HomeMy WebLinkAboutH 701F.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Cannel
�VTI�\Dw�1DML
TRANSITION
AIR HANDLING UNIT
BRICK WALL WITH STORE FRONT
REMOVE EXISTING SPANDREL GLASS AND C
MUILLION PIECE.
EXISTING MUILLION PIECES TO REMAIN AS INDIC4
ABUTT DUCTTOONE SIDE IN VOID —
SPACE. INFILL THE VOID SPACE WITH
INSULATED PANEL MATCHING MULLION.
SEAL ALL AROUND.
BRICK WALL WITH STORE FRONT
AND UPPER GLASS AND
MUILLION PIECE REMOVED —
DUCT INTO BUILDING
il4' =1'-0'
DECK
m
INSULATED DUCT PANELS
SEAL THE GAP BETWEEN THE DUCT
AND THE WALL WATERTIGHT ALL
AROUND THE PERIMENTER OF THE
DUCTWORK AND PENTRATION. DUCT
SHALL BE EXTERNALLY INSULATED AS
IT PASSES THROUGH THE WALL.
PROVIDE STAINLESS FLASHING AND
COUNTERFLASHING MATERIALS AND
SEALANT TO PROVIDE A WATERTIGHT
WALL PENETRATION. SLOPE THE TOP
OF THE DUCT SLIGHTLY DOWN AND
AWAY FROM THE BUILDING ON THE
EXTERIOR SO THAT WATER ON TOP
OF THE DUCT INSUATION SHEDS
AWAY FROM THE BUILDING.
WORK WITH WEATHER
'PORTSISUPPORT
ROUND BRANCH DUCT
TO TERMINAL BOX
DISCHARGE DUCT SIZE
PER SCHEDULE OR PLANS.
DUCT RADIUS TO DIFFUSER —
MIN.2 DUCT DIAMETERS
PAINT INSIDE OF
PLENUM FLAT BLACK
PLENUM BOX /
HEIGHT BOX
PLENUM BOX DEPTH = IT MIN.
DUCTWORKIOIFFUSER SHALL BE SUPPORTED
INDEPENDENTLY FROM STRUCTURE (NOT
SUPPORTED BY CEILING)
� i-1I2' EXTERIOR INSULATION
GRILLE HEIGHT AS
/I-
SHOWN ON THE
DIFFUSER SCHEDULE
SEE ARCHITECTURAL
DRAWINGSFOR
MOUNTING HEIGHT
MOUNTING
AND LOCATIONS.
CONSTRUCTAN INDIVIDUAL PLENUM
BOX FOR EACH LINEAR DIFFUSER.
6' J
PLAN NOTES
1. AMINIMUM OF FIVE(5) FEET LENGTH OF FLEXIBLE DUCT SHALL BE PROVIDED TO EACH DIFFUSER. DUCTWORK SHALL CONTAIN
1800 OF BENDING. FLEXIBLE DUCTWORK LENGTH SHALL NOT EXCEED TEN (10) FEET EXCEPT WHERE SPECIFICALLY NOTED. FLEX
DUCT SHALL NOT CONTACT CEILING AND SHALL BE PROPERLY SUPPORTED BOAS TO HAVE NO KINKS.
2, TIE -WRAP CONNECT FLEX DUCT HELICAL COIL TO ROUND METAL DIFFUSER NECK AND TO ROUND METAL DUCTWORK AT OTHER
END OF FLEX DUCT. PULL FLEX DUCT VAPOR BARRIER OVER LOWER TIE -WRAP AND INSTALL SECOND TIE -WRAP OVER THE VAPOR
BARRIER. INSULATE METAL DUCT OR DIFFUSER OVERTOP OF SECOND TIE -WRAP AND INSTALL INSULATORS TAPE ON EDGES.
i1 LINEAR DIFFUSER DETAIL
NO SCALE
2i
PLAN NOTES
1. COORDINATE CLOSELY WITH ARCHITECTURAL DRAWINGS.
2, SPACE EQUIDISTANT ON BRAKE METAL. SEE PLANS FOR LOCATIONS.
3. BUILD PLENUM BOX ACCORDING TO DETAIL 51H701.
4. REFERENCE ECG4 GRILLES ON H500 SCHEDULE.
GALVANIZED
DUCTWORK
AIRFLOW
y�
DIRECTION
FLANGED
CONNECTION
�1 METAL SHIELD GRILLE DETAIL
NO SCALE
�7
ARMSTRONG CEILING SYSTEM
FULLY WELDED STAINLESS DUCTWORK
HUMIDIFIER LOCATED SIZE AS NOTED ON PLANS
WITHIN DUCTWORK F r WELDEDCONNECTION
FLANGED CONNECTION
GALVANIZED
DUCTWORK
FLANGED
CONNECTION
2" CD
PLAN NOTES:
1. VK'MINIMUM LENGTH OF FULLY WELDED STAINLESS DUCTWORK UPSTREAM OF HUMIDIFIER.
2. 5'-0" MINIMUM LENGTH OF LEVEL, STRAIGHT, FULLY WELDED STAINLESS DUCTWORK DOWNSTREAM OF HUMIDIFIER
WITH NO TAKEOFFS, TRANSITIONS, OR DUCT PENETRATION$ WITHIN THIS REGION.
3. GALVANIZED STEEL, INSULATED DOUBLE WALL ACCESS DOORS ON ACCESSIBLE SIDE OF DUCT. HEIGHTOFACCESS
DOOR TO BE 2' LESS THAN HEIGHT OF DUCT. INCLUDE VIEWING LENS IN ACCESS DOOR.
4. INSTALL HUMIDIFIER CONTROL DEVICES IN GALVANIZED SECTION PRIOR TO FIRST DUCT TAKEOFF, WITHIN 12- OF END
OF STAINLESS DUCT, BETWEEN STAINLESS SECTION AND ACCESS DOOR.
5. GALVANIZED, INSULATED DOUBLE WALL ACCESS DOOR ON ACCESSIBLE SIDE OF DUCT. HEIGHT OF ACCESS DOOR TO
BET LESS THAN HEIGHT OF DUCT.
6. 6" LONG SECTION OF WELDED STAINLESS DUCT WHICH IS 3" TALLER THAN THE UPSTREAM SECTION. 3" DEEP POCKET
FUNCTIONS AS GRAIN PAN TO COLLECT WATER DURING POTENTIAL HUMIDIFIER MALFUNCTION.
T INSTALL A 3"DEEP P-TRAP. ROUTE THE DRAIN IN i ll"COPPER CD TO THE MAIN CONDENSATE LINE. TURN PIPE DOWN
WALL AND TERMINATE 12' ABOVE RIM LEVEL OF SINK. SEE PLANS FOR LOCATION. LABEL PIPE'HUMIDIFIER
MALFUNCTION IF FLOWING".
BSA
BSA LifeStructures
9365 Counselors Row Suite 300
Indianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www. bsal'Ifestructures.00m
VISIONFIRST
Indiana Lions Eye Bank
OFFICE AND
LAB
RENOVATION
CLIENT PROJECT NO. - 21160001
CONSTRUCTION
DOCUMENTS
MARK I DATE I DESCRIPTION
HVAC DETAILS
DATE DEC. 19, 2018
BSALS PROJECT NO. 21160001
DATE: 02/20/19
HUMIDIFIER DUCT INSTALLATION WITH DRAIN DETAIL
NO SCALE
H701