i1 FIRST FLOOR POWER PLAN
Ire'=r-o'
73 i
i
Ems® ®I
TSi
DD
3T
ATS-2J
EDP
_
B 1311E I iL MDP
iT 07 2L
P
3P
�T
2P
4P
5P
1@7
Y
i1 ENLARGED FIRST FLOOR ELECTRICAL ROOM
GENERAL NOTES
A. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS AND ADDITIONAL GENERAL NOTES.
PLAN NOTES
300
MOUNT NEW BOOSTING TRANSFORMER FROM STRUCTURE ABOVE.
301
INSTALL NEW IDEA BREAKER IN AVAILABLE SLOT IN EXISTING DISTRIBUTION PANEL.
MATCH EXISTING MANUFACTURE AND MID RATING FOR NEW BREAKER.
302
INSTALL NEW 30P 48WAC BRANCH PANEL IN LOCATION SHOWN. REFER TO RISER
DIAGRAM ON SHEET E700 FOR ADDITIONAL INFORMATION.
303
INSTALL NEW FLOOR BOX AT SAME LOCATION AS FLOOR BOX REMOVED DURING
DEMOLITION. CONNECT COMPLETE TO EXISTING CIRCUIT MADE AVAILABLE DURING
DEMOLITION.
304
CONNECT EXISTING FURNITURE WHIP TO NEW SYSTEMS FURNITURE BEING
INSTALLED. COORDINATE TERMINATION AT FURNITURE WITH MANUFACTURER.
HOME -RUN AND CIRCUITING INFORMATION IS EXISTING AND SHOWN FOR
REFERENCE.
305
CONNECT (2) OUT OF THE EXISTING (3) EXISTING FURNITURE CIRCUITS TO NEW
SYSTEMS FURNITURE BEING INSTALLED. COORDINATE TERMINATION AT FURNITURE
WITH MANUFACTURER. REMOVE WIRING FOR THIRD CIRCUIT LOCATED AT THIS
FURNITURE FEED AND MAINTAIN IN AREA FOR REUSE IN THIS AREA.
306
INSTALL NEW FURNITURE CONNECTION BACK BOX AND WHIP AT LOCATION SHOWN
TO CIRCUITS INDICATED FOR NEW SYSTEMS FURNITURE BEING INSTALLED.
COORDINATE TERMINATION AT FURNITURE WTH MANUFACTURER.
307
CONNECT EXISTING DUPLEX RECEPTACLE TO NEW CIRCUIT SHOWN.
308
RECONNECT EXISTING DUPLEX RECEPTACLE CIRCUIT TO NEW PANEL AS SHOWN.
309
GARBAGE DISPLCSAL. COORDINATE MOUNTING OF CONTROL SWITCH WITH
ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH -IN.
310
NEW POINT OF USE WATER HEATER. MOUNT DISCONNECT SWITCH NEAR UNIT
311
INSTALL (4)4'C+(1)4'C SPARE+ (1) 1'D FOR CONTROL WIRING. CONDUIT TO BE
DIRECT BURY TYPE AND STUB UP UNDER GENERATOR AND NEAR EXTERIOR WALL
OF BUILDING. CONDUIT TO TRANSITION INTO THE BUILDING NEAR BASE OF WALL.
INSTALLED.
313
GENERATOR ANNUNCIATOR PANEL.
314
PROVIDE ELECTICPL CONNECTION TO ELECTRIC DUCT COIL BEING INSTALLED NEAR
THIS LOCATION. COORDINATE WITH MECHANICAL CONTRACTOR PRIOR TO
ROUGH -IN.
315
PROVIDE SWITCH FOR EXHAUST FAN. CONNECT COMPLETE TO RECEPTACLE
CIRCUIT SHOWN.
316
PROVIDE POWER CONNECTION TO SPLIT -UN IT COOILING SYSTEM BEING INSTALLED
NEAR THIS LOCATION. COORDINATE EXACT PLACEMENT WITH MECHANICAL TRADE
PRIOR TO ROUGH -IN.
317
INSTALL NEW 42P 208VAC BRANCH PANEL IN LOCATION SHOWN. REFER TO RISER
DIAGRAM ON SHEET E700 FOR ADDITIONAL INFORMATION.
318
EXISTING 100A DISCONNECT SWITCH FOR RACK MOUNT UPS.
319
NEW LOCATION OF EXISTING UNIT HEATER. RECONNECT TO EXISTING CIRCUIT
3 F
POWERCONNECTIONFORDOORA CES EO IP ENT. C RDI AT WITH DR
ACCESS VENDOR PRIOR TO ROUGH -IN.
BSA
BSA LifeStructures
9365 Counselors Row Suite 300
Indianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www. bsal'rfestructures.00m
VISIONFIRST
Indiana Lions Eye Bank
OFFICE AND
LAB
RENOVATION
CLIENT PROJECT NO. - 21160001
CONSTRUCTION
DOCUMENTS
T KEYPLAN
nIAN NORM
MARK
DATE
1 DESCRIPTION
1
011142019
ADDENDUM 1
2
1 011222019
JADDENDUM2
FIRST FLOOR POWER
PLAN
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Carmel
DATE: 02/20/19
DATE DEC. 19, 2D18
BSALS PROJECT NO. 21160001
E310