HomeMy WebLinkAboutE-3 ELEC SCHEDULES, DETAILS, AND SYMBOLSElectrical Symbols Legend
Lighting
Q
LED disc Iighliplure provided by owner, installed by E.C. per requirements.
®
N2 LED troffer l ighl
p
2 lamp wal l l ight fixture provitletl by owner, installed by E.C. per requirements.
1 lamp pendant fixture provided by owner, installed by E.C. per requirements.
®
13 lamp pendant fixture provided by owner, installed by E.C. per requirements.
®
Ceiling mounted exit sign
"O
Wall mounted exit sign
Switches
$
Single pole switch
$3
Three-way switch
Dimmer switch
$I
Timer switch
CP
Disconnect switch
Power
8
Duplex receptacle (20 Amp rated)
F
Quad receptacle (20 Amp rated per duplex)
Ground fault interrupt duplex receptacle (20 Amp rated)
8wP
Weatherproof, ground fault interrupt duplex receptacle (20 Amp rated) with
"While-In-Use"cover
around fault interrupt Wad receptacle (20 Amp rated per tluplex)
®
Special purpose receptacle as noted on drawings
o
Existing 1201 panelboand to remain
QMotor
connection
Communication
e
Telephonedata outlet location, 1" concert with pullwim to above accessible ceiling
Circuiting
Conduit system concealed above ceiling
Surface mounted call system
- - -
Conduit system under floor
Hamadan. Conduit system to panel as noted on drawings
Q
Junction box
Cf-
Conduit up
Conduit down
0-
Notes
1. Switches shall be a maximum +48" A.F.F. to the top of the device unless otherwise noted
on plans.
2. Receptacles, telephone outlets, and television outlets shall be a minimum of+18" A.F.F.
rather bottom of the device unless otherwise noted on plans.
3. Not all symbols listed above are shown on plans. The symbol legend is used for reference
of symbols shown on plans. See specifications for information related to symbols.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Corks
City of Camel
�V�I��V'�6*14aWMt_
DATE: \ 03/25/19
AL1-1,3,5
Panel designation
Ground conclusions) (if used)
Phase conductons)
Neutral conductors)
Switch leg or Go-between
All conductors 012 AWG
otherwise noted
All conduit N*'unless
otherwise noted
Circuit No. designation
Notes
1. #12 AWG is min. conductor size except as noted.
2. W4" conduit is min. Size except as capacity
ascribing 24 volt control conductors and switchlegs
may be in 1/2" size, others as noted.
3. 1/2" is min. Flexsteel, Greenfield and Sealite size.
Seale: None
Light Fixture Schedule
Illustration
Type
Manufacturer
Model No.
Lamp Type
Voltage
Mounting
Description
(See Note 1)
Notes
Columbia
LCATM-35MLG-EDU
2'x2'LED volumeldblroHer. Acrylic, prismatic cater
Lthonia
diffuser. 0 10V dimmable. Suitable ton damp locations. IC
Metalux
rated.
'C1'
Mercury
LED /3500K
120
Ceiling
$5
Recessed
Moment
Williams
Day Bids
Notes:
1.
Pictures are shown as a visual wall and may not depict specific attributes listedin this schedule.
2.
Ememencvbackuo: minimum of 90 minute rolfime for emergency operation.
3.
0-1011LEDonermingdaver. Provide Manufacturer approved compafible dimmer where applicable (refer 0 Nghfir)g plans for dimmer bcafioril
4.
Coordinate with cabinetry structure prior to rough- in and verity exact quantities ofaN system components prior to ordering.
5.
Coordinate with ceiling and/or wall structure prior to rough in and adjust as necessary to avoid installation conflicts.
Notes: Main: Main Lug Only
tt
*= GFCl circuit breaker Existing Tenant Panel NStt Bus: Existing
Mounting: Recessed
**=HACR circuit breaker Location: Back of suite
Cr.
No.
20 AMP
1 Pole
u.0 N.
Cis.
No.
<Load(KW)>
Remarks
Liq F'
Hee
Equip-
Other
Other
Equip-
A/C
Heat
Rec.
Light
Lighting Front Room
1.1
1
30
60
2
.7
Lighting Back
Receptacles Front
.8
3
4
.8
Power Tables
Power Tables
.8
5
e
.8
Power Chairs
Power Chairs
.8
]
8
.8
Power Chairs
Power Chairs
.8
9
10
.8
Power Chairs
Power Chairs
.8
11
12
.4
Receptacle
Receptacles
.4
13
14
.3
Receptacle RR
Receptacle RR
.3
15
15
.7
Refrigerator At
Receptacle Countertop
.3
17
18
.3
HVAC Receptacle
Quad Rec
1.0
19
20
1.0
Quad Rec
Front Wall Seances
.8
21
22
.8
Front Pendants
Track Lighting
.8
23
24
.8
Window Receptacles
Spare
25
26
Spare
Spare
27
28
Spare
Spare
29
30
smile
Space
31
32
Space
Space
33
34
Space
EF-1
1
.6
35
35
Space
* Washer
1.0
37
38
14.8
RTU-1 **
D ryer
45
39
40
41
42
2.7
6.0
-
-
6.1
-
Connected load (KW)
-
-
14.8
-
6.7
1 1.5
2.7
6.0
-
-
6.1
-
Demand load (KAd
-
-
14.8
-
6.7
1 1.5
Legend
Total Demand(KWI
Feeder
Calculated
= 1 Pole
2 Pole
= 3 Pole
Light
Rae
I Heal
I A
Equip.
Other
Total
Fed From. Existing (bottom)
Wire Size Existing
Conduit: Existing
Total Demand Amps = 105±
M
4.2
12.7
1d.8
6.1
-
37.8
Soe Lin & Associates, LLC
4340 East West Highway
Suite 105
Bethesda, Maryland
20814 USA
301.986-9300
Fax.986-0500
Notes Consultants
own By
ALB
Chkd By
SLH
Job No.
18122
Project
NAIL SALON
7245 EAST146th St
CARMEL, IN 46033
ZUMCIT REAL ESTATE MGMT.
Drawing Title
ELEC.SCHEDULES,
DETAILS, & SYMBOLS
�eras"�jEL L.n'moyti �
yrSpSt�yG1S'IFA �Rpc �
_* PE10100876 *3
���'x'� �✓pANP ��`
Sheet No.
E-3