HomeMy WebLinkAboutLF 000RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and meal Codes
City of Cannel
�\
VTGIOI
DATE: 02/20/19
TYPICAL
LAB ABBREVIATIONS
GENERAL LAB NOTES
LAB FIXTURE SCHEDULE
WITHISATINNICKey` EPDXY POWDEWATERSAVER EIISH`DRTEQ"
ADA
AMERICAN DISABILITIES ACT
1,
ALL WALL BENCHTOPS AND MOVABLE TABLES SHALL BE 30"
LABORATORY VALVES:
DEEP INCLUDING WALL BENCH BACK SPLASH(UNLESS
MOBILE BENCHES VALVES
AFF
ABOVE FINISHED FLOOR
NOTED OTHERWISE(.
WATERSAVER CT4200-141WSA
DOUBLE BALL VALVE FIT ING, PANEL MOUNTED FOR LV, NG,CA.
2,
ALL ISLAND BENCHTOPS SHALL BE 60" DEEP (UNLESS NOTED
ARCH
ARCHITECTURAL DOCUMENTS
OTHERWISE(.
3.
ALL BENCHES AND TABLES SHALL BE 36" HIGH (UNLESS
DECK -MOUNTED VALVES ON COUNTERTOPS
BBC
BIOSAFETY CABINET
OTHERWISE NOTED(,
4.
ALL BENCHITABLE TOPS TO BE 314"LAB GRADE SOLID
WATERSAVER CT4100-231WSA
SINGLE BALL VALVE FITTING DECK -MOUNTED FOR LV, NG, CA.
CFCI
CONTRACTOR FURNISHED I CONTRACTOR INSTALLED
PHENOLIC (UNLESS NOTED OTHERWISE.
5,
ALL BACK AND SIDE SPLASHES TO BE BE 314"THICK AND 4"
WATERSAVER CT4100-234WSA
FOUR SIDED BALL VALVE FITTING, DECK -MOUNTED FOR LV, NG, CA.
CFM
CUBIC FEET PER MINUTE
HIGH PHENOLIC, PIPEDROP CURBS TO BE 3A THICK AND 5"
HIGH PHENOLIC (UNLESS NOTED OTHERWISE(.
VACUUMBRAND A5-VCL02
SINGLE VACUUM FITTING.
CENT
CENTRIFUGE
6.
PROVIDE 3I4"THICK AND 4" HIGH PHENOLIC SIDESPLASHES
AT ALL BENCHTOPS AGAINST FUME HOODS ANDIOR
CLING
CEILING
ADJACENT WALLS.
WALL VALVES
7,
OVERALL LENGTH OF BENCHTOPS SHALL BE DETERMINED BY
CLR
CLEAR OR CLEARANCE
CASEWORK SIZES AND DIMENSIONS AS INDICATED ON
WATERSAVER CT4100-158FT
SINGLE BALL VALVE FITTING WALL -MOUNTED FOR LV, NG, CA MOUNTED
PLANS. TOPS SHALL OVERHANG 112" AT EACH END AND 1"
AT+52" A F.F. U IN . (AT COUNTERTOP LOCATIONS.(
CR-TCP
COLD ROOM -TEMPERATURE CONTROL PANEL
FROM FRONT OF BASE CABINETS AND TABLES. WHEN
OVERALL DIMENSIONS ARE GIVEN .II2"OVERHANGISNOT
WATERSAVER CT2873-366V-178FT PH
SINGLE BALL VALVE FITTING WITH PRESSURE REGULATOR WALL
CSP
CEILING SERVICE PANEL
INCLUDED.
MOUNTEDFORCAMOUNTEDAT+52"A.F.F. HORIZONTALLY. (AT
8,
ALL CASEWORK, FUME HOODS AND ANY OTHER
COUNTERTOP LOCATIONS I
DIA
DIAMETER
FURNISHINGS WITH EXPOSED -TO -VIEW BACKS AND SIDES
SHALL BE FIN ISHED.
WATERSAVER CT4100-158FT
S ING LE BALL VALVE FIT ING,WALL-MOUNTED FOR LV, N G, CA AT 52"A.F. F.
DIV
DIVISION
9,
INSTALL CLOSURE PANELS BETWEEN BACK OF CABINETS OR
H ODDS AND WALLS AT EXPOS ED ENDS AND B ETWEEN BASE
VACUUMBRAND A5VCL02
SINGLE VACUUM FITTING. MOUNTHORIZONTAL.
EAU
ELECTRIC ALARM UNIT
CABINETS ANDIOR HOODS THAT ARE SETBACK TO BACK.
10.
ALL PENETRATIONS THROUGH BENCHTOP SHALL BE SEALED
EM
EMERGENCY (POWER) OUTLET
WITH ACID RESISTANT SEALANT.
WATER FIXTURES
11.
BACKS OF COUNTERTOPS AND SPLASHES AGAINST WALLS
EQUIP
EQUIPMENT
SHALL BE SEALEDTO THE WALL WITH ACID RESISTANT
HWCW WATERSAVER CT414-BVB-CTB0055
DECK -MOUNTED MIXING FAUCET WITH B" SWING GOOSENECK, VACUUM
SEALANT.
BREAKER, POWEDER COATED DIECAST ALUMINUM HANDLES, AND
EP
ELECTRICAL PANEL
12.
CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR
NON-ERATED LAMINAR FLOW OUTLET. PROVIDE(2) H28 LOOSE KEY
TO FABRICATIONS.
STOPS.
EPS
ELECTRICAL POWER SPECIAL
13.
COLORS FOR ALL COMPONENTS OF THE PROJECT INDICATED
ON THESE DRAWINGS ARE AS INDICATED IN THE
CW WATERSAVER CT614VB-H26
DECK -MOUNTED SINGLE FAUCET RIGIDISWING GOOSENECK WITH
EO. EX
EQUIPMENT EXHAUST
SPECIFICATIONS,
VACUUM BREAKER, POWDER -COATED DIECAST ALUMINUM HANDLE AND
14.
FREE STANDING SHELVING AND CASEWORK LESS THAN IS
REMOVABLE SERRATED HOSE END. PROVIDE WITH#28 LOOSE KEY STOP.
FEB
FIRE EXTINGUISHER ON BRACKET
DEEP SHALL BE SECURED TO PREVENT TIPPING SUBMIT
PROVIDE LH UNITS WHERE INDICATED ON THE DRAWINGS.
SHOP DRAWINGS OF ATTACHMENT PRIOR TO INSTALLATION.
FH
FUMEHOOD
15.
SAFETY SHOWER I EYEWASH UNITS SHALL COMPLY WITH
CWA WATERSAVER CT614VB-H28
DECK -MOUNTED SINGLE FAUCET RIG IDISWING GOOSENECK WITH
ANSI STANDARDS FOR USABILITY BY THE PHYSICALLY
VACUUM BREAKER, POWDER -COATED DIECAST ALUMINUM HANDLE AND
FHFP
FUME HOOD FILLER PANEL
DISABLED, SAFETY SHOWER I EYEWASH UNITS SHALL BE
CTB012TS ASPIRATOR AND CTB-0125 SPLASH ELIMINATOR, PROVIDE WITH
FURNISHED UNDER DIVISION 12 FOR INSTALLATION UNDER
H28 LOOSE KEY STOP.
FP
FILLER PANEL
DIVISION 22.
16.
FOR LABORATORY SERVICE FITTING TYPES, LOCATIONS AND
SPR-1 WATERSAVER CTPR411
DECK -MOUNTED PRE -RINSE MIXING FAUCET WITH 39" STAINLESS STEEL
FZR
FREEZER
ORDER, SEE LABORATORY FURNISHING PLANS THESE
HOSE PRE -RINSE SPRAY ASSEMBLY, WALL SUPPORT FLANGE AND
FITTINGS SHALL BE PROVIDED UNDER DIVISION 12 FOR
POWDER -COATED DIECAST ALUMINUM HANDLES, PRE -RINSE SPRAY
GA
GAUGE
INSTALLATION UNDER DIVISION 22,
ASSEMBLY SHALL HAVE SELF -CLOSING VALVE WITH REPLACEABLE
17.
WHERE NO FUME HOOD OCCURS ADJACENT TO CORROSIVE
STAINLESS STEEL SEAT AND INSULATED HANDLE. PROVIDE WITH (2(#28
GC
GENERAL CONTRACTOR
STORAGE CABINETS, ROUTE VENT PIPE (IN PIPE CHASE( UP
LOOSE KEY STOPS.
NEAREST PIPE DROP ENCLOSURE TO EXHAUST DUCT
NO
HEAVY DUTY
SYSTEM FOR CONNECTION UNDER DIVISION 23.
SPR-2 WATERSAVER CTPR1711WSA
DECK -MOUNTED PRE -RINSE MIXING FAUCET WITH 39" STAINLESS STEEL
1B.
WHERE FUME HOOD OCCURS ADJACENT TO CORROSIVE
HOSE PRE -RINSE SPRAY ASSEMBLY, WALL SUPPORT FLANGE AND
INC
INCUBATOR
STORAGE CABINETS, ROUTE VENT PIPE (IN PIPE CHASE( TO
POWDER-COATEDDIECAST ALUMINUM HANDLES, PRE -RINSE SPRAY
FUME HOOD AND EXTEND 4" ABOVE FUME HOOD WORK
ASSEMBLY SHALL HAVE SELF -CLOSING VALVE WITH REPLACEABLE
KS
KNEESPACE
SURFACE BEHIND BAFFLE.
STAINLESS STEEL SEAT AND INSULATED HANDLE. PROVIDE WITH (2)#28
19,
ALL SNORKEL EXHAUST SHOWN ON THESE DRAWINGS,
LOOSE KEY STOPS,
LABHKS.
LAB COAT HOOKS
INCLUDING FLEXIBLE DUCT HOSE, SHALL BE PROVIDED
UNDERDIVISION12. DIVISION 23 SHALL MAKE FINAL
RO WATERSAVER CT7653
DECK -MOUNTED PURE WATER FIXTURE WITH RIGID GOOSENECK,
LB
LAB BENCH
CONNECTION TO SNORKEL.
POWDER -COATED DIE CAST ALUMINUM HANDLE AND REMOVABLE
20.
INSTALLATION OF EQUIPMENT, SUPPORTS OR ANY OTHER
POLYPROPYLENE SERRATED HOSE END. ALL COMPONENTS IN CONTACT
LT
LAB TABLE
ITEMS THAT MAY INTERFERE WITH LIGHTING STRUCTURAL
WITH RO WATER ARE INERT POLYPROPYLENE. MANUALVALVE PROVIDE
OR MECHANICAL SYSTEMS, SHALL BE CAREFULLY
RIGHT-HAND OR LEFT-HAND UNITS AS REQUIRED BY THE INSTALLATION.
MAX
MAXIMUM
COORDINATED. NOTIFY OWNER'S REPRESENTATIVE OF
112"0.D. POLYPROPYLENE TUBE EXTENSION FOR CONNECTION TO
DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.
BUILDING PURE WATER SYSTEM.
MIN
MINIMUM
21.
UNLESS NOTED OTHERWISE, ALL MISCELLANEOUS
CHANNELS, BRACKETS AND FITTINGS INDICATED ON ALL
MKRB
MARKERBOARD
LABORATORY FURNISHING DRAWINGS SHALL BE SUPPLIED,
E M ERG ENCY SIN OWER AND EYE WASH F IXT URES
INSTALLED, AND PAINTED UNDER DIVISION 12,
MTD
MOUNTED
22.
CONTRACTOR SHALL EXAMINE ALL LABORATORY
RSS-1 WATERSAVER SSBF2150-PCC-AP2800.232
RECESSED SAFETY STATIONS WITH DRAIN PAN AND EXPOSED 10
FURNISHINGS PLANS AND COORDINATE WITH REFLECTED
DIAMETER STAINLESS STEEL SHOWER HEAD. EXPOSEDPIPEAND
NTS
NOT TO SCALE
CEILING PLANS FOR PROPER VERTICAL SERVICE COLUMN B
CEILING ESCUTCHEON ARE TO BE STAINLESS STEEL, SHOWER HEAD TO
PIPE DROP ENCLOSURE HEIGHTS.
BE MOUNTED AT 96" A.F.F. PROVIDE ELECTRIC LIGHT, ALARM HORN, AND
OC
ON CENTER
23.
HEAVY DUTY UNISTRUT AND OTHER STRUCTURALLY
ALARM WITH SILENCING SWITCH.
ANCHORED AND SUSPENDED DEVICES WHICH REQUIRE
OFOI
OWNER FURNISHED, OWNER INSTALLED
COORDINATION WITH OTHERTRADES SHALLBETHE
EW WATERSAVER FE774 DECK -MOUNTED AUTOF LOW EYEWASH. PROVIDE EW849RLEFT-HAND
RESPONSIBILITY OF DIVISION 12 (UNLESS OTHERWISE
MOUNTED WHERE INDICATED ON THE DRAWINGS.
OFCI
OWNER FURNISHED, CONTRACTOR INSTALLED
NOTED(, ADDITIONAL FRAMING MAYBE REQUIRED TO
ACCOMMODATE ANCHORAGE AROUND DUCTWORK OR
OR
OPPOSITEHAND
OTHER OBSTRUCTIONS.
24.
ALL MARKERBOARDS, COAT RACKS, AND FIRE
OVH
OVERHEAD
EXTINGUISHERS ARE INDICATED ON THE "LF"DRAWINGS FOR
COORDINATION ONLY
"LF"
SINK SCHEDULE
PHEN
PHENOLIC
25.
SERVICE FITTING SHOWN ONTHE PLAN DRAWINGS ARE
FORLOCATIONONLY. REFER TO DETAILS AND
PH
PHASE
SPECIFICATIONS FOR ACTUAL FITTINGS.
ITEM
NIE QN.) MATERIAL
TYPE NOTES
SK-1.
25X15XII STAINLESS STEEL
UNDERMOUNT
26. ELECTRICAL DEVICES SHALL BE PROVIDED UNDER DIVISION
FIND
PAPER TOWEL DISPENSER
26. ELECTRICAL DEVICES SHOWN ON THE "LF"DRAWINGS
ARE FOR FORTHE LOCATION OF CASEWORK CUTOUTS.
SK-2.
12X 15 X 8718 STAINLESS STEEL
UNDERMOUNT
REF
REFRIGERATOR
DEVICES SHOWN AT CONSTANT TEMPERATURE ROOMS,
FUME HOODS, VERTICAL SERVICE COLUMNS, VACUUM PUMP
IRS
ROOM SIGNAGE
CABINETS, ACID CABINETS AND FLEXIBLE LABORATORY
FURNITURE SYSTEM SHALL BE PROVIDED BY THE
RSS
RECESSED SAFETY STATION
EQUIPMENT SUPPLIER.
27.
ALL WALL MOUNTED RACEWAYS SHALL BE MOUNTED PER
S
LIGHT SWITCH
ARCHITECTURAL ELEVATIONS, (UNLESS OTHERWISE
NOTED(.
SIM
SIMILAR
28.
ALL CASEWORK SINKS SHELVING, AND SUPPORTS INSIDE
CONSTANT TEMPERATURE ROOMS SHALL BE STAINLESS
SK
SINK
STEEL CONSTRUCTION(UNLESS OTHERWISE NOTED(.
SPEC
SPECIFICATIONS
SNKL
SNORKEL
SS
STAINLESS STEEL
LABORATORY BENCHTOP
LEGEND
TDS
TECHNICAL DESK STATION (MOBILE BENCH AT+30".(
PH LAB GRADE SOLID PHENOLIC
E ]EPDXY RESIN
TEMP
TEMPERATURE
SS STAINLESS STEEL
TL
TASK LIGHT
+30",+34",+36" INDICATES BENCHTOP HEIGHT
ABOVE FINISH FLOOR
TYP
TYPICAL
LAB SYMBOLS
UC
UNDER COUNTER
UNO
UNLESS NOTED OTHERWISE
SINK AND FIXTURE SYMBOLS AND
VPC
VACUUM PUMP CABINET
DESIGNATIONS. SEE SINK AND FIXTURE
3�
SCHEDULES, THIS SHEET, FOR EXPLANATIONS
WP
WEATHERPROOF
OF TYPES
SK7
LV ANDFI TURF CHEDULESTHISSONS SEE SINK
NG SCHEDULES THIS SHEEP, FOR
LAB SERVICE ABBREVIATIONS
DETAIL SYMBOLS LEGEND
LA
exx"� EXPLANATION OF TYPES
EXPLANATION
CO2
CARBON DIOXIDE
LiA LV ba
SUFFIX DESIGNATES MOUNTING HEIGHT A . F.
DETAIL NUMBER
THAT DEVIATES FROM TYPICAL MOUNTING
CW
POTABLE COLD WATER
HEIGHT
ES
EMERGENCY SHOWER
c SHEET NUMBER
EW
EYEWASH
SECTION NUMBER
CEILING SERVICE PANELS
HW
POTABLE HOT WATER
SHEET NUMBER
HWCW
HOT WATER -COLD WATER
ELEVATION NUMBER
--------j
IS
INERT GAS
SHEET NUMBER
LA
LABORATORY AIR(15 PSI(
FUMEHOOD
LA100
LABORATORY AIR (100 PSI(
LV
LABORATORY VACUUM
N
NITROGEN
14100
NITROG EN(100 PSI(
PW
PURE WATER
EXX
EQUIPMENTTAG
RO
REVERSE OSMOSIS
RSS
RECESSED SAFETY STATION
SPR
SPRAYER I PRE -RINSE UNIT
BUMPER RAIL WALL PROTECTION
BSA LifeStructures
9365 Counselors Row Suite 300
Indianapolis, IN 46240.1478
ph 317.819.7878 fx 317.819.7288
www.bsalifestructures.com
VISIONFIRST
Indiana Lions Eye Bank
OFFICE AND
im
RENOVATION
CLIENT PROJECT NO. - 21160001
CONSTRUCTION
DOCUMENTS
m KEYPLAN
L NNORTH
MARK _ DATE I DESCRIPTION
13 No.`°
AR10500148
STATE OF
LAB GENERAL NOTES AND
LEGENDS
DATE DEC. 19, 2018
BSALS PROJECT NO. 21160001
LF000