HomeMy WebLinkAboutM70.3 Condenser FanJ
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of CaINDeI (�
�VT�'�DNtiYWML_
DATE: \ 02/12/19
HEIGHT ABOVE ROOF DECK.
MAKE HEIGHT AS LOW AS /
POSSIBLE BUT NOT LESS
THAN 2 0
ALUMINUM EXHAUST H000
WITH SWING OUT DAMPER.
4" DISCHARGE SIZE
(NOT 2 112").
DRYER VENTDETAIL70
NO SCALE
HIGH TEMPERATURE
SILICONE SEAL
STAINLESS STEEL HOOD 18
GAUGE, FORCEFITTOVENT
WOOD NAILER -
MINIMUM 3" CLEAR FROM
VENT TO METAL LINER
15" TALL SQUARE CURB -
WITH METAL LINER
ROOF CONSTRUCTION —
PACKED INSULATION
METALESCUTCHEON -
FORCE FIT TO VENT
STRUCTURAL FRAME AROUND
OPENING. SEE STRUCTURAL
DRAWINGS OR PROVIDE
<4"X4"X5116"
SEAL ALLEXPOSED SEAMS WATERTIGHT
ANCHOR HOOD TO CURB, 6" O.C.
,HT- 8" MINIMUM. TALLER
AS REQUIRED FOR
ROOFING WARRANTY
� FINISHED ROOF LINE
FLEXIBLE SEALANT RATED FOR 400-F
STEEL SLEEVE
DRYER VENT, CONSTRUCTED OF
MINIMUM 26 GAUGE GALVANIZED
SHEETMETAL WITH NO SCREWS OR
DAMPERS THAT COULD CATCH LINT.
DRYER DUCT THROUGH ROOF
SPIN IN FITTING AT BRANCHIMAIN
CONNECTION.
ATTACH FLEXIBLE DUCTWORK
WITH DRAWBAND AND SEAL
INSULATION AND VAPOR BARRIER
TO FSK TAPE.
SUPPLY DIFFUSER
GENERAL DETAIL NOTES
INSTALL MANUAL VOLUME DAMPER
AT ALL BRANCH DUCTS. PROVIDE
2" EXTENDED OPERATOR HANDLE
FOR INSULATED DUCTS.
FLEX DUCT -MAXIMUM 80
LENGTH AND NO MORE THAN
TWO (2) 90- BENDS,
INSULATE BACK OF SUPPLY
DIFFUSERS WITH 1" MINERAL FIBER
INSULATION WITH FSK JACKET.
TAPE AND SEAL INSULATION
VAPOR BARRIER.
CEILING
A. FLEXIBLE DUCTWORK BENDS SHALL NOT BE LESS THAN 15 TIMES THE DUCT DIAMETER,
B. INSULATION AND VAPOR BARRIERS PRESENT ON FACTORY FABRICATED DUCTS SHALL BE FITTED OVER
THE CORE CONNECTION AND SHALL BE SECURED WITH A DRAW BAND, TAPE AND SEAL ALL JOINTS AND
SEAMS WITH FSK TAPE TO MAINTAIN VAPOR BARRIER.
C SUPPORT FLEXIBLE DUCTWORK FROM STRUCTURE, DO NOT SUPPORT FLEXIBLE DUCTWORK FROM
ADJACENT ABOVE CEILING UTILITIES (DUCTWORK, PIPING, CONDUITS, ETC.(
�1 CEILING DIFFUSER/GRILLE DETAIL 70
NO SCALE
TAG
AIR TERMINAL TYPE
DIFFUSER/REGISTER/GRILLE SCHEDULE
THROW
FACE (FT. BASED ON MAX.
NECK SIZE CFM VELOCITY OF 50 MAX TOTAL A.P.O.
SIZE (IN.( MATERIAL RANGE FPMI NC (IN. WG.I
DESIGN REFERENCE
MANUFACTURER MODEL
NOTES
SR1
SUPPLY REGISTER
1016"
10XV
ALUMINUM
0-150
11
20
0.040
PRICE
640
1,2,3
SR2
SUPPLY REGISTER
14"x8
14"x6"
ALUMINUM
155-200
13
20
0.040
PRICE
640
1, 2,3
FSR1
LINEAR BAR FLOOR GRILLE
17x4"
17x4"
ALUMINUM
0-125
15
20
0.040
PRICE
LEON
2,S5
FSR2
LINEAR BAR FLOOR GRILLE
12"x6"
12"x6"
ALUMINUM
130-200
17
1 20
1 0.040
1 PRICE
LEON
2,S5
RGi
RETURN GRILLE
8NIT
8"x10"
ALUMINUM
0-200
-
20
0.040
PRICE
630
1,3,4
RG2
RETURN GRILLE
20N18"
20"x18"
ALUMINUM
750-1000
-
20
0.040
PRICE
630
1,S4
EGi
EXHAUST GRILLE
6"x6"
6NF
ALUMINUM
20-75
20
0.040
PRICE
630
1, 3,4
TOM
1. BRANCH DUCT RUNOUT TO THE DIFFUSER SHALL BE THE SAME SIZE AS THE DIFFUSER NECK UNLESS NOTED OTHERWISE ON THE DRAWINGS.
2, ALL SUPPLY DIFFUSER BACKPLATES SHALL BE INSULATED WITH A MINIMUM OF I" INSULATION . INSULATION MAY BE FACTORY OR FIELD APPLIED.
3. PROVIDE FRAME STYPLE APPROPRIATE FOR CEILING TYPE (I.E. LAY IN, SURFACE MOUNT, SIDEWALL, ETC.(. REFER TO DRAWINGS AND ARCHITECTURAL
REFLECTED CEILING PLANS FOR LOCATIONS.
4. PLEN UM RETURN GRILLES SHALL HAVE A RETURN BOOT WITH RETURN DAMPER ATTACHED TO THE BACK.
5, 118" BARS, 112" BLADE SPACING, 150 DEFLECTION.
AIR COOLED CONDENSING UNIT SCHEDULE 70
MARK
COOLING
CAPACITY (BTUH)
MIN. SEER
i ELECTRICAL DATA
UNIT WEIGHT
(LESS)
BASIS OF DESIGN
MAX SOUND
RATING (dB)
NOTES
MCA
MOCP
VOLTS
PHASE
MANUFACTURER
MODEL
ACCU-1-70
36,000
15
1 23
35
208
1
240
TRANE
4TTV0036A10QA
70
1,2
ACCU-2-70
24,000
15
1 17
25
1 208
1 1
1 230
1 TRANE
4TTV0036A10GA
1 66
1 LZ
NOTES.
I. WHAREiRGEAANT.
2. AXTVSHORT CYCLE TIMER.
FAN SCHEDULE
70
AIRFLOW
ES.P.
ELECTRICAL REQUIREMENTS
DESIGN REFERENCE
TAG
LOCATION
(CFM)
(IN.W.G.)
POWER (VQ
FAN TYPE
FAN RPM
DRIVE
AMPS
VOLT/PHASE
WEIGHT (LBS)
MANUFACTURER
MODEL
NOTES
EF-70
MECHANICAL
150
0.3
141
INJUSE CENTRIFUGAL
895
DIRECT
1.7
1 120/1
12
GREENHECK
CSP-6150
1,2,3
FURNACE
SCHEDULE 70
MARK
CONFIGURATION
NOMINAL
TONS
AIRFLOW
(CFM)
FAN DATA
COOLING DATA
HEATING DATA
ELECTRICAL DATA
BASIS OF DESIGN
UNIT WEIGHT
(LIENS)
NOTES
ESP
DRIVE
HP
TOTAL BTU
EAT OB
(°F)
EAT WB(°F)
BTU INPUT
BTU OUTPUT
EAT OB
(°F)
AFUE
(%N)
MCA
MOCP
VOLTS
PHASE
MANUFACTURER
MODEL
F-1-70
VERTICAL UPFLOW CONDENSING GAS
3.0
1050
Q3
DIRECT1
Q5
36.000
1 75
1 63
32.000
30.000
1 70
1 95
11.1
15
1 120
1 1
TRANE
I TUHMBOBOACV3VB
170
1.2.3.4.6.7.8
F-2-70
I VERTICALDOWNFLOW CONDENSING GAS
1 2.5
1 900
0.3
DIRECT
I Di
36.000
1 75
1 63
32.000
30.000
1 70
1 95
11.1
15
1 120
1 1
TRANE
I TDHMB0BDACV3V1B
170
1.2.3.5.6.7.8
NOTES'.
I. HEAT RATING BASED ON 40% LOW INPUT
$. VARIABLE SPEED BLOWER.
S PROVIDE I- TPAPPED CONDENSATE PIPED TO FLOOR DRAIN.
4. DR COIL CASED FOR UPPLOW.
s. DR COIL CASED FOR ODWNFLOW.
6. RETURN AIR SUB BASE BY MANUFACTURER.
1. CONCENTRIC VENT SET BY MANUFACTURER.
S. SPACE TEMPERATURE MEASURED VIA COMMON RETURN AIR SENSOR.SYSTEM MALL RESPOND TO MOST
RECENT INPUT FROM ANY CONNECTED THERMOSTAT.
l I.
I III III
CERTIFICATION:uryµ��
l}#P\FPMO1AG. 1yJ1 �
A '
A
/m//�Y�
¢c` ALL INFORMATION CONTAINED IN FOR DOCJMENT 15
CONSIDERED TO BE ROT" CONFIDENTIAL AND
PROPRIETARY INTELLECTUAL PROPERTY OF SLACKLINE
STUDIO AND SHALL NOT BE CODES REPRODUCED
DISTRIBUTED OR ASSIGNED TO A TURN PARTY A FRONT
DNAGNORICED USE OF THESE DOCUMENTS 15 NOT
PERMUTTED
ARCHITECT
BLACKLINE
SLACERINESTUDIO GET
3178)3 BAR
aiiiiiiiiin
M.E.P.
GENESIS ENGINEERING GROUP
aiiiiiiiiin
STRUCTURAL
SCHWARZ ENGINEERING GROUP
v!
J_
Q
W
0
0
Z
a
U)
W
J
W UU
= U
z
(, w 0 z
TU
U c E
J w
V z 0
CO U)
Z 0 c IZ
a W
OD 06
(M) CD c a
TANI 0 0
W c :_
DRAWN'. CHECKED'.
Author Checker
Motion and Main Brownstone
Interior Remodel — Units 90,
60,70,50
111112019
IIIIIIIIIIE
® M70.3