HomeMy WebLinkAboutEP-501-ELECTRICAL-DETAILS-Rev.1E.C. SHALL FOLLOW THIS DETAIL FOR
PROPER GROUNDING CONNECTIONS.
TO MAIN
BUILDING
GROUNDING
SYSTEM
SURGE ARRESTOR
EQUIPMENT
GROUND BUS
DISC. LINK
4/0 CU
TO RE-BAR IN CONCRETE
FOUNDATION
CONNECT TO COLD
WATER SYSTEM
#6 CU
MAIN GROUND BUS
NEXT TO MAIN SWITCHBOARD
1600 WATT EMERGENCY LIGHTING INVERTER
BASIS OF DESIGN:
EVENLITE LITEMINDER
CAT # LM-1600VA-1P-IB-OB-C(1)-MB
277V CKT GLP-7
LIGHTING LOAD
DESIGNATED
(APPROX. 1105 CONN.)
277V INVERTER POWER
Sheet Name:
Proj. No.:
Date:
02/22/18 - GARAGE PERMIT
074904The Proscenium DevelopmentCarmel Development II, LLC.GarageIntersection of Carmel Dr. and Rangeline Rd.Carmel, Indiana 46032ARCHITECTURE ENGINEERING GEOSPATIAL
03/08/18
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
G
7635 Interactive Way
Suite 100
Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
Issuances:
REV DESCRIPTION DATE
BIM 360://74904 - Proscenium - R18/74904 Garage - ELEC R18.rvt3/13/2018 3:43:45 PMELECTRICAL DETAILS
EP-501
SCALE : N.T.S.1 GROUNDING DETAIL
SCALE : 12" = 1'-0"2 EMERGENCY LIGHTING DETAILS
0 Issued For Garage Permit 02/22/18