WORK SHALL BE DONE IN ACCORDANCE WITH LOCAL, STATE OF INDIANA, 2014 NEC
AND NATIONAL CODES, RECOMMENDATIONS, REGULATIONS, AND REQUIREMENTS.
CONTRACTORS SHALL VISIT PROJECT SITE PRIOR TO BIDDING TO ASCERTAIN AND
BECOME FAMILIAR WITH EXISTING CONDITIONS AS THEY PERTAIN TO THE SCOPE OF
WORK. CONTRACTOR SHALL VERIFY EXACT LOCATION AND SIZES OF ELECTRICAL
EQUIPMENT AND ALL OTHER APPURTENANCES ASSOCIATED WITH THE WORK.
COORDINATE AND UTILITY SHUT DOWNS, (ELECTRIC AND TELEPHONE) WITH THE
OWNER AND PROVIDE NOTICE NOT LESS THAN 72 HOURS IN ADVANCE.
COORDINATE ELECTRICAL REQUIREMENTS FOR NEW OR WORK WITH THE PLUMBING
AND MECHANICAL CONTRACTORS. VERIFY VOLTAGE, PHASE AND ACCESSORY
REQUIREMENTS, SUCH AS MOTOR STARTERS AND DISCONNECTS.
OPENINGS IN NEW WALLS AND FLOORS SHALL BE PLANNED AND COORDINATED WITH
GENERAL CONTRACTOR FOR THE INSTALLATION OF APPROPRIATE SLEEVES.
ALL CONDUIT SHALL BE 3/4" MINIMUM U.N.O.
CONDUIT SHALL BE CONCEALED IN CEILING OR WALLS WHEREVER POSSIBLE.
ALL UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC UNLESS NOTED
OTHERWISE.
ALL BRANCH CIRCUITS AND FEEDERS SHALL CONTAIN A GREEN INSULATED GROUND
CONDUCTOR. GROUNDING BY MEANS OF RACEWAY IS NOT PERMITTED.
REFER TO MECHANICAL, PLUMBING, AND ARCHITECTURAL PLANS FOR EXACT
LOCATION OF EQUIPMENT.
COORDINATE LOCATIONS OF LIGHTING FIXTURES IN MECHANICAL/ELECTRICAL ROOMS
WITH EQUIPMENT, PIPING AND DUCTWORK.
CONTRACTOR SHALL COORDINATE EXACT HEIGHT OF DEVICES DESIGNED AS OVER
COUNTER WITH CASE WORK AND FURNITURE DRAWINGS.
VERIFY CEILING TYPES PER THE ARCHITECTURAL REFLECTED CEILING PLAN. PROVIDE
APPROPRIATE TYPE FIXTURE, LAY-IN FOR GRID, FLANGE FOR DRYWALL, ETC.
NO MORE THAN 3 PHASE CONDUCTORS SHALL BE INSTALLED IN ANY ONE CIRCUIT,
UNLESS NOTED OTHERWISE. EACH BRANCH CIRCUIT SHALL CONTAIN THEIR OWN
NEUTRAL CONDUCTOR. NO SHARED NEUTRALS.
FURNISH ALL ELECTRICAL ACCESS FLOORS TO GENERAL CONTRACTOR FOR HIS
INSTALLATION. REFER TO SPECIFICATIONS FOR ACCESS DOOR REQUIREMENTS.
CONTRACTOR SHALL PROVIDE ALL FIRESTOPPING FOR CONDUIT OR CABLE TRAY
PENETRATIONS THAT PENETRATE ACOUSTICAL RATED OR SMOKE AND FIRE RATED
ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ALL RATED
ASSEMBLIES. ALL RATED PENETRATIONS SHALL BE FIRESTOPPED TO ORIGINAL
ASSEMBLY RATING. ALL NON-RATED FLOOR PENETRATIONS SHALL BE SEALED WATER
TIGHT WITH A FLEXIBLE SEALANT.
BRANCH CIRCUIT WIRING CHART TO BE UTILIZED AS GUIDELINE FOR VOLTAGE DROP
COMPENSATION, INCREASE CONDUIT SIZING PER WIRE SIZE. (APPLIES TO ALL SHEETS)
A. 20A-120 VOLT CIRCUITS
a. #12 WIRE - 75' LENGTH MAX. - #12 GRD.
b. #10 WIRE - 125' LENGTH MAX. - #8 GRD.
c. #8 WIRE - 200' LENGTH MAX. - #8 GRD.
d. #6 WIRE - 300' LENGTH MAX. - #6 GRD.
PROVIDE ALL PULL BOXES, IN ACCESSIBLE AREA, THAT EXCEED NEC NUMBER OF
BENDS OR LENGTH IN FEEDER AND BRANCH CIRCUITS. INSTALL BOXES WHERE
REQUIRED PER CODE.
ALL WIRING DEVICES SHALL BE OF HEAVY DUTY COMMERCIAL GRADE CONSTRUCTION.
REFER TO ARCHITECTURAL SHEETS AND CODE SHEET FOR ALL FIRE-RATED PARTITION
LOCATIONS AND RATINGS.
CONTRACTOR IS RESPONSIBLE FOR ALL CORE-DRILLS REQUIRED FOR INSTALLATION
OF ELECTRICAL WORK.
VERIFY THE LOCATION OF ALL UTILITIES PRIOR TO EXCAVATION, TRENCHING, OR
DRILLING.
ALL EXPOSED METAL CONDUITS ARE TO BE PAINTED TO MATCH THE ADJACENT
SURFACE. COORDINATION OF PAINTING OF CONDUIT IS TO BE BY THE ELECTRICAL
CONTRACTOR, WITH PAINTING BY OTHERS.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED
JUNCTION BOXES, PULL BOXES. ETC FOR A COMPLETE INSTALLATION PER THE N.E.C.
AND LOCAL CODES. ALL CONDUCTORS SHALL BE RATED FOR 90 DEGREE CELSIUS.
COORDINATE WORK WITH OTHER TRADES. COORDINATION OR SCHEDULING SHALL BE
RESPONSIBILITY OF THE INVOLVED CONTRACTORS.
ALL LOW VOLTAGE CABLING INSTALLED IN SPACES WITHOUT A LAY-IN OR WITH A HARD
CEILING SHALL BE INSTALLED IN CONDUIT AND BOXES.
ALL ELECTRICAL ROOMS ARE SHOWN WITH EQUIPMENT DRAWN TO SCALE AND
ARRANGED TO ENSURE FIT AND CODE REQUIRED CLEARANCES. EQUIPMENT SHALL BE
INSTALLED IN THE LOCATIONS SHOWN, UNLESS WRITTEN APPROVAL IS GIVEN BY THE
ENGINEER, BASED UPON 1/4 SCALE DRAWINGS SUBMITTED BY THE CONTRACTOR FOR
REVIEW AND APPROVAL.
GENERAL LIGHTING/POWER NOTES
LIGHT FIXTURES DESIGNATED AS "NIGHT LIGHTS" SHALL BE ON UNSWITCHED CIRCUIT, UNLESS
NOTED.
EXIT LIGHTS SHALL BE ON UNSWITCHED CIRCUIT, UNLESS NOTED.
ALL RECESSED DOWNLIGHTS MOUNTED IN GRID CEILING SHALL BE CENTERED IN CEILING TILE,
UNLESS NOTED.
IN ALL MECHANICAL ROOMS, COORDINATE EXACT LOCATION OF LIGHT FIXTURES WITH HVAC
DUCTWORK.
CONDUCTORS FOR BRANCH CIRCUITRY ARE #12 AWG MINIMUM, UNLESS NOTED. DERATE PER CODE
WHERE CIRCUITS ARE COMBINED.
ALL HOMERUN CONDUCTORS BACK TO PANEL SHALL BE #10 AWG MINIMUM, UNLESS NOTED.
PROVIDE A GREEN GROUND CONDUCTOR IN ALL BRANCH CIRCUITRY. DERATE PER CODE WHERE
CIRCUITS ARE COMBINED.
WHERE TERMINATED IN J-BOX, ALL SPARE CIRCUITRY SHALL BE LABELED WITH PANEL AND CIRCUIT
NUMBER.
COORDINATE WITH MECHANICAL CONTRACTOR AND PROVIDE ALL NECESSARY AUXILIARY
CONTACTS, RELAY, ETC. IN MOTOR STARTERS FOR REQUIRED CONTROL OF MECHANICAL
EQUIPMENT.
ALL HOME RUN WIRING SHALL BE INSTALLED IN EMT OR RGS CONDUIT, UNLESS NOTED.
ALL UNDERGROUND PVC CONDUITS SHALL HAVE RIGID GALVANIZED STEEL ELBOWS.
ALL LIGHT FIXTURES SHALL BE SEISMICALLY BRACED WITH AN INDEPENDENT WIRE (CEILING GRID
TYPE WIRE) FROM TWO OPPOSITE CORNERS TO STRUCTURAL CEILING OR BAR JOIST.
DO NOT SUPPORT CONDUIT OFF OF CEILING GRID, CEILING GRID SUPPORTS, MECHANICAL
SUPPORTS, OR ANY OTHER TRADE'S SUPPORTS. INSTALL CONDUITS AND BOXES ON SEPARATE
SUPPORTS FROM BAR JOIST OR STRUCTURE.
DO NOT SUPPORT FROM METAL ROOF DECK. PROVIDE SUPPORT FROM CONCRETE SLABS, BAR
JOIST, STRUCTURAL BEAMS, COLUMNS OR UNISTRUT BETWEEN STRUCTURAL ELEMENTS.
ALL SINGLE PHASE CIRCUITS SHALL HAVE A SEPARATE DEDICATED NEUTRAL CONDUCTOR FOR EACH
CIRCUIT. SHARING OF NEUTRAL CONDUCTOR IS NOT PERMITTED.
PROVIDE 4" HIGH, SMOOTH FINISH CONCRETE HOUSEKEEPING PADS UNDER ALL TRANSFORMERS
(45KVA AND LARGER) AND MAIN DISTRIBUTION SWITCHBOARDS. PAD SHALL BE 4" LARGER THAN
TRANSFORMER AND SWITCHBOARD IN EACH DIRECTION. USE 3000 PSIG, 28 DAY COMPRESSIVE
STRENGTH CONCRETE. ROUND ALL EDGES AND CORNERS OF CONCRETE PAD.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
ABBREVIATIONS
A
AFF
AFG
BKR
C
CATV
CUH
CKT
Cu
E
EF
ELEC
EM
EMT
FCU
G
GFI
GRC
HP
J
KVA
AMPS
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BREAKER
CONDUIT
CABLE TELEVISION
CABINET UNIT HEATER
CIRCUIT
COPPER
EXISTING
EXHAUST FAN
ELECTRICAL
EMERGENCY
EMERGENCY METALLIC TUBING
FAN COIL UNIT
GROUND
GROUND FAULT INTERRUPTER
GALVANIZED RIGID CONDUIT
HORSEPOWER
JUNCTION BOX
KILOVOLT AMPERE
KW
LGTG
MECH
NIC
NL
NTS
PVC
P
TTB
TYP
UON
UV
V
VAV
VIF
W
WC
WP
UH
UNO
KILOWATTS
LIGHTING
MECHANICAL
NOT IN CONTRACT
NIGHT LIGHT
NOT TO SCALE
POLYVINYL CHLORIDE
PHASE (POLE)
TELEPHONE TERMINAL BOX
TYPICAL
UNLESS OTHERWISE NOTED
UNIT VENTILATOR
VOLTS
VARIABLE AIR VOLUME
VERIFY IN FIELD
WATTS
WATER COOLER
WEATHERPROOF
UNIT HEATER
UNLESS NOTED OTHERWISE
LIGHTING FIXTURE. REFER TO FIXTURE SCHEDULE. LETTER INDICATES TYPE.
A
A
LIGHTING
NL
B
B
3
4
OS
P
D
C
GFI
WP
IG
CL
M
PP11-21
J
UE
W
4
6
WAP
COM
EMERGENCY LIGHTING FIXTURE WITH EMERGENCY BALLAST. "NL" INDICATES
NIGHT LIGHT CIRCUIT. FULL LUMEN OUTPUT MINIMUM 1400 LUMENS ON LAMP.
LIGHTING FIXTURE. LETTER INDICATES TYPE.
EMERGENCY LIGHTING FIXTURE WITH EMERGENCY BALLAST. OR POWERED
THROUGH INVERTER SYSTEM.
CEILING MOUNTED EXIT SIGN. REFER TO FIXTURE SCHEDULE. SHADED AREA
DENOTES FACE OF UNIT. CONNECT TO LOCAL UNSWITCHED LIGHTING
CIRCUIT.
WALL MOUNTED EXIT SIGN. REFER TO FIXTURE SCHEDULE.
SHADED AREA DENOTES FACE OF UNIT. CONNECT TO LOCAL
UNSWITCHED LIGHTING CIRCUIT.
SINGLE POLE WALL SWITCH. 120/277 VOLT, 20 AMP. 44" AFF.
THREE WAY WALL SWITCH. 120/277V, 20 AMP. 44" AFF
FOUR WAY WALL SWITCH. 120/277V, 20 AMP. 44" AFF
OCCUPANCY SENSOR WALL SWITCH. 120/277V, 20 AMP. 44" AFF
SINGLE POLE WALL SWITCH WITH PILOT LIGHT. 120/277V, 20 AMP. 44" AFF
DIMMER SYSTEM CONTROL STATION. REFER TO DWG ____.
OCCUPANCY SENSOR.OS
EXTERIOR LIGHT FIXTURE.
ER - EXISTING TO REMAIN.
PL1 - NEW FIXTURE. REFER TO FIXTURE SCHEDULE.
DUPLEX RECEPTACLE. 120 VOLT, 20 AMP. 16" AFF UNO.
DUPLEX RECEPTACLE MOUNTED AT 44" OR ABOVE BACKSPLASH. 120 VOLT,
20 AMP.
DOUBLE DUPLEX RECEPTACLE. 120 VOLT, 20 AMP. 16" AFF UNO.
PT
120 VOLT DOUBLE DUPLEX, 20 AMP RECEPTACLE MOUNTED AT 44" AFF OR 4"
ABOVE BACKSPLASH.
DUPLEX RECEPTACLE WITH GROUND FAULT PROTECTION. 120 VOLT, 20 AMP.
18" AFF UNO.
WEATHERPROOF OUTLET BOX.
120 VOLT DUPLEX , 20 AMP, ISOLATED GROUND RECEPTACLE.
120 VOLT DUPLEX , 20 AMP RECEPTACLE CEILING MOUNTED IN A/V
POCKET. OUTLET FOR PROJECTOR REFER TO LV DRAWINGS FOR
REQUIREMENTS.
FLUSH FLOOR DUPLEX RECEPTACLE IN FLOOR BOX.
ELECTRICAL LEGEND
POKE THRU FLUSH FLOOR DEVICE WITH POWER, DATA AND A/V.
P - POWER
120 VOLT SINGLE 20 AMP RECEPTACLE.
SPECIAL PURPOSE RECEPTACLE. REFER TO FLOOR PLANS FOR NEMA
CONFIGURATION.
FRACTIONAL HP MOTOR STARTER WITH THERMAL OVERLOADS.
INDICATES FINAL CONNECTION REQUIRED.
HOMERUN TO PANELBOARD. NOTION INDICATES PANEL AND CIRCUIT
NUMBER. (ALL CONDUCTORS SHALL BE #10 UNLESS NOTED OTHERWISE.)
ELECTRICAL PANELBOARD.
JUNCTION BOX.
CONDUIT STUB-OUT AND CAP BELOW GRADE. MARK STUB-OUT AT
GRADE LEVEL.
UNDERGROUND HIGH VOLTAGE OR SECONDARY SERVICE FEED.
SAFETY DISCONNECT SWITCH (NON-FUSED).
SAFETY DISCONNECT SWITCH (FUSED).
COMBINATION MOTOR STARTER/DISCONNECT.
WITH HOA SWITCH AT UNIT (FUSIBLE). OR (CIRCUIT BREAKER FOR ELEVATOR).
WC 120 VOLT 20 AMP DUPLEX, GFI RECEPTACLE FOR ELECTRIC WATER COOLER.
COORDINATE INSTALLATION WITH PLUMBING CONTRACTOR.
PLCP
BAS
PLATFORM LIGHTING CONTROL PANEL.
BUILDING AUTOMATION CONTROL PANEL.
DATA /COMMUNICATION OUTLET. TWO PORTS REFER TO DETAIL FOR
MOUNTING REQUIREMENTS.
WALL PHONE. 54" AFF.
DATA OUTLET. 16" AFF.
DATA/COMMUNICATION. FOUR PORT DATA, 16" AFF.
DATA/COMMUNICATION. SIX PORT DATA, 16" AFF.
CABLE TRAY ABOVE CEILING.
WIRELESS ACCESS CONNECTION POINT WITH CEILING MOUNTED CISCO
WIRELESS DEVICE.
UNDERGROUND COMMUNICATION DUCT.
POWER
ELECTRICAL MOTOR.
DATA AND COMMUNICATION
FIRE ALARM
DOOR ACCESS
F
F
D
S
H
SD
FACP
F
Z
E.O.L.R.
KB
SD
E
C
K
J
F
S
1
E-406
1
E-406
1
E-402
EF-1
FIRE ALARM PULL STATION. 44" AFF.
FIRE ALARM HORN/STROBE. 80" AFF.
S/R FIRE ALARM DUCT MOUNTED SMOKE DETECTOR. S = SUPPLY, R = RETURN
- COORDINATE WITH DUCTWORK. MAKE SAMPLING TUBE FULL WIDTH OF
DUCT IN LENGTH.
FIRE ALARM CEILING MOUNTED SMOKE DETECTOR.
FIRE ALARM CEILING MOUNTED HEAT DETECTOR.
SMOKE DAMPER. PROVIDE SMOKE DETECTOR FOR DAMPER OPERATION AND 120
VOLT POWER CONNECTION AS SHOWN ON THE POWER DRAWINGS. COORDINATE
ALL CONNECTIONS WITH MECHANICAL CONTRACTOR. CONNECT TO ALARM
SYSTEM.
FIRE ALARM CONTROL PANEL.
FIRE ALARM ANNUNCIATOR PANEL.
FIRE ALARM STROBE. 80" AFF.
MAGNETIC DOOR HOLD OPEN.
FIRE ALARM MONITOR MODULE
END OF THE LINE RESISTOR.
KNOX BOX WITH ALARM CONTACT.
DUCT MOUNTED SMOKE DAMPER BY MECHANICAL CONTRACTOR. PROVIDE A DUCT
MOUNTED SMOKE DETECTOR, WITH RELAY BASE, MOUNTED WITHIN 5'-0" OF THE
DAMPER WITH NO AIR OUTLETS OR INLETS BETWEEN THE DETECTOR AND THE
DAMPER.
ELECTRIC DOOR STRIKE.
DOOR SWITCH/CONTACT.
KEY OR KEYCARD ACTIVATED SWITCH IN TAMPER PROOF ENCLOSURE.
WP - WEATHERPROOF.
JUNCTION BOX
HANDICAP DOOR ACCESS BUTTON IN FLUSH WALL BOX.
G GROUND ROD 3/4" DIA. x 10' LONG
GROUND CABLE EXOTHERMIC WELD CONNECTION TO REBAR ROD IN CONCRETE
FOOTER.
GROUND CABLE EXOTHERMIC WELD CONNECTION TO BUILDING
STEEL.
UNDERGROUND COPPER CABLE.
L LIGHTNING PROTECTION CABLE.
LIGHTNING PROTECTION AIR TERMINAL.
DETAIL # ____ DETAIL REFERENCE TAG
DRAWING # REFER TO DETAIL SHEETS
KEYNOTE FOR DRAWING
DETAIL REFERENCE TAG (SECTION)
DD
DOOR OR CABLETRAY CONFIGURATION DETAIL REFERENCE TAG
LETTER NEXT TO TAG REFERS TO SPECIFIC DOOR OR CABLETRAY
LAYOUT.
CONFIGURATION INDICATED IN DETAIL.
MECHANICAL EQUIPMENT TAG. REFER TO EQUIPMENT DATA
SCHEDULE.
FAAP
FWP EXTERIOR FIRE ALARM BELL. WP - WEATHERPROOF
RPS FIRE ALARM REMOTE POWER SUPPLY
R FIRE ALARM CONTROL RELAY MODULE.
GROUNDING
LIGHTNING PROTECTION
GENERAL
V VALVE SUPERVISORY SWITCH PROVIDED BY OTHERS.
W WATERFLOW SWITCH PROVIDED BY OTHERS.
P FIRE ALARM PRESSURE SWITCH.
Sheet Name:
Proj. No.:
Date:
02/22/18 - GARAGE PERMIT
074904The Proscenium DevelopmentCarmel Development II, LLC.GarageIntersection of Carmel Dr. and Rangeline Rd.Carmel, Indiana 46032ARCHITECTURE ENGINEERING GEOSPATIAL
03/08/18
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
G
7635 Interactive Way
Suite 100
Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
Issuances:
REV DESCRIPTION DATE
BIM 360://74904 - Proscenium - R18/74904 Garage - ELEC R18.rvt3/13/2018 3:49:28 PMELECTRICAL LEGEND,
GENERAL NOTES, AND
ABBREVIATIONS
EP-001
0 Issued For Garage Permit 02/22/18