0 0 1 20A SPARE(AFCI) 42 43 2ND FLOOR ISLAND RECS(GFCI I AFCI) 2DA 1 1 0 0 1 1 ZIA SPARE(AFCI) 44 45 GAD FLOOR KITCHEN PECS(GFCI I AFCO 20A 1 0 0 1 1 20A SPARE(AFCI) 46 47 2ND FLOOR KITCHEN PECS(GFCI I AFCO 2DA 1 0 0 1 ZIA SPARE(AFCI) 48 49 GAD FLOOR KITCHEN PECS(GFCI I AFCO 20A 1 0 0 1 20A SPARE(AFCI) 50 51 2ND FLOOR BATHROOM(GFCI I AFCO 2DA 1 0 0 1 ZIA SPARE( GFCI I AFCO 52 53 GAD FLOOR DINING RECS(AFCI) 20A 1 0 0 1 20A SPARE( GFCI I AFCO 64 55 2ND FLOOR LIVI NG ROOM RECS III 2DA 1 0 0 1 ZIA SPARE( GFCI I AFCO 56 57 12ND FLOOR LIVI NG ROOM PECS III 20A 1 0 0 1 20A SPARE( GFCI I AFCO 58 59 12ND FLOOR FIRE PLACE III 2DA 1 0 0 1 2DA SPARE( GFCI I AFCO 60 LOT70B(SUB FEED) 0 0 Total Load: 0.0 kVA 0.0 kVA Load Summary: Load Classlflcallon Connected Load Demand Factor Estimated Demand Panel Totals Total Conn. Load: OVA Total Eat. Demand: OVA Total Conn. Current: 0 A Total Est. Demand Current 0 A Remade: Branch Panel: LOT70B Location: MECH 400 Supplied From: LOT70A MouN Surface Enclosure Tvoe: Type1 General Panel Comments: Voltaoc: 120240 Singe Phase: 1 li 3 Ground: Yes Branch: Norma' A.I.C. Rating: TBD MaiN�pe'. MILO Mein Rating: 200A Cimult Number Circuit Description Trip Poles A B Poles I Trip Cimuit0eseription Cimuit Number 1 3 4TH FLOOR CONDENSER 40A 2 0 0 1 1 20q 13RD FLOOR LIGHTING (AFCI) 2 0 0 1 1 20q 14TH FLOOR UGHTING 111 4 5 7 dTH FLOOR CONDENSER 40A 2 0 0 1 20q 13RD FLOOR BEDROOM PECS 111 6 0 0 1 20q 13RD FLOOR BEDROOM RECS (AFCI) 8 9 3RD FLOOR DRYER 30 A 2 0 0 1 20A 3RD FLOOR BATHROOM(GFCI I AFCI) 10 77 0 0 1 20q 3RD FLOOR BATHROOM IGFCIIAFD) 12 13 3RD FLOOR BATH HEATED TI LE 20A 2 0 0 1 20A 3RD FLOOR WASHER(GFCI I AFCO 14 15 0 0 1 20A 3RD FLOOR UIC REFRIGERATOR 111 16 17 3RD FLOOR CLOSET HEATED TILE 20A 2 0 0 1 20A 3RD FLOOR CLOSET PECS(AFCCI) 18 19 0 0 1 20A 3RD FLOOR HALL RECS( AFCI) 2D 21 4TH FLOOR DECK HEATER(GFCI I AFCO 20A 1 0 0 7 20q 4TH FLOOR DECK RECS IGFCIIAFD) 22 23 4TH FLOOR DECK HEATER(GFCI I AFCO 20A 1 0 0 1 20A 4TH FLOOR BEDROOM PECS(AFCI) 24 25 4TH FLOOR DECK HEATER(GFCI I AFCO 20A 1 0 11 0 1 20A 4TH FLOOR BATHROOM( GFCI I AFCO 25 27 4TH FLOOR FURNACE 111 20 A 1 0 0 1 1 20 A 4TH FLOOR HALL RECS III 28 29 SPARE(AFCI) 20A 1 0 0 1 20q 14TH FLOOR UIC REFRIGERATOR 111 30 31 SPARE(AFCI) 20A 1 0 0 1 1 20A 4TH FLOOR MECHAN ICAL PECS (I 32 33 SPARE(AFCI) 20A 1 0 0 1 20A SPARE(GFCI I AFCI) 34 35 SPARE( GFCI I AFCO 20A 1 0 0 1 20A SPARE GFCI I AFCI) 36 37 PROVISION 0 0 PROVISION 38 39 PROVISION 0 0 PROVISION 40 41 PROVISION 0 0 PROVISION 42 Tolel Lead: 0.0 kVA OO kVA Load Summary: Load Classlflcallon Conneced Load Demand Factor Estimated Demand Panel Totals Total Conn. Load: OVA Total Est Demand: OVA Total Conn. Current: 0 A Total Est Demand Current: 0 A Remarks: �7RB 1201240 IF3W 200A MLO F200 I— LOT]OA 1201240 1PdW 400A MCB — F400 I FOURTH FLOOR I i THIRDFLOOR TOSE, OME METER CENTER CIRCA, T BREAV,1 PHASE, SWIPE METER CENTER WITH UT BR MAIN CIRCUIT BREAKER AND FOUR REAKERT, 1 ME I 1PH SOCKET BRANCH UNITS WITH BREAKERS CIRCUITBREAKERPER METERSOCKET. LABEL METER BREAKERS PER UTILITY COMPANY REQUIREMENTS SECONDFLOOR I ❑ ❑ O ❑ O ❑ O O FIRST FLDOR L — ❑ O ❑ I O TU ILM 120124OV, 11 BUILDING EXTERIOR MNMMM — RISER DIAGRAM NOTE: UNIT PANEL FEEDERS TO BE ROUTED UNDERGROUND INTO BUILDING FROM BASEMENMETER CENTER AND UP THROUGH WALLS TO PANELS. — — T DELECTRICAL RISER DIAGRAM -LOT 70 NO SCALE II1IIIII1 CERTIFICATION: y'�.�pM1A. y,(%S �� p619 [q Obi �y 1 AFAE.C., REV //Alm ALL INFORMATION CONTAINED IN THIN DOC D ME HIT 19 UNAUTHORIZED USE OF THESE DOCUMENTS 15 NOT PERMITTED UNNINNINNIN ARCHITECT BLACKLINE SLACKHRESINDARE MET 31 TIES 70 M.E.P. GENESIS ENGINEERING GROUP 91 SOUTH MAIN TURN IT SUITE TER STRUCTURAL SCHWARZ ENGINEERING GROUP OF OM H 33 U) LU J 0 LU W 0 2 z U W o a Z fn rn ° E J LU E: R a Z o U m 01) C s `N r m 2 U oa 06 LU on 0 0 JNEER a C W N UNNINNINNIN DRAWN'. CHECKED'. JAW JAW REVISION d. Monon and Main Brownstone Interior Remodel — Units 90, 60,70,50 111112019 E70=6