HomeMy WebLinkAboutM-2 HVAC FLOOR PLANSeauence of Operations RTU-1 Occupied mode: RTU fan shall run run continuously. Open CIA damper Unoccupied mode: Fan shall cycle upon call for heating or cooling. Close O/A dampers. For Humidistat: Cooling has priority. Upon call for dehumidification, when cooling set point is met, operate compressors to cool supply air to 55 F [ADJ.] and utilize hot gas reheat to reheat supply air to 70 F [ADJ]. EF-1 EF-1 shall operate from a occupancy sensor with override switch. Override shall be of an adjustable/programmable duration. EF-2 EF-2 shall operate from timer and will run continuously when the building is occupied. /­� PROPOSED FLOOR PLAN RELEASED FOR CONSTRUCTION scale: 1/8^ =1-0• Subject to compliance with all regulations of State and Local Codes City of Camel DATE: 03/25/19 Rooftop Unit Schedule External Cooling Performance Heating Electrical Connection Air Outside Performance Nominal Static Supply Duct Return Duct Weight Mark AAON Model Volume Air t Remarks Tons (CFM) CFM (CFM) CFM Pressure Connection ConnectionI(OF) l EDB LDB Gas Input Voltage Phase Starter Disconnect (lbs) (w.g.) LDB (°F) ing (°F) (°F) (MBH) MCA MOCP N) (0) By: By: r7O9W113 H) RTU1 RN-008-8-0-EB 8 2" 1200 1.5 Vertical Vertical 87 54.66 5 28.2 105.9 210 208 3 41 60 MFR MFR 1291 See Notes 09-3LB Notes: Acceptable Manufacturers: 1. Gas pressure regulator suitable for site gas pressure. 1. AAON 2. Provide Stainless Steel Heat Exchangers. 2. CapriveAlr 3. Provide hot gas reheat for dehumidification cycle, and appropriate controls. 3. Carrier 4. Provide digital 7-Day programmable, Wit! enabled T-stets with occupied and unoccupied cycles and humidistat like Honewell VisionPro 8000. 4. Trans (Horizon) 5. Provide 14' full perimeter roof curb. 5. Valent 6. Digital Scroll a inverter compressors. 6. Daikin T Wall mounted system controller. 7. Addison 8. Heat pumps fa tat stage heat. 9. Phase and brownout protection. Exhaust Fan Schedule Electrical Codirection reenheck Airflow Static Pressure Weight Mark Model (CFM) (In. W.g.) (lbs) Remarks Voltage Phase Power IV) (0) (HP) EF-1 G-09fS13 wo 0.6 i m 1 1/ 8 30 1, 2, 3, 4 EF-2 G-09fS13 190 0.4 120 1 1 / 12 30 1, 2, 3, 5 Notes: Acceptable Manufacturers: 1. Install tenon curb provided by Fan MFR. Provide tapered curb. 1. Greenheck 2. Gravity back draft damper by Fan MFR. 2. Loren Cook 3. Direct drive with solid state speed controller. 3. PennBarry 4. Fan shall operate from occupancy sensor with override switch by EC. 4. Twin City 5. Fan shall operate iron a timer. Terminal Outlets Mark Function Price Model Airflow Range (CF(in.)(in.) Face Size (in Neck Size Color Remarks PD-1 Plaque Diffuser SPD 50-180 24 x 24 60 While 1,2,3 PD-2 Plaque Diffuser SPD 181-300 24x 24 80 While 1,2,3 ER-1 Exhaust Register 530 0-100 73/x73/ 6x6 While 1,2,3 LBMH Linear Bar Grille bBPH-15C 50 118 x 71 10x6 By Architect 1,2,3 ECR-1 Eggcrate Return 80 501-1500 24x 12 1 22x 10 1 White 1,2,3 ECR-2 Eggcrate Return 80 1 1501-2000 1 24x 24 22x 22 1 White 1 1,2,3 Notes: Acceptable Manufacturers: 1. Provide factory extended panel for any diffuser which is smaller than the grid in which A is 1. Price installed. 2. Titus 2. Sound baffle by Sheet Metal Contractor. 3. Nadir 3. Provide plaster frame for diffusers, registers and grilles installed in gypsum board. 4. Metalaire General Notes: 1. These plans are diagrammatic in nature, and do not represent every necessary offset and fitting. Contractor shall install his work in a manner that will conform wlih the structure. Contractor shall avoid obstructions, preserve head room and maintain maximum clearance without additional cost to the owner. 2. Conceal all piping, power wiring cannot wiring and control components unless otherwise noted. If concealment is not possible, contact Engineer for alternatives prior to fabrication. 3. Sheet metal supply ductwork in concealed spaces shall be insulated wlih Ih'thick,.75 PCF density, fiberglass ductwrap. All ductwork in unconditioned spaces shall be insulated with 2 thick, 1.0 PCF density, fiberglass duclwrap. (Min 136) 4. Phenolic dud by Pal -Duct or Kool-Duct is an acceptable alternativeto sheetmetal duct and insulation in concealed spaces. Use flanged joints. 5. Keep all ductwork, dud system and equipment openings covered with adhesive duct protective wrap like VentureTape 1512, until system stall This is to Prevent intrusion of construction did and deals into the duct system, and HVAC equipment 6. If any questions arise concerning the HVAC requirements of these documents, please contact The Engineering Collaborative at (317) 636 3941, prior to bidding, fabrication or installation of equipment. Z Sheet metal transitions by Sheet Metal Connector. 8. Refer W detail sheets M-4 fa additional requirements and information that applies to this project. 9. Subslab ductwork should be PVC coated Galvanized sheet metal of 20 gauge Plan Notes: 1O Place exhaust register in the center of ceiling tile and prove factory extended panel. (� Exhaust Fan placed on roof. O4' dryer Dud. Refer to manufacturer's instructions far type of duct, termination detall and installation. Sole Lin & Associates, LLC 4340 East West Highway Suite 105 Bethesda, Maryland 20814 USA 301.986-9300 Fax.986-0500 Notes Consultants Dwn By AK Chkd By JTL Job No. 18122 Project NAIL SALON 7245 EAST146th St CARMEL, IN 46033 ZUMCT REAL ESTATE MGMT. Drawing Title HVAC FLOOR PLAN L...4o >@�ooy` "�ia' Sheet No. M-2