HomeMy WebLinkAboutM-4 HVAC GENERAL NOTESREu
Su
DATE
APPLICABLE CODES AND ORDINANCES:
Provide all materials and equipment and perform all labor required to install complete and
operable mechanical systems as indicated on the drawings, as specified and as required by
code.
Entire installation shall be in strict accordance with applicable codes and ordinances.
Secure and pay for all required permits.
Provide a minimum of 10'-0' between exhaust outlets, plumbing vents and all outside air
makes.
Provide a minimum of 3'-0' between exhaust outlets and operable windows or tloors
Contractor shall not locate any duct or piping directly over any electrical panel, switchgear,
transformer, etc. Coordinate locations of ducts and piping with the Electrical Contractor 0
avoid these conflicts.
AS -BUILT DRAWINGS:
Contractor shall maintain a set of drawings that document field changes to these drawings,
and shall submit them to the Nchitect/Engineer as part of the project close out.
ARCHITECT:
Contractor shall be guided by the Architect's reflected ceiling plan fa exact location of
diffusers, registers and grilles unless otherwise noted.
Coordinate diffuser, register, and grille locations with architectural reflected ceiling plans,
lighting, and other ceiling items and make minor duct modifications to suit.
Exterior louvers are indicated for information only. Detailed descriptions are provided in the
architectural specifications.
Furnish all material and equipment as specified excedwhere sports approval for
substitution is given by the Architect/Engineer.
GENERAL:
Do not operate new HVAC systems until drywall sanding is complete and primed and
jobsite dust is no longer significant. Construction dust is extremely detrimental to the long
tam operation of the HVAC system. Provide temporary heating a coolingrdehumidifi cation
systems during construction if it is desired or required.
These drawings indicate required sizes and points of termination for piping, ductwork,
conduit, etc. The equipment shown illustrates suggested routing, but all necessary offsets
and fittings may not be shown. Contractor shall install his work in a manna that will conform
wdth the structure. Contractor shall avoid obstructions, preserve head room and maintain
maximum clearance without additional cost to the Owner.
All dimensions shown on these plans are in feet and/or inches unless otherwise noted.
Mechanical work shall be complete in every detail and all miscellaneous items of material
and labor necessary to complete the work described, shown or reasonably implied on
drawings or specifications, shall be included in the contract.
Proposal shall be based on specified material and equipment. In order to promote
competition, however, bloods may submit alternate Proposals on any alternate materials
anchor equipment they wish to Propose, including any price changes affected by acceptance
of alternatives. These must be provided in addition to the base bid not in place of the base
bid.
Contract document drawings for mechanical work are diagrammatic and are intended to
convoy scope and general arrangement only.
Install all mechanical equipment and appurtenances in accordance with Manufacturers'
recommendations, contract documents, and applicable codes and regulations.
Provide vibration isolation as specified for all mechanical equipment to prevent transmission
of vibration to building structure.
Provide vibration isolators for all piping supports connected to and within 50 feet of isolated
ABED FOR CONSTRUCTION ipports and anchor points) throughout mechanical
jest to compliance with all regulations
of State and Local Codes
City of Camel
03/25/19
Mechanical Symbols and Abbreviations
Abbreviations
Drawing Symbols
Sheet Metal Symbols
ACC
ACCU
air cooled condenser
air cooled condensing unit
GC
GPM
General Contractor
gallons per minute
Denotes section Section number
Fire damper
l u m
1Pn
damper
Volume d
°P
AFF
above finish floor
H
humidifier
T
T
BCC
branch circuit controller
HDR
heavy duty register or grille
0 S 1
Supply diffuser
®�+�
BDD
backdratl damper
HRB
heat momery box
M1
BOD
bottom of duct CC cabinet convector
HRU
variable refrigerant heat recovery unit
Sheet number
Where
Supply dud riser
CD
ceiling diffuser (supply air)
HP
heat pump
Arrow indicates Direction section
CEF
ceiling exhaust fan
HWP
hot water pump
in which Section is cut Is located
Return duct user
0
CFM
cubic feet per minute
HWR
hot water return
CUH
cabinet unit heater (electric or hi
HWS
hot water supply
Supply register
CEO
CHWP
CH WR
chilled water pump
chilled water return
HX
IN
heat exchanger
inch
Denotes detail Detail number
Lineardiffuser
CHWS
chilled water supply
KEC
kitchen equipment contractor
CT
cooling tower
LAT
leaving air temperature
D 1
Flexible connection
C1
CP
condensate pump (steam)
LS
linear slot diffuser
CW
cold water
MAN
manual
M1 E—Sheet number
Return air grille
IS
DB
dry bulb
MAU
make up air unit
Where detail
DOAS
dedicated outdoor air system
MFR
Manufacturer
Denotes Is located
Exhaust grille
Z
DSAC
ductless split air conditioner
MBH
1000 STUN
Construction
0
diameter
MC
Mechanical Contractor
Starf point
Exhaust
0
EDB
entering air dry bulb
OIA
outside air
EWB
entering air wet bulb
DAL
outside air louver
Square Elbow with Turning Vanes
YJ
EBR
electric baseboard radiation
PC
plaque diffuser
EC
Electrical Contractor
PSI
pounds per square inch
Rectangular to round duct transition
ECR
eggcrate grille
RA
return air
EDC
electric duct coil
RD
round diffuser
Note Designation
Temperature Control Symbols
EF exhaust fan
RG return air grille
EG
exhaust grille
RPM
revolutions per minute
Room thermostat or sensor
(D
EH
exhaust hood
RTU
roof top unit
Plan Notes: Specific information as indicated on a
ER
exhaust register
SA
supply air
drawing
Room humidistat or sensor
G w
ERV
energy recovery ventilator
SBCC
subbranch circuit controller
ESP
external static pressure
SDG
spiral duct grille
Leader line of plan note referenced
Motorized damper
EVC
evaporative cooler
SP
static pressure
directed to item of plan note
CO2 Sensor
O
EWH
electric wall heater
SR
supply register
reference
F
furnace
SVK
solenoid valve kit
1 ( Circle with number indicates a plan
Wall Mounted System Manager
FD
fire damper
TCC
Temperature Control Contracts
note reference, with the number
SD
fire and smoke damper
TSP
total static pressure
indicating the Hem number of the plan
FLA
full load amps
UH
unit heater
note referenced
Design Conditions:
FPM
per
feet per minute
VAV
variable air volume box
Outdoor:
FPVAV
tan powered variable air volume box
VD
volume damper
General Plan Notes: General information as it pertains
Summer 89-75 F
FT
toot
We
wet bulb
only mthe drawing it is on
Winter:-3F
IS
gas
VJr
weight
Indoor:
XT
expansion tank
General Notes: General information containing
Summer 75F and 5W6RH
to all the drawings of the
Winter: 70 F and 20%RH
discipline it is on
The location of existing underground utilities is shown in an approximate way only. The
Contractor shall determine the exact location of all existing utilities before commenting work.
The Contractor shall pay for and repair all damages caused by failure to exactly locate and
Preserve any and all underground utilities unless otherwise indicated.
Coordinate construction of all mechanical work with Architectural, Structural, Civil, Electrical
work, etc., shown on other contract document drawings.
Each respective contractor shall be responsible for coordinating the installation of his work
with the work of other contractors and tratles Prior to the installation.
Maintain a minimum of 6'-8' clearance to underside of pipes, duct, conduits, suspended
equipment, etc., throughout access routes in mechanical rooms.
All tests shall be completed before any mechanical equipment or piping insulation is applied.
Locate all temperature, pressure, and flow measuring devices in accessible locations with
straight section of pipe or duct up and downstream as recommended by the Manufacturer
for appropriate accuracy.
Work shall include startup of all systems, furnishing of operating and maintenance
instructions and one (1) year guarantee, commencing on date of acceptance by the Owner
or as otherwise specified.
Testing, adjusting, and balancing agency shall be by a member of the Associated Air
Balance Council (AABC) or the National Environmental Balancing Bureau (NEBB). Testing,
adjusting, and balancing shall be performed in accordance with the AABC standards.
Where two or more items of the same type of equipment are required the product of one
Manufacturer shall be used unless otherwise noted.
Coordinate all equipment connections with Manufacturers' certified drawings. Coordinate
and provide all duct and piping Variations required fa final equipment connections to
furnished equipment. Field verify and coordinate all duct and piping dimensions before
fabrication.
The locations of all items shown on the drawings or called for in the specifications that are
not definitely fixed by dimensions are approximate only.
The exact locations necessary to secure the best conditions and results must be determined
by the project site conditions and shall have the approval of the Engineer before being
installed. Do not scale drawings.
All miscellaneous steel required to ensure Proper installation and/or as shown in details for
piping, ductwork, and equipment shall be furnished and installed by the Mechanical
Contractor.
Provide access panels for installation in walls and ceilings, where required, to service
dampers, valves, smoke detectors, and other concealed mechanical equipment. Access
panels shall be turned over to General Contractor for installation.
All equipment, piping, ductwork, etc., shall be supported as detailed, specified, anchor
required to provide a vibration free installation.
All outwork, piping, and equipment supported from structural steel shall be coordinated with
the General Contracts. All attachments to steel barjoists, trusses, orjoist girders shall be
at the upper member. Provide beam clamps meeting MSS standards. Welding to structural
members shall not be permitted. The use of c-clamps shall not be permitted.
Mechanical equipment, ductwork, and piping shall not be supported from metal deck.
All roof mounted equipment curbs for equipment provided by the Mechanical Contractor
shall be furnished by the Mechanical Contractor and installed by the General Contractor.
Locations and sizes of all floor, wall, and roof openings shall be coordinated with all other
trades.
All openings in fire walls due to ductwork, piping, conduit, at., shall be fire stopped with a
product similar to 3M a equal. Pmduct shall be listed by UL or FM and meet the
requirements of local and state codes.
All air conditioning condensate drain lines from each air handling unit or rooftop unit shall be
piped full size of the unit drain outlet, with 'P'tap, and piped to the nearest drain or roof
deck. See details shown on the drawings or the contract specifications for depth of air
conditioning condensate traps.
Mechanical General Notes
Refer to typical details for ductwork, piping, and equipment installation
All valves, coils, dampers, at. Shall be installed allowing easy access to them. Areas
adjacent to the access panels shall be clear of obstruction.
Furnish and install all equipment and material required to complete the installation as shown
on the drawings.
Equipment sizes, weights, power, geometry and service space requirements may vary
between different Manufacturers. Consult approved Manufacturer drawings as submitted
and coordinate with these &swings. It shall be the Contractor's responsibility to bear the
costs associated with this coordination.
All air handling units shall operate without moisture carryover.
Locate all mechanical equipment (RTUs, single duct, etc.) for unobstructed access to unit
access panels, controls, and valuing.
Refer to mechanical details for additional equipment requirements.
HVAC I SHEETMETAL:
Certain items such as rises and dome in ductwork, access doors, volume dampers, etc., are
indicated on the contract document drawings for clarity for a specific location requirement
and shall not be interpreted as the extent of the requirements for these items.
All ductwork dimensions, as shown on the drawings, are internal clear dimensions.
Keep all ductwork, duct system and equipment openings covered with atlhesive duct
protective wrap like Venturei 1512, until system start-up. This is to prevent intrusion of
construction dirt and debris into the dud system, and HVAC equipment.
Provide flexible connections in all ductwork systems (supply, return, and exhaust) connected
to air handling units,fans, and other equipment which require vibration isolation. Flexible
connections shall be provided at the point of connection to the equipment unless otherwise
noted.
Unless otherwise noted, all ductwork is overhead, tight to the underside of the structure, with
space fa insulation and below any required piping.
Runs of flexible duct shall not exceed 5'-0'. Flexible duct shall not be used as an elbow.
Provide sheet metal elbow at diffuser neck where to is not out of the bottom of the supply
main. Refer to details.
All ductwork shall be coordinated with all tratles involved. Offsets in ducts, including divided
ducts and transitions wound obstructions, shall be provided at no additional cost to the
Owner.
Provide access doors in ductwork to provide access fa all smoke detectors, fire dampers,
smoke dampers, volume dampers, humidifiers, coils, and other items located in the
ductwork which require service anchor inspection.
Smoke detectors shall be furnished by Unit Manufacturer and wired by the Electrical
Contractor. The Mechanical Contractor shall be responsible for mounting the smoke
detector in ductwork as shown on the drawings and in accordance with Manufacturer's
printed instructions.
See specifications for ductwork gauges, bracing, hangers, and other requirements.
Contractor shall not locate any duct or piping directly over any electrical panels, switchgear,
transformer, etc. Coordinate locations of ducts and piping with the Electrical Contractor to
avoid these conflicts.
All ducts proposing chaff walls shall be sealed airtight with firestop.
Provide volume dampers upstream of all air inlets/outlets unless otherwise noted.
All rooftop units shall be accessed from the roof.
Power for all rooftop units shall be wired by the Electrical Contractor and shall be placed on
a dedicated circuit.
Locate rooftop units on roof. Coordinate with structural plans. Set units as required to allow
supply and return openings to clear roof structure.
Furnish and install rain hoods on flues and intake ducts above roof.
Provide companion opposed blade volume dampers with all diffusers mounted in drywall
ceilings. Do not Provide companion volume dampers with diffusers mountetl in lay -in tile
ceilings. Provide manual volume dampers in the branch ducts serving diffusers located
above lay in tile ceilings.
Diffusers, registers, and grilles mounted in drywall ceilings shall have plaster frames.
Unless otherwise noted all ductwork above ceilings shall be insulated with 16- dudwrao
Ducavrap shall be .751to I cu ff. density.
Unless otherwise noted all ductwork in unconditioned spaces shall be insulated with 2'
dudwrap (Min 196). Ductwrap shall be J5 is I cu ft. density.
Install volume damper at each branch takeoff from main supply ducts.
Mechanical Contractor shall furnish and install a 3-x3-A/a'steel angle frame around each
rooftop unit roof opening. Field weld frames to top of joists.
Locate rooftop units on roof so that the duct drops will clear the roof structure.
Refer to Mechanical Detail Sheets for additional equipment requirements.
Phenolic duct by PalDucta Kool-Duct is an acceptable alternative to shemmetal duct and
insulation in concealed spaces. Use flanged joints. Submit detailed duct drawings for
engineer review.
RELATED ELECTRICAL AND PLUMBING:
Unless otherwise noted all low voltage wiring (24 volts) shall be provided and installed by the
Mechanical Contractor. This includes tans, radiant heaters, rooftop units, etc.
Unless otherwise noted line voltage wiring (120 volts a greater) shall be provided and
installed by the Electrical Contractor. Wiring should be concealed at all times unless
otherwise noted on the plans. Contact the Engineer if concealment is not possible.
All control wire and conduit shall comply with the National Electric Code (NEC) and Division
1626 of the specifications.
Condensate chain pipe run out shall be full size to the nearest drain. Refer to'P' sheets for
routing.
Coordinate installation of gas piping for HVAC units with Plumbing Contractor.
Furnish and install a gas cock at each unit connection.
Refer to electrical and plumbing drawings fa additional coordination with these drawings.
Any unit supplied with natural a LP gas shall be furnished with pressure regulators by Unit
Manufacturer.
APPEARANCE:
All equipment should be installed with great regard to a neat finished product.
Whenever possible, wiring should be routed in such a way as to minimize visibility.
Eliminate the need for condensate pumps if possible.
Contact the Engineer prior to installing any equipment that will not be able to be installed in a
neat, first class manner, consistent with the Manufacturer's installation instructions.
RELATED GENERAL CONSTRUCTION:
Unless otherwise noted flashing of roof openings will be done by the General Contractor.
Deliver rooftop unit and exhaust fan curbs to General Contractor for installation. Contact
General Contractor to coordinate this portion of the work.
Concrete housekeeping pads to suit mechanical equipment shall be sized and located by
the Mechanical Contractor. Minimum concrete pad thickness shall be 31/' unless otherwise
noted. Pad shall extend beyond the equipment a minimum of 6- on each side. Concrete
housekeeping pads shall be Provided by the Mechanical Contracts. It shall be the
responsibility of the Mechanical Contractor to coordinate size and location of concrete
housekeeping pads with the General Contractor.
GOLLABpR�
l'r
$v
G
Exterior louvers are indicated for information only. Louver sizes, locations, and details shall
be coordinated with the General Contractor.
SUBSTITUTIONS:
Cost of any changes required by this, a other trades, due 0 substitution of equipment other
than the basis of design, shall be included in the Mechanical Contractor's Proposal.
UTILITIES:
Unless otherwise noted the local gas company shall provide gas to the building and furnish
and install the meter. Connection to the meter and extension of the piping shall be made in
accordance with the utility company requirements.
Contact local utility company to arrange for gas meta installation. Furnish and install piping
and specialties as required to receive meter.
Verily local conditions at the site.
RELATED CONTROLS:
Unless otherwise noted, locate all room thermostats and humi iistats 4'-0- (centerline) above
finish floor. Notify the Engineer prior to installation of any rooms where the above location
cannot be maintained a where there is a question on location.
All control wiring and related control components should be concealed unless otherwise
noted on the plans. Contact the Engineer if concealment is not possible.
TEMPORARY SERVICE:
Equipment provided as part of this contract should not be used fa heatinglcooling&entilation
of the project prior to all sanding being complete, and at least 1 coat of paint on all surfaces.
The intent of this is to prevent the infiltration of construction dust into the heating I cooling
coils and causing long term performance or reliability issues.
SOB Lin & Associates, LLC
4340 East West Highway
Suite 105
Bethesda, Maryland
20814 USA
301.986-9300
Fax.986-0500
Notes Consultants
Dwn By
AK
Chkd By
JTL
Job No.
1812
Project
NAIL SALON
7245 EAST146th St
CARMEL, IN 46033
ZUMOT REAL ESTATE MGMT.
Drawing Title
HVAC GENERAL NOTES
ss g QyG1S7Fa� T g
_* PE10100876
z'�p, STHIE OF p�:z
bay 'A✓OIANP Gxtri�
Sheet No.
M -4