HomeMy WebLinkAboutH 700F.
EF-1
HORIZONTAL RUN
N BETWEEN BAR
JOISTS
l
1 fr(r/ 14JX14
RETLRN
DDcr
Zp
CAPPED
EXHAUST FAN 1 SECTION
iI
SAFETY
RELIEF
VALVE
FROM
EQUIPMENT
SERVED
SEE PLANS FOR LINE SIZE.
91
DRAIN FROM
VALVE BODY
PLAN NOTES:
I. LARGER SIZES MAY BE FLANGED
VENT PIPE UP THRU ROOF
y DRIP PAN ELBOW
I—^ "Y"FI—TTING
"'�+"'�L RUN 314"DRAIN
LINE TO NEAREST
UNION (TYPICAL) FLOOR DRAIN
SAFETY RELIEF VALVE WITH DRIP PAN ELBOW PIPING DETAIL
NO SCALE
RELEASED FDR CDN
Subject to compliance with
of State and local
SUPPLYAIR
SUPPL
LAWN AREAS
CONCRETE SUPPORT PAD
PAVEMENTAREAS
6' CONCRETE SLAB
WIM4 (tg IT EW 1 p4 CENT,
N
(EPDXY COATED) — (ALL SIDES)
FINISHED
PROVIDE ISOLATION JOINT
GRADE
GRADE
\
WHEN SUPPORT PAD ABUTS
CONCRETEEPAVE PAVEMENT
III,I UII
II
"'
II II II
4" COMPACTED,
DRAINAGE FILL
—
• f
•
�V
PLAN NOTES
1. CONTRACTOR TO COORDINATE SIZE,LOCATION, FINISHED GRACE, CURB PENETRATIONS, AND
POSITIVE DRAINAGE REQUIREMENTS WITH EQUIPMENT PROVIDER.
2, PROVIDE STEEL TROWEL FINISH ON EXPOSED SURFACES AND SLOPE TOP SURFACE TO PROVIDE
POSITIVE DRAINAGE.
H1
EQUIPMENT SUPPORT DETAIL
NOSCALE
1-12- COPPER TUBE OR SIZE PER
MANUFACTURERS RECOMMENDATIONS
COVER PLATE AND DUCTWORKOR
GASKET (TYPICAL) AHU PLENUM
ELECTRIC I 11 r
HUMIDIFIER
6" MIN. (TYP), -� U j ` MANIFOLD SUPPORT
lku1 u/ (TYPICAL)
12'
COPPER
PLAN NOTES
I, LOCATE DISPERSION TUBE PER MANUFACTURER'S RECOMMENDATIONS
2. CONDENSATE LINE TO GRAVITY DRAIN WITH NO LIFTING. COORDINATE PIPE ROUTING WITH ALL TRADES.
INSTALL THIS PIPE PRIOR TO ANY OTHER INSTALLATIONS OF PIPE, CONDUIT, DUCT OR CEILING. SEE
PLANS FOR CONDENSATE LINE ROUTED TO CONDENSATE COOLER LIKE DRI-STEEM DRANE-KOOLER.
3. SEE STEAM TRAP DETAIL
ELECTRIC HUMIDIFIER PIPING DETAIL
NO SCALE
UWM77m
ACCESS ACCESS I z n ACCESS
DOOR DOOR ADOORS DOOR
w
L__J
i
HOTGAS DXCOIL
REHEAT COIL
®
CONTROL
PANEL
SUPPLYAIR
yQO
0
—
LL
VU
o �
x
RETURNAIR
®
�u
W w
®
Ja
z �
STRUCTIDN
all regulations
99
Codes
City of Cannel
�VTI�\Dw�1DML
DATE: 02/20/19
4 AHU 1
PLAN NOTES
I. MOUNT WALL EXHAUST GRILLE WITH BOTTOM 12'A.F.F.
�1 LOW EXHAUST/RETURN DETAIL
NO SCALE
STRAINER CHECKVALVE
GATE VALVE Z
GATE VALVE
CAPPED
NIP
PLE
WITH
CNPPLE
PLAN NOTES:
1. INSTALL 112' BLOW OFF VALVE ON STRAINER WITH NIPPLE AND CAP.
8 STEAM TRAP DETAIL
NO BE
ROUND BRANCH DUCT TO MAIN PLENUM TO BE EXTERNALLY INSULATED
,�
(SEE SCHEDULE FOR SIZE) —'`J
SHEETMETAL PLENUM SHALL BE
SUPPORTED INDEPENDENTLY FROM
STRUCTURE (NOT SUPPORTED BY
CEILING) INSIDEOF PLENUM
O INSULATED FLEXIBLE" SHALL BE PAINTED FLAT BLACK
DUCTWORK \
DUCTWORKIDIFFUSER SHALL BE %/\\ PLENUM BOXHEIGHT=
SUPPORTED INDEPENDENTLY FROM ` > ROUND DUCT DIA+4-
STRUCTURE (NOT SUPPORTED BY CEILIN NIDUCTWORKIDIFFUSER SHALL BE SUPPORTED
OUTDOOR
SQUARE DIFFUSER/GRILLE —" INDEPENDENTLY FROM STRUCTURE
AIR
(NOT SUPPORTED BY CEILING) INSIDE
SQUARE DIFFUSER OBSTRUCTED INSTALLATION OF PLENUM TO BE PAINTED FLAT BLACK.
ROUND BRANCH DUCT TO MAIN
_
(SEE SCHEDULE FOR SIZE) EXTERNALLY
INSULATE PLENUM.
INTERNAL INSULATION
ISNOTALLOWED.
O1 INSULATED FLEXIBLE DUCTWORK
/ PLENUM BOX
ROUND BRANCH C2)-- %j HEIGHT =ROUND
AHU 1 SITS ON CONCRETE PAD.
DUCT TO MAIN %// DUCT DIAMETER «4'
SEE DETAIL
(SEESCHEOJLE INSULATED / // ADJUSTAIR
IANCHEQUIPMENT
ANCHORED
AHU TANCHOREO TO PAC.
FOR SIZE) FLEXIBLE �.+ �% PER SCHEDULE AND PLANS
EDULE AND PLANS
DUCTWORK `` SLOT DIFFUSER
(THREE SLOT SHOWN)
SLOT DIFFUSER INSTALLATION
DUCT RADIUS TO
DIFFUSER MIN 2 DUCTWORKIDIFFUSER SHALL BE
DUCT DIAMETERS SUPPORTED INDEPENDENTLY
� FROM STRUCTURE(NOT
lam / SUPPORTED BY CEILING)
MI'MIN.
OUTDOOR AIR
SQUARE TO ROUND TRANSITION,
EXTERNALLY INSULATE BACK OF DIFFUSER
`— SQUARE DIFFUSER
PLAN NOTES SQUARE DIFFUSER INSTALLATION
1. AMINIMUM OF FIVE(5) FEET LENGTH OF FLEXIBLE DUCT SHALL BE PROVIDED TO EACH DIFFUSER. DUCTWORKSHALL CONTAIN 180.OF
BENDING. FLEXIBLE DUCTWORK LENGTH SHALL NOT EXCEED EIGHT(8) FEET EXCEPT WHERE SPECIFICALLY NOTED. FLEXOUCTSHALLNOT
CONTACT CEILING AND SHALL BE PROPERLY SUPPORTED BOAS TO HAVE NO KINKS.
2. TIE-WRAPCONNECT FLEX DUCT HELICAL COIL TO ROUND METAL DIFFUSER NECKAND TO ROUND METAL DUCTWORKAT OTHER END OF FLEX
DUCT. PULL FLEX DUCT VAPOR BARRIER OVER LOWER TIE -WRAP AND INSTALL SECOND TIE -WRAP OVER THE VAPOR BARRIER. INSULATEMETAL
DUCT OR DIFFUSER OVER TOP OF SECOND TIE -WRAP AND INSTALL INSULATOR'S TAPE ON EDGES.
3. PROVIDE A MINIMUM OF NB'OF STRAIGHT, VERTICALLY ORIENTED, FLEXIBLE DUCT AT THE DIFFUSER NECK. IF UNABLE TO PROVIDE STRAIGHT
DUCT RUN THEN PROVIDE OBSTRUCTED INSTALLATION PLENUM IN ACCORDANCE WITH THIS DETAIL,
DIFFUSER DETAIL
NO SCALE
MOTOR
DISCONNECT
SWITCH
BIRDSCREEN /
}
FOAM RUBBER GASKET �
APPLIED TO UNDERSIDE
OF FAN CURB CAP
FAN CURB CAP
SEE ROOF CURB DETAIL
ROOF INSULATION
SECURE FAN TO CURB WITH SHEET
METAL SCREWS IT O.C. ALL AROUND
DOME
— DISCHARGE APRON
CURB O
— ROOF INSULATION
ROOF DECK
ROOFING TO EMEND UP AND
OVER TOP OF CURB
L CURB FASTENING FLANGE
SECURE CURB TO ROOF J
ROOFDECK
USING FASTENERS AT IT O.C.
I
SEAL OPENING AIRTIGHT
BEFORE APPLYING ROOFING
I
ROOF OPENING
INTERNALLY LINE DUCTWORK
I
WITH 1' FIBERGLASS
MINIMUM 18 GAUGE DUCT
INSULATION (MIN R-3 WIN OR
_ J
HVAC INSULATION SPEC,
WHICHEVER IS HIGHER)
DAMPER O
PLAN NOTES
1. CURB AND EXHAUST FAN SHALL BE FROM SAME MANUFACTURER.
2, DAMPER SHALL BE TWO WHEEL DIAMETERS FROM INLET CONE, ALL DUCT CONNECTIONS SHALL BE BELOW
BACKDRAFT DAMPER.
3. CHECK SCHEDULE FOR UPBLASTIIDOWNBLAST FAN.
i1 POWER ROOF VENTILATOR DETAIL
NO SCALE
FRAMED WALL OPENI NO OF SIZE TO PASS DUCT FRAMED WALL OPEN ING OF SIZE TO
ANDLEAVE ROOM FOR SEALANT TO MEET UL- PASS DUCT AND LEAVE ROOM FOR
DUCT DUCT
91810@NR1C1.191 C
EACH SIDE OF DUCT ON
EACH SIDE OF WALL
WITH
1 NONCOMBUSTIBLE
S SEALANT.
FINISHED WALL FINISHED
SURFACE OF WALL UNINSULATEO DUCT THROUGHINTERIOR�
RATED SURFACE NON -RATED WALLS OR SMOKE-RESISTAN
ASSEMBLY UNINSULATE D DUCT THROUGHO CORRIDORWALLS
INTERIOR FIRE RATED WALLS FRAMED WALL OPENING OF
OtAND
AMED WALL OPENING OF SIZE
E TO LEAVE ROOM FOR DUCT
PASS DUCT AND INSULATION, AND SEALANT.
ULATION
LEAVE ROOM FOR
ALANT
DUCT MEET UL-LISTINOUCT
DUCT INSULATION DUCT INSULATION
TO BE TO BE
CONTINUOUS CONTINUOUS
THROUGH WALL. THROUGH WALL.
1 FILL ANNULAR GAPS
_— EACH
FINISHED 3O FINISHED SIDE OF DUCT ON EACH
WALL WALL SIDE OF WALL WITH
IL
SURFACE OF NONCOMBUSTIBLE
RATED SURFACE
INSULATED DUCT THROUGH INTERIOR'S OR SEALANT.
ASSEMBLY FIRE RESISTANCE RATED WALLS INSULATE WALLS OR SMOHINTER TA
NON -RATED WALLS OR SMOKE -RESISTANT
PLAN NOTES CORRIDOR WALLS
1. INSTALL FIRESTOP SYSTEM AS SPECIFIED IN DIVISION 7. INSTALL RETAINING ANGLES AS REQUIRED BY SYSTEM LISTING.
2. INCLUDES FIRE BARRIERS, SMOKE BARRIERS, AND FIRE PARTITIONS AS DEFINED IN THE LOCAL APPLICABLE CODES AND ON THE PLANS.
3. LOCATE FIRESTOP LABEL ON EACH SIDE OF PENETRATION SO THAT IT IS VISIBLE FROM AN ACCESSIBLE LOCATION ABOVE CEILING.
r <Z DUCT PENETRATION DETAILS
NOSCALE
DRAIN LINE SHALL BE AT LEAST
THE SAME SIZE AS THE NIPPLE
ON THE DRAIN PAN
CLEAN OUT
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
INSULATEENTIRE
CRAW ASSEMBLY
WITH ELASTOMERIG
r
GROUND
UNIT
A
B
NI
IN)
AHU I DX COIL
2
85
ENTIRE GRAIN PAN
CONDENSATE
DRAIN SHALL BE
C MINIMUM.
1
INCREASE GRAVEL DEPTH IF NECESSARY TO
MEET HEIGHT REQUIREMENTS.
CONDENSATE DRAIN TRAP DETAIL
NO SCALE
BSA
BSA LifeStructures
9365 Counselors Row Suite 300
Indianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www. bsafrfestructures.00m
VISIONFIRST
Indiana Lions Eye Bank
OFFICE AND
LAB
RENOVATION
CLIENT PROJECT NO. - 21160001
CONSTRUCTION
DOCUMENTS
MARK DATE DESCRIPTION
I 01/142019 ADDENDUM I
T` No. '
PE10302020
STATE OF
HVAC DETAILS
DATE
BSALS PROJECT NO.
DEC. 19, 2018
21160001
H 700