HomeMy WebLinkAbout18662M-M2ROOFTOP UNIT SCHEDULE MARK MFGR MODEL NO. MOM. TONS EVAP. CFM EXT. STATIC P. IN. W6. (NOTE 2) COOLING HEATING (GAS) ELECTRICAL MINIMUM OUTDOOR AIR (GFM) TOTAL WEIGHT (LB5) EER FREON NOTES TOTAL BTUH SETTS. BTUH AMB. EVAP. EAT DB/y,5 BT1H INPUT BT1H OUTPUT VOLT/mMZ BLOWER MOTOR MIN. MCA (AMPS) MIN. MOGP (AMPS) RTU-1 LENNOX K68092540 1.5 3,000 1.0 53,500 61,1410 105 50/61 130,000 120,000 208/3/60 3 HP 45 50 503 1,450 12.7 R-410a 1,2,3,4,5 RTU-2 503 12.7 RTU-3 K60150540 12.5 5,000 139,900 102,121 1 150,000 144,000 5 HP 67 50 935 1,615 122 ALTERNATE RTU MANUFACTURER MARK MFGR MODEL NO. MOM. TONS EVAP. CFM EXT. STATIC P. IN. WG. MOTE 2) COOLING HEATING (GAS) ELECTRICAL MINIMUM OUTDOOR AIR (GFM) TOTAL WEIGHT (LIES) EER FREON NOTES TOTAL BTUH SBVS. BTUH AMB. EVAP. EAT DB/WB BTUH INPUT BTUH OUTPUT VOLT/N/HZ BLOWER MOTOR MIN. MGA (MPS) MIN. MOGP (AMA) RTU-1 TRANE YSC092F3 1.5 5,000 1.0 55,510 61,600 105 80/67 150,000 121,500 208/3/60 1 HP 39 50 503 1,450 12.0 R-410a 1,2,5A5 Fal 503 RTU-3 Y5D150F3 12.5 5,000 139,100 111,510 250,000 115,000 3 HP 64 80 935 1,615 NOTES: 1. PROVIDE OUTDOOR AIR ECONOMIZER WITH STANDARD CONTROL, FIXED DRY-BULB CONTROL WITH A HIGH LIMIT SHUT OFFSET AT 550F, BAROMETRIC RELIEF DAMPER, CONSTANT AIR VOLUME, HINGED ACCESS DOORS, SCROLL COMPRESSORS WITH CRANKCASE HEATER, HI6H PRE55URE SWITCHES, orlil STAT, HAIL GUARDS, STANDARD COOLING DOWN TO 300F. OUTDOOR AIR DAMPER TO FULLY CLOSE WITH FAN SHUTDOWN FOR ALL UNITS. 2, EXTERNAL STATIC PRESSURE LISTED REPRESENTS STATIC PRESSURE REGIUIRED FOR DUCTWORK AND DIFFUSERS OUTSIDE THE HVAG UNT COMPLETELY INDEPENDENT OF ANY PRESSURE DROP THROUGH THE HVAG EQUIPMENT INCLUDING BUT NOT LIMITED TO FILTERS, COILS AND ECONOMIZERS. THE FAN AND MOTOR SHALL BE SIZED APPROPRIATELY TO MEET THIS DEFINITION OF EXTERNAL STATIC, PRESSURE. 3. PROVIDE COMMERCIAL 7-DAY PROGRAMMABLE HEAT/COOL/AUTO CHANGEOVER THERMOSTAT WITH REMOTE SENSOR AND ECONOMIZER OUTPUT FOR EACH UNIT. ECONOMIZER/OUTDOOR AIR DAMPER 15 TO CLOSE DURING UNOCCUPIED HOURS. 4. PROVIDE 15" HIGH (AT LOWEST POINT) PRE -FABRICATED INSULATED ROOF CURB WITH SLOPE TO MATCH SLOPE OF ROOF FOR EACH UNIT. 5, PROVIDE NEW 2" MERV 8 FILTERS UPON COMPLETION OF CONSTRUCTION. 6. DISCONNECTS BY ELECTRICAL. MECHANICAL CONTRACTOR TO COORDINATE UNIT MOGP WITH ELECTRICAL CONTRACTOR. NATIONAL ACCOUNT INFORMATION FREDDY'S FROZEN CUSTARD HAS NATIONAL ACGOJNT AGREEMENTS FOR ROOF TOP UNITS WITH LENNOX AND TRANS. NO ALTERNATE MANUFACTURERS ARE ALLOWED. FOR LENNOX EGEUIPMENT CONTACT: DAVE EBNER, LENNOX INDUSTRIES NATIONAL ACCOUNT MANAGER, (651) 223-1552, Daae.Ebner®LennO ind.LOM FOR TRANE EQUIPMENT EQUAL TO THE UNITS SPECIFIED CONTACT: TONY FISGHELS, TRANE ACCOUNT MANAGER - NATIONAL ACCOUNTS, (305) 209-3239 (OFFICE), (505) 655-6725 (MOBILE) TONY.FISGHELS®TRANE44OM EXHAUST FAN SCHEDULE MARK MFGR MODEL CFM EXTERNAL STATIC. P. IN. INS. RPM ELECTRICAL FAN TYPE REMARKS Voi PWR EF-1 GOOK 6G-164 150 0.25 1300 120/1/60 136W CEILING EXH. - EF-2 1 1 150 ( I it 1 1 I - NOTES: 1. PROVIDE CEILING GRILLE, INTEGRAL BACK DRAFT DAMPER, AND ROOF JACK FOR EF-1 AND EF-2. DIFFUSER SCHEDULE MARK MFGR MODEL NECK SIZE FAGS SIZE FIN15H REMARKS SD-1 TINS TMR 12"(D 22"m WHITE FIELD PREP FOR PAINTING SD-2 TMS/3 12"O 24"X24" SD-3 PAR/3 f RETURN (NO DEFLECTORS) SD-4 T5504 b (D THERMAL VAV DIFFUSER SD-5 TMS/3 6"m 12"X12^ WITH O.B. DAMPER AND TRIM KIT SD-6 8"m 24"X24" WITH O.B. DAMPER AND TRIM KIT SD-1 8"m 12"X12^ WITH O.B. DAMPER AND TRIM KIT lei 55ORLFl/3 20"X20" 24"X24" SEE NOTE 1. lei 35ORL a'xb' - lei T700L - 15 X12" WITH AUXILIARY FRAME NOTES: 1. RETURN GRILL TO BE ALUMINUM FILTER RETURN, WITH NO HINGE OPTION, FILTER TO BE AMERICAN AIR FILTER (AAF) FRONTLINE GREEN 1', WITH AAF AMERIFRAME SIZE 20x2CX1. AIR BALANCE 50HEDULE: SUPPLY AIR UNIT OUTSIDE AIRFLOW CFM RETURN AIRFLOW CFM SUPPLY AIRFLOW CFM OA SA % EXHAUST AIR UNIT EXHAUST AIRFLOW CFM REMARKS RTU-1 503 2,497 3000 20.1% KEF-1 2584 RTU-2 503 2,497 3000 20.1% KEF-2 775 RTU-3 935 4,065 5000 18.7% KEF-3 525 MUA-1 2743 0 2743 100.0% EF-1, EF-2 300 TOTAL 4,684 9,()591 13,743 34.17 1 TOTAL 4, 184 RESULTING BUILDING PRESSURIZATION 500 CFM THE BUILDING HVAG SYSTEM SHALL BE BALANCED BY AN INDEPENDENT NEBB CERTIFIED BALANCING G01`411ii R HIRED BY THE OWNER. CONTACT Jason Neises A National TAB 855-682-6822 X 103 RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and meal Codes City of Camel dVT� la+sC) ul DATE: \\ 04/03/19 FIRE RATED ENCLOSURE - GREASE DUCTS ].THERMAL CERAMICS FIREMASTER FASTWRAP XL IS INSTALL UL LISTED TESTED TO ASTM E2336 AND UL LISTED PER HNKT.G18 FIRESOP SYSTEM WITH EQUAL F AND T- RATING AT TO PROVIDE ZERO CLEARANCE TO COMBUSTIBLES AND PENETRATIONS OF RATED ASSEMBLIES TO PROVIDE A 1- OR 2- HOUR ENCLOSURE. THROUGH PENETRATIONS FIRESTOP SYSTEMS ARE TESTED IN ACCORDANCE WITH ASTM E 814 WILL 1479). ICC-ES 112 IN.(13MM) STEEL BANDING APPROVAL PER REPORT ESR 2213 OR ESR 2832. PLACED I-1/2 IN.(38MM) FROM TRANSVERSE JOINTS 2. COMPLIANT TO THE FOLLOWING CODES: AND MAXIMUM 12 IN(305 MM) O.C. NFPA 96 INTERNATIONAL MECHANICAL CODES UNIFORM MECHANICAL CODE. CALIFORNIA MECHANICAL CODE 3. INSULATION APPLIED IN TWO LAYERS WITH TIGHT COMPRESSION JOINT ON BOTH LAYERS AT ALL JOINTS. 4. MINIMUM 16 GAUGE CARBON STEEL (OR 18 GAGE STAINLESS STEEL) RECTANGULAR OR ROUND GREASE EXHAUST DUCT 5. INSTALL UL LISTED AND LIQUID TIGHT THERMAL CERAMICS FASTDOOR XL ACCESS DOORS AT ALL CHANGES IN DIRECTION AND AT MINIMUM EVERY 20 FT ON HORIZONTAL RUNS. 6. SUPPORT HANGER SYSTEMS ➢O NOT NEED TO BE WRAPPED PROVIDED THE HANGER RODS ARE MINIMUM OF 3/8 IN. DIAMETER AND SUPPORTS ARE MINIMUM 2 X 2 X 1/8 IN. STEEL ANGLE OR SMACNA EQUIVALENT SUPPORT SYSTEM. 7. THERMAL CERAMICS DUCT WRAP SHALL BE INSTALLED DIRECTLY ONTO THE DUCT AND APPLIED FROM THE HOOD CONNECTION TO THE CONNECTION TO THE FAN. 8. THERMAL CERAMICS DUCT ENCLOSURE SYSTEM SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS AND UL LISTINGS. HIND BAND EXTENSION- 611 EXH. FAN (TYP) VENTED ROOF CURB (TYP) 2 HOUR FIRE RATED DUCT HRAP SEE DETAIL � 15'xl5' 16 (FALI CARBON STEEL I^ELDEO EXHAUST DUCT (CONTINUOUS HELD5 LIQUID TIGHT) AIR GONDITIONING GREASE EXTRACTORS WITH COLLECTION TROUGH 1 1/2' C3 ) 4 TIGHT COMPRESSION JOINT ON BOTH LAYERS AIR INTAKE TRU55 �m� !% FASTDOOR XL - UL LISTED DUCT ACCESS AND 2-HOUR RATED INSULATION COVER UL LISTED-FASTDOOR XL MAU-1 Z LU NO W um v / NW W UL 11/7/2018 No. reiiaw705 WINTER ARCHITECTS II 1024 EAST V FIRST STREET MAKE-UP AIR DUCT WICHITA, KS. 'J� LLL 67214 ��CEILING PH. 316-267-7142 'AIR GONDITIONING DUCT GREASE HOOD AUTO FIRE SUFFRE55ION SYSTEM GREASE HOOD DETAIL SCALE: NONE DATE �odrwng k,Eeenprwrid owe g Einar mE wgIspmviedo, in inMinal m' a ::m.`m:ni. e�romoua�, wives mmn,1 .wp,,rgnw. orap meprinrwN.new.raw r;enmroOrnis duarn ow or uywr;Imnen DR AWN BY: SM/TH CHECKED BY: DS/BC, mENGINEERS INCORPORATED SHEET N0. n /�f� I V' G 5720 Reeder Shawnee, I45.66203 (913)262-1]]2