HomeMy WebLinkAboutEP-001-ELECTRICAL-LEGEND,-GENERAL-NOTES,-AND-ABBREVIATIONS-Rev.1GENERAL PROJECT NOTES 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. WORK SHALL BE DONE IN ACCORDANCE WITH LOCAL, STATE OF INDIANA, 2014 NEC AND NATIONAL CODES, RECOMMENDATIONS, REGULATIONS, AND REQUIREMENTS. CONTRACTORS SHALL VISIT PROJECT SITE PRIOR TO BIDDING TO ASCERTAIN AND BECOME FAMILIAR WITH EXISTING CONDITIONS AS THEY PERTAIN TO THE SCOPE OF WORK. CONTRACTOR SHALL VERIFY EXACT LOCATION AND SIZES OF ELECTRICAL EQUIPMENT AND ALL OTHER APPURTENANCES ASSOCIATED WITH THE WORK. COORDINATE AND UTILITY SHUT DOWNS, (ELECTRIC AND TELEPHONE) WITH THE OWNER AND PROVIDE NOTICE NOT LESS THAN 72 HOURS IN ADVANCE. COORDINATE ELECTRICAL REQUIREMENTS FOR NEW OR WORK WITH THE PLUMBING AND MECHANICAL CONTRACTORS. VERIFY VOLTAGE, PHASE AND ACCESSORY REQUIREMENTS, SUCH AS MOTOR STARTERS AND DISCONNECTS. OPENINGS IN NEW WALLS AND FLOORS SHALL BE PLANNED AND COORDINATED WITH GENERAL CONTRACTOR FOR THE INSTALLATION OF APPROPRIATE SLEEVES. ALL CONDUIT SHALL BE 3/4" MINIMUM U.N.O. CONDUIT SHALL BE CONCEALED IN CEILING OR WALLS WHEREVER POSSIBLE. ALL UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC UNLESS NOTED OTHERWISE. ALL BRANCH CIRCUITS AND FEEDERS SHALL CONTAIN A GREEN INSULATED GROUND CONDUCTOR. GROUNDING BY MEANS OF RACEWAY IS NOT PERMITTED. REFER TO MECHANICAL, PLUMBING, AND ARCHITECTURAL PLANS FOR EXACT LOCATION OF EQUIPMENT. COORDINATE LOCATIONS OF LIGHTING FIXTURES IN MECHANICAL/ELECTRICAL ROOMS WITH EQUIPMENT, PIPING AND DUCTWORK. CONTRACTOR SHALL COORDINATE EXACT HEIGHT OF DEVICES DESIGNED AS OVER COUNTER WITH CASE WORK AND FURNITURE DRAWINGS. VERIFY CEILING TYPES PER THE ARCHITECTURAL REFLECTED CEILING PLAN. PROVIDE APPROPRIATE TYPE FIXTURE, LAY-IN FOR GRID, FLANGE FOR DRYWALL, ETC. NO MORE THAN 3 PHASE CONDUCTORS SHALL BE INSTALLED IN ANY ONE CIRCUIT, UNLESS NOTED OTHERWISE. EACH BRANCH CIRCUIT SHALL CONTAIN THEIR OWN NEUTRAL CONDUCTOR. NO SHARED NEUTRALS. FURNISH ALL ELECTRICAL ACCESS FLOORS TO GENERAL CONTRACTOR FOR HIS INSTALLATION. REFER TO SPECIFICATIONS FOR ACCESS DOOR REQUIREMENTS. CONTRACTOR SHALL PROVIDE ALL FIRESTOPPING FOR CONDUIT OR CABLE TRAY PENETRATIONS THAT PENETRATE ACOUSTICAL RATED OR SMOKE AND FIRE RATED ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ALL RATED ASSEMBLIES. ALL RATED PENETRATIONS SHALL BE FIRESTOPPED TO ORIGINAL ASSEMBLY RATING. ALL NON-RATED FLOOR PENETRATIONS SHALL BE SEALED WATER TIGHT WITH A FLEXIBLE SEALANT. BRANCH CIRCUIT WIRING CHART TO BE UTILIZED AS GUIDELINE FOR VOLTAGE DROP COMPENSATION, INCREASE CONDUIT SIZING PER WIRE SIZE. (APPLIES TO ALL SHEETS) A. 20A-120 VOLT CIRCUITS a. #12 WIRE - 75' LENGTH MAX. - #12 GRD. b. #10 WIRE - 125' LENGTH MAX. - #8 GRD. c. #8 WIRE - 200' LENGTH MAX. - #8 GRD. d. #6 WIRE - 300' LENGTH MAX. - #6 GRD. PROVIDE ALL PULL BOXES, IN ACCESSIBLE AREA, THAT EXCEED NEC NUMBER OF BENDS OR LENGTH IN FEEDER AND BRANCH CIRCUITS. INSTALL BOXES WHERE REQUIRED PER CODE. ALL WIRING DEVICES SHALL BE OF HEAVY DUTY COMMERCIAL GRADE CONSTRUCTION. REFER TO ARCHITECTURAL SHEETS AND CODE SHEET FOR ALL FIRE-RATED PARTITION LOCATIONS AND RATINGS. CONTRACTOR IS RESPONSIBLE FOR ALL CORE-DRILLS REQUIRED FOR INSTALLATION OF ELECTRICAL WORK. VERIFY THE LOCATION OF ALL UTILITIES PRIOR TO EXCAVATION, TRENCHING, OR DRILLING. ALL EXPOSED METAL CONDUITS ARE TO BE PAINTED TO MATCH THE ADJACENT SURFACE. COORDINATION OF PAINTING OF CONDUIT IS TO BE BY THE ELECTRICAL CONTRACTOR, WITH PAINTING BY OTHERS. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED JUNCTION BOXES, PULL BOXES. ETC FOR A COMPLETE INSTALLATION PER THE N.E.C. AND LOCAL CODES. ALL CONDUCTORS SHALL BE RATED FOR 90 DEGREE CELSIUS. COORDINATE WORK WITH OTHER TRADES. COORDINATION OR SCHEDULING SHALL BE RESPONSIBILITY OF THE INVOLVED CONTRACTORS. ALL LOW VOLTAGE CABLING INSTALLED IN SPACES WITHOUT A LAY-IN OR WITH A HARD CEILING SHALL BE INSTALLED IN CONDUIT AND BOXES. ALL ELECTRICAL ROOMS ARE SHOWN WITH EQUIPMENT DRAWN TO SCALE AND ARRANGED TO ENSURE FIT AND CODE REQUIRED CLEARANCES. EQUIPMENT SHALL BE INSTALLED IN THE LOCATIONS SHOWN, UNLESS WRITTEN APPROVAL IS GIVEN BY THE ENGINEER, BASED UPON 1/4 SCALE DRAWINGS SUBMITTED BY THE CONTRACTOR FOR REVIEW AND APPROVAL. GENERAL LIGHTING/POWER NOTES LIGHT FIXTURES DESIGNATED AS "NIGHT LIGHTS" SHALL BE ON UNSWITCHED CIRCUIT, UNLESS NOTED. EXIT LIGHTS SHALL BE ON UNSWITCHED CIRCUIT, UNLESS NOTED. ALL RECESSED DOWNLIGHTS MOUNTED IN GRID CEILING SHALL BE CENTERED IN CEILING TILE, UNLESS NOTED. IN ALL MECHANICAL ROOMS, COORDINATE EXACT LOCATION OF LIGHT FIXTURES WITH HVAC DUCTWORK. CONDUCTORS FOR BRANCH CIRCUITRY ARE #12 AWG MINIMUM, UNLESS NOTED. DERATE PER CODE WHERE CIRCUITS ARE COMBINED. ALL HOMERUN CONDUCTORS BACK TO PANEL SHALL BE #10 AWG MINIMUM, UNLESS NOTED. PROVIDE A GREEN GROUND CONDUCTOR IN ALL BRANCH CIRCUITRY. DERATE PER CODE WHERE CIRCUITS ARE COMBINED. WHERE TERMINATED IN J-BOX, ALL SPARE CIRCUITRY SHALL BE LABELED WITH PANEL AND CIRCUIT NUMBER. COORDINATE WITH MECHANICAL CONTRACTOR AND PROVIDE ALL NECESSARY AUXILIARY CONTACTS, RELAY, ETC. IN MOTOR STARTERS FOR REQUIRED CONTROL OF MECHANICAL EQUIPMENT. ALL HOME RUN WIRING SHALL BE INSTALLED IN EMT OR RGS CONDUIT, UNLESS NOTED. ALL UNDERGROUND PVC CONDUITS SHALL HAVE RIGID GALVANIZED STEEL ELBOWS. ALL LIGHT FIXTURES SHALL BE SEISMICALLY BRACED WITH AN INDEPENDENT WIRE (CEILING GRID TYPE WIRE) FROM TWO OPPOSITE CORNERS TO STRUCTURAL CEILING OR BAR JOIST. DO NOT SUPPORT CONDUIT OFF OF CEILING GRID, CEILING GRID SUPPORTS, MECHANICAL SUPPORTS, OR ANY OTHER TRADE'S SUPPORTS. INSTALL CONDUITS AND BOXES ON SEPARATE SUPPORTS FROM BAR JOIST OR STRUCTURE. DO NOT SUPPORT FROM METAL ROOF DECK. PROVIDE SUPPORT FROM CONCRETE SLABS, BAR JOIST, STRUCTURAL BEAMS, COLUMNS OR UNISTRUT BETWEEN STRUCTURAL ELEMENTS. ALL SINGLE PHASE CIRCUITS SHALL HAVE A SEPARATE DEDICATED NEUTRAL CONDUCTOR FOR EACH CIRCUIT. SHARING OF NEUTRAL CONDUCTOR IS NOT PERMITTED. PROVIDE 4" HIGH, SMOOTH FINISH CONCRETE HOUSEKEEPING PADS UNDER ALL TRANSFORMERS (45KVA AND LARGER) AND MAIN DISTRIBUTION SWITCHBOARDS. PAD SHALL BE 4" LARGER THAN TRANSFORMER AND SWITCHBOARD IN EACH DIRECTION. USE 3000 PSIG, 28 DAY COMPRESSIVE STRENGTH CONCRETE. ROUND ALL EDGES AND CORNERS OF CONCRETE PAD. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. ABBREVIATIONS A AFF AFG BKR C CATV CUH CKT Cu E EF ELEC EM EMT FCU G GFI GRC HP J KVA AMPS ABOVE FINISHED FLOOR ABOVE FINISHED GRADE BREAKER CONDUIT CABLE TELEVISION CABINET UNIT HEATER CIRCUIT COPPER EXISTING EXHAUST FAN ELECTRICAL EMERGENCY EMERGENCY METALLIC TUBING FAN COIL UNIT GROUND GROUND FAULT INTERRUPTER GALVANIZED RIGID CONDUIT HORSEPOWER JUNCTION BOX KILOVOLT AMPERE KW LGTG MECH NIC NL NTS PVC P TTB TYP UON UV V VAV VIF W WC WP UH UNO KILOWATTS LIGHTING MECHANICAL NOT IN CONTRACT NIGHT LIGHT NOT TO SCALE POLYVINYL CHLORIDE PHASE (POLE) TELEPHONE TERMINAL BOX TYPICAL UNLESS OTHERWISE NOTED UNIT VENTILATOR VOLTS VARIABLE AIR VOLUME VERIFY IN FIELD WATTS WATER COOLER WEATHERPROOF UNIT HEATER UNLESS NOTED OTHERWISE LIGHTING FIXTURE. REFER TO FIXTURE SCHEDULE. LETTER INDICATES TYPE. A A LIGHTING NL B B 3 4 OS P D C GFI WP IG CL M PP11-21 J UE W 4 6 WAP COM EMERGENCY LIGHTING FIXTURE WITH EMERGENCY BALLAST. "NL" INDICATES NIGHT LIGHT CIRCUIT. FULL LUMEN OUTPUT MINIMUM 1400 LUMENS ON LAMP. LIGHTING FIXTURE. LETTER INDICATES TYPE. EMERGENCY LIGHTING FIXTURE WITH EMERGENCY BALLAST. OR POWERED THROUGH INVERTER SYSTEM. CEILING MOUNTED EXIT SIGN. REFER TO FIXTURE SCHEDULE. SHADED AREA DENOTES FACE OF UNIT. CONNECT TO LOCAL UNSWITCHED LIGHTING CIRCUIT. WALL MOUNTED EXIT SIGN. REFER TO FIXTURE SCHEDULE. SHADED AREA DENOTES FACE OF UNIT. CONNECT TO LOCAL UNSWITCHED LIGHTING CIRCUIT. SINGLE POLE WALL SWITCH. 120/277 VOLT, 20 AMP. 44" AFF. THREE WAY WALL SWITCH. 120/277V, 20 AMP. 44" AFF FOUR WAY WALL SWITCH. 120/277V, 20 AMP. 44" AFF OCCUPANCY SENSOR WALL SWITCH. 120/277V, 20 AMP. 44" AFF SINGLE POLE WALL SWITCH WITH PILOT LIGHT. 120/277V, 20 AMP. 44" AFF DIMMER SYSTEM CONTROL STATION. REFER TO DWG ____. OCCUPANCY SENSOR.OS EXTERIOR LIGHT FIXTURE. ER - EXISTING TO REMAIN. PL1 - NEW FIXTURE. REFER TO FIXTURE SCHEDULE. DUPLEX RECEPTACLE. 120 VOLT, 20 AMP. 16" AFF UNO. DUPLEX RECEPTACLE MOUNTED AT 44" OR ABOVE BACKSPLASH. 120 VOLT, 20 AMP. DOUBLE DUPLEX RECEPTACLE. 120 VOLT, 20 AMP. 16" AFF UNO. PT 120 VOLT DOUBLE DUPLEX, 20 AMP RECEPTACLE MOUNTED AT 44" AFF OR 4" ABOVE BACKSPLASH. DUPLEX RECEPTACLE WITH GROUND FAULT PROTECTION. 120 VOLT, 20 AMP. 18" AFF UNO. WEATHERPROOF OUTLET BOX. 120 VOLT DUPLEX , 20 AMP, ISOLATED GROUND RECEPTACLE. 120 VOLT DUPLEX , 20 AMP RECEPTACLE CEILING MOUNTED IN A/V POCKET. OUTLET FOR PROJECTOR REFER TO LV DRAWINGS FOR REQUIREMENTS. FLUSH FLOOR DUPLEX RECEPTACLE IN FLOOR BOX. ELECTRICAL LEGEND POKE THRU FLUSH FLOOR DEVICE WITH POWER, DATA AND A/V. P - POWER 120 VOLT SINGLE 20 AMP RECEPTACLE. SPECIAL PURPOSE RECEPTACLE. REFER TO FLOOR PLANS FOR NEMA CONFIGURATION. FRACTIONAL HP MOTOR STARTER WITH THERMAL OVERLOADS. INDICATES FINAL CONNECTION REQUIRED. HOMERUN TO PANELBOARD. NOTION INDICATES PANEL AND CIRCUIT NUMBER. (ALL CONDUCTORS SHALL BE #10 UNLESS NOTED OTHERWISE.) ELECTRICAL PANELBOARD. JUNCTION BOX. CONDUIT STUB-OUT AND CAP BELOW GRADE. MARK STUB-OUT AT GRADE LEVEL. UNDERGROUND HIGH VOLTAGE OR SECONDARY SERVICE FEED. SAFETY DISCONNECT SWITCH (NON-FUSED). SAFETY DISCONNECT SWITCH (FUSED). COMBINATION MOTOR STARTER/DISCONNECT. WITH HOA SWITCH AT UNIT (FUSIBLE). OR (CIRCUIT BREAKER FOR ELEVATOR). WC 120 VOLT 20 AMP DUPLEX, GFI RECEPTACLE FOR ELECTRIC WATER COOLER. COORDINATE INSTALLATION WITH PLUMBING CONTRACTOR. PLCP BAS PLATFORM LIGHTING CONTROL PANEL. BUILDING AUTOMATION CONTROL PANEL. DATA /COMMUNICATION OUTLET. TWO PORTS REFER TO DETAIL FOR MOUNTING REQUIREMENTS. WALL PHONE. 54" AFF. DATA OUTLET. 16" AFF. DATA/COMMUNICATION. FOUR PORT DATA, 16" AFF. DATA/COMMUNICATION. SIX PORT DATA, 16" AFF. CABLE TRAY ABOVE CEILING. WIRELESS ACCESS CONNECTION POINT WITH CEILING MOUNTED CISCO WIRELESS DEVICE. UNDERGROUND COMMUNICATION DUCT. POWER ELECTRICAL MOTOR. DATA AND COMMUNICATION FIRE ALARM DOOR ACCESS F F D S H SD FACP F Z E.O.L.R. KB SD E C K J F S 1 E-406 1 E-406 1 E-402 EF-1 FIRE ALARM PULL STATION. 44" AFF. FIRE ALARM HORN/STROBE. 80" AFF. S/R FIRE ALARM DUCT MOUNTED SMOKE DETECTOR. S = SUPPLY, R = RETURN - COORDINATE WITH DUCTWORK. MAKE SAMPLING TUBE FULL WIDTH OF DUCT IN LENGTH. FIRE ALARM CEILING MOUNTED SMOKE DETECTOR. FIRE ALARM CEILING MOUNTED HEAT DETECTOR. SMOKE DAMPER. PROVIDE SMOKE DETECTOR FOR DAMPER OPERATION AND 120 VOLT POWER CONNECTION AS SHOWN ON THE POWER DRAWINGS. COORDINATE ALL CONNECTIONS WITH MECHANICAL CONTRACTOR. CONNECT TO ALARM SYSTEM. FIRE ALARM CONTROL PANEL. FIRE ALARM ANNUNCIATOR PANEL. FIRE ALARM STROBE. 80" AFF. MAGNETIC DOOR HOLD OPEN. FIRE ALARM MONITOR MODULE END OF THE LINE RESISTOR. KNOX BOX WITH ALARM CONTACT. DUCT MOUNTED SMOKE DAMPER BY MECHANICAL CONTRACTOR. PROVIDE A DUCT MOUNTED SMOKE DETECTOR, WITH RELAY BASE, MOUNTED WITHIN 5'-0" OF THE DAMPER WITH NO AIR OUTLETS OR INLETS BETWEEN THE DETECTOR AND THE DAMPER. ELECTRIC DOOR STRIKE. DOOR SWITCH/CONTACT. KEY OR KEYCARD ACTIVATED SWITCH IN TAMPER PROOF ENCLOSURE. WP - WEATHERPROOF. JUNCTION BOX HANDICAP DOOR ACCESS BUTTON IN FLUSH WALL BOX. G GROUND ROD 3/4" DIA. x 10' LONG GROUND CABLE EXOTHERMIC WELD CONNECTION TO REBAR ROD IN CONCRETE FOOTER. GROUND CABLE EXOTHERMIC WELD CONNECTION TO BUILDING STEEL. UNDERGROUND COPPER CABLE. L LIGHTNING PROTECTION CABLE. LIGHTNING PROTECTION AIR TERMINAL. DETAIL # ____ DETAIL REFERENCE TAG DRAWING # REFER TO DETAIL SHEETS KEYNOTE FOR DRAWING DETAIL REFERENCE TAG (SECTION) DD DOOR OR CABLETRAY CONFIGURATION DETAIL REFERENCE TAG LETTER NEXT TO TAG REFERS TO SPECIFIC DOOR OR CABLETRAY LAYOUT. CONFIGURATION INDICATED IN DETAIL. MECHANICAL EQUIPMENT TAG. REFER TO EQUIPMENT DATA SCHEDULE. FAAP FWP EXTERIOR FIRE ALARM BELL. WP - WEATHERPROOF RPS FIRE ALARM REMOTE POWER SUPPLY R FIRE ALARM CONTROL RELAY MODULE. GROUNDING LIGHTNING PROTECTION GENERAL V VALVE SUPERVISORY SWITCH PROVIDED BY OTHERS. W WATERFLOW SWITCH PROVIDED BY OTHERS. P FIRE ALARM PRESSURE SWITCH. Sheet Name: Proj. No.: Date: 02/22/18 - GARAGE PERMIT 074904The Proscenium DevelopmentCarmel Development II, LLC.GarageIntersection of Carmel Dr. and Rangeline Rd.Carmel, Indiana 46032ARCHITECTURE ENGINEERING GEOSPATIAL 03/08/18 1 2 3 4 5 6 7 8 9 A B C D E F G 7635 Interactive Way Suite 100 Indianapolis, IN 46278 317.299.7500 FAX: 317.291.5805 Issuances: REV DESCRIPTION DATE BIM 360://74904 - Proscenium - R18/74904 Garage - ELEC R18.rvt3/13/2018 3:49:28 PMELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS EP-001 0 Issued For Garage Permit 02/22/18