HomeMy WebLinkAbout30-E-601 IdexxWSASTIl1)10
EXISTING PAD
MOUNTED UTILITY
TRANSFORMER
EXISTING PAD
MOUNTED UTILITY
TRANSFORMER
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and meal Codes
City of Camel
DATE: 03/15/19
EXTERIOR I INTERIOR
EXISTING SERVICE -- -, (E) HUNG
DISCONNECT
CABINET -
^^",TRANSFORMER
''-'� -
EXISTING UTILITY
METER FOR
IDEXX SPACE
V J (E) 208 V (E) SINGLE PHASE
PANEL
-'i PANEL
' PANEL LOAD CENTER
` EXISTING CONDUIT TO REMAIN.
DEMOLISH EXISTING CONDUCTORS
------------ ' ---------------------------- COMPLETELY BACK TO SOURCE.
WIRING DIAGRAM
DEMOLITION ONE LINE DIAGRAM N.T.S.
EXISTING UTILITY
METER FOR
IDEXX SPACE
EXTERIOR I INTERIOR
EXISTING SERVICE
DISCONNECT
CABINET
WIRING DIAGRAM
NEW WORK ONE LINE DIAGRAM
- #1/0, #6 GND, 1.5" CONDUIT
(HUNG)
KVA
4 - #4/0, #4 END, 2.5" CONDUIT
PANEL I�'�I PANEL
Li I I P1
EXISTING CONDUIT TO REMAIN.
PROVIDE 4 - #3/0 , #6 GND IN 2"
CONDUIT
N.T.S.
ONE -LINE DIAGRAM LEGEND
EXISTING WORK
NEW WORT(
DEMOLISHED
NEW PANEL LP2 ELECTRICAL LOAD
TABULATION SCHEDULE
LIGHTING
RECEPTACLES
MOTORS
ELECTRIC
AND MISC.
HEATING
2.2 KVA
33 KVA
31 KVA
4.0 KVA
CONNECTED LOAD
NON SIMULTANEOUS
- 0 KVA
- 0 KVA
- 0 KVA
- 0 KVA
LOAD
SUBTOTAL
2.2 KVA
33 KVA
31 KVA
4.0 KVA
FEEDER SIZING
X 1.25
X 1.01ST10KVA
X 1.25 LARGEST
X 1.00
DEMAND FACTOR
X 0.5 REMAINDER
+REMAINDER
SUBTOTAL
2.75 KVA
21.5 KVA
34 KVA
4.0 KVA
TOTAL LOAD FOR
63 KVA@
480 VOLTS
= 101 AMPS
SERVICE SIZING
N2 S. FRONT STREET
COW MB08, 0H1043206
614.824.1633
CD
cC
U
C�
C
_O
C-D
0
00
L0
CV
T
PRELIMINARY
NOT FOR
;ONSTRUCTIOI
28 JAR 2018 BWNERREWEW
NOTFOR KORDA DRAWNBY.KNEI CHECKOXIN
)NSTRUCTION KOREA NEMETH ENGINEERING ELECTRICAL ONE LINE
CONCEPTUAL DESIGN 1650 WATERMARK DRIVEDIAGRAM
SUITE 200
SCHEMATICS COLUMBUS, OHIO 43215 DESIGN DEVELOPMENT DRAWNBY RaveeW. svaws E_601
DEscNED BY Doi Ruby
WORKING DRAWINGS
FOR REVIEW CHECKEDB. Cnacx«
PROJECT NUMBER: 2018-0885