RTU-1
Occupied mode: RTU fan shall run run continuously. Open CIA damper
Unoccupied mode: Fan shall cycle upon call for heating or cooling. Close O/A
dampers.
For Humidistat: Cooling has priority. Upon call for dehumidification, when cooling
set point is met, operate compressors to cool supply air to 55 F [ADJ.] and utilize
hot gas reheat to reheat supply air to 70 F [ADJ].
EF-1
EF-1 shall operate from a occupancy sensor with override switch. Override shall be
of an adjustable/programmable duration.
EF-2
EF-2 shall operate from timer and will run continuously when the building is
occupied.
/� PROPOSED FLOOR PLAN
RELEASED FOR CONSTRUCTION scale: 1/8^ =1-0•
Subject to compliance with all regulations
of State and Local Codes
City of Camel
DATE: 03/25/19
Rooftop Unit Schedule
External
Cooling Performance
Heating
Electrical Connection
Air
Outside
Performance
Nominal
Static
Supply Duct
Return Duct
Weight
Mark
AAON Model
Volume
Air
t
Remarks
Tons
(CFM)
CFM
(CFM)
CFM
Pressure
Connection
ConnectionI(OF)
l
EDB LDB Gas Input
Voltage Phase Starter
Disconnect
(lbs)
(w.g.)
LDB (°F)
ing
(°F) (°F) (MBH)
MCA MOCP
N) (0) By:
By:
r7O9W113
H)
RTU1
RN-008-8-0-EB
8
2"
1200
1.5
Vertical
Vertical
87
54.66
5
28.2
105.9
210
208
3
41
60
MFR
MFR
1291
See Notes
09-3LB
Notes:
Acceptable Manufacturers:
1.
Gas pressure regulator suitable for site gas pressure.
1. AAON
2.
Provide Stainless Steel Heat Exchangers.
2. CapriveAlr
3.
Provide hot gas reheat for dehumidification cycle, and appropriate
controls.
3. Carrier
4.
Provide digital 7-Day programmable, Wit! enabled T-stets with occupied and unoccupied cycles and humidistat like Honewell VisionPro 8000.
4. Trans (Horizon)
5.
Provide 14' full perimeter roof curb.
5. Valent
6.
Digital Scroll a inverter compressors.
6. Daikin
T
Wall mounted system controller.
7. Addison
8.
Heat pumps fa tat stage heat.
9.
Phase and brownout protection.
Exhaust Fan Schedule
Electrical
Codirection
reenheck
Airflow
Static Pressure
Weight
Mark
Model
(CFM)
(In. W.g.)
(lbs)
Remarks
Voltage
Phase
Power
IV)
(0)
(HP)
EF-1
G-09fS13
wo
0.6
i m
1
1/ 8
30
1, 2, 3, 4
EF-2
G-09fS13
190
0.4
120
1
1 / 12
30
1, 2, 3, 5
Notes:
Acceptable Manufacturers:
1. Install tenon curb provided by Fan MFR. Provide tapered curb.
1. Greenheck
2. Gravity back draft damper by Fan MFR.
2. Loren Cook
3. Direct drive with solid state speed controller.
3. PennBarry
4. Fan shall operate from occupancy sensor with override switch by EC.
4. Twin City
5. Fan shall operate iron a timer.
Terminal Outlets
Mark
Function
Price
Model
Airflow
Range
(CF(in.)(in.)
Face Size
(in
Neck Size
Color
Remarks
PD-1
Plaque Diffuser
SPD
50-180
24 x 24
60
While
1,2,3
PD-2
Plaque Diffuser
SPD
181-300
24x 24
80
While
1,2,3
ER-1
Exhaust Register
530
0-100
73/x73/
6x6
While
1,2,3
LBMH
Linear Bar Grille
bBPH-15C
50
118 x 71
10x6
By Architect
1,2,3
ECR-1
Eggcrate Return
80
501-1500
24x 12
1 22x 10
1 White
1,2,3
ECR-2
Eggcrate Return
80
1 1501-2000
1 24x 24
22x 22
1 White
1 1,2,3
Notes: Acceptable Manufacturers:
1. Provide factory extended panel for any diffuser which is smaller than the grid in which A is 1. Price
installed. 2. Titus
2. Sound baffle by Sheet Metal Contractor. 3. Nadir
3. Provide plaster frame for diffusers, registers and grilles installed in gypsum board. 4. Metalaire
General Notes:
1. These plans are diagrammatic in nature, and do not
represent every necessary offset and fitting. Contractor
shall install his work in a manner that will conform wlih
the structure. Contractor shall avoid obstructions,
preserve head room and maintain maximum clearance
without additional cost to the owner.
2. Conceal all piping, power wiring cannot wiring and
control components unless otherwise noted. If
concealment is not possible, contact Engineer for
alternatives prior to fabrication.
3. Sheet metal supply ductwork in concealed spaces shall
be insulated wlih Ih'thick,.75 PCF density, fiberglass
ductwrap. All ductwork in unconditioned spaces shall be
insulated with 2 thick, 1.0 PCF density, fiberglass
duclwrap. (Min 136)
4. Phenolic dud by Pal -Duct or Kool-Duct is an acceptable
alternativeto sheetmetal duct and insulation in
concealed spaces. Use flanged joints.
5. Keep all ductwork, dud system and equipment openings
covered with adhesive duct protective wrap like
VentureTape 1512, until system stall This is to
Prevent intrusion of construction did and deals into the
duct system, and HVAC equipment
6. If any questions arise concerning the HVAC
requirements of these documents, please contact The
Engineering Collaborative at (317) 636 3941, prior to
bidding, fabrication or installation of equipment.
Z Sheet metal transitions by Sheet Metal Connector.
8. Refer W detail sheets M-4 fa additional requirements
and information that applies to this project.
9. Subslab ductwork should be PVC coated Galvanized
sheet metal of 20 gauge
Plan Notes:
1O Place exhaust register in the center of ceiling tile and
prove factory extended panel.
(� Exhaust Fan placed on roof.
O4' dryer Dud. Refer to manufacturer's instructions far
type of duct, termination detall and installation.
Sole Lin & Associates, LLC
4340 East West Highway
Suite 105
Bethesda, Maryland
20814 USA
301.986-9300
Fax.986-0500
Notes Consultants
Dwn By
AK
Chkd By
JTL
Job No.
18122
Project
NAIL SALON
7245 EAST146th St
CARMEL, IN 46033
ZUMCT REAL ESTATE MGMT.
Drawing Title
HVAC FLOOR PLAN
L...4o
>@�ooy`
"�ia'
Sheet No.
M-2