HomeMy WebLinkAboutEP-602-FIRE-ALARM-RISER-AND-SCHEDULE-Rev.1INPUTS FIRE ALARM MATRIX OUTPUTSCOMMONAREAACTUATE COMMON ALARM SIGNAL LAMPACTUATE COMMON SUPERVISORY SIGNAL LAMPACTUATE COMMON TROUBLE SIGNAL LAMPACTUATE PIEZO - FACP \ ANNUNCIATORACTUATE AUDIO\VISUAL DEVICES - GENERAL ALARMACTUATE FIRE\SMOKE DAMPERS BY LOCATIONACTUATE SMOKE RELIEF DAMPER TOP OF ELEVATOR SHAFTSHUTDOWN AIR HANDLER EQUIPMENT WITH ASSOCIATED DUCT DETECTORUNLOCK ACCESS CONTROLLED DOORSRELEASE ELECTROMAGNETICALLY CLOSED DOORSRECALL ELEVATOR TO PRIMARY RECALL FLOORRECALL ELEVATOR TO ALTERNATE RECALL FLOORACTIVATE ELEVATOR WARNING LIGHTSACTIVATE ELEVATOR SHUNT TRIPTRANSMIT SIGNAL TO CENTRAL STATIONAMANUAL PULL BOX SMOKE DETECTOR HEAT DETECTOR DUCT DETECTOR ELEVATORELEVATOR LOBBY SMOKE - NOT FLOOR 1 ELEVATOR LOBBY SMOKE - FLOOR 1 SMOKE DETECTOR ELEVATOR MACHINE ROOM HEAT DETECTOR ELEVATOR MACHINE ROOM SMOKE DETECTOR ELEVATOR PIT HEAT DETECTOR ELEVATOR PIT SMOKE DETECTOR ELEVATOR TOP OF SHAFT HEAT DETECTOR ELEVATOR TOP OF SHAFT FLOW SWITCH ELEVATOR MACHINE ROOM TAMPER SWITCH ELEVATOR MACHINE ROOM FLOW SWITCH TOP OF SHAFT TAMPER SWITCH TOP OF SHAFT FIRESPRINKLERFLOW SWITCH TAMPER SWITCH DRY SYSTEM LOW HI\LOW HEAT TRACE FAULT SYSTEMSYSTEM ALARM SYSTEM SUPERVISORY SYSTEM TROUBLE GROUND FAULT FIRE ALARM SYSTEM LOW BATTERY FIRE ALARM AC POWER FAILURE NOTIFICATION APPLIANCE SHORT CIRCUIT OPEN CIRCUIT 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA BB FFF F F F F F F GARAGE FIRE ALARM CONTROL PANEL V F GARAGE FFF GRP-5 NOTE: POWER CIRCUIT FOR FIRE ALARM PANELS LISTED BELOW EQUIPMENT. ALL DEVICES REQUIRE A CIRCUIT BREAKER W ITH A RED MARKING AND LOCKING DEVICE. OUTSIDE WP GARAGEGARAGE GARAGEGARAGEGARAGEGARAGEGARAGE F GARAGEGARAGEGARAGEGARAGEGARAGE F GARAGE F GARAGE F GARAGE B VVVVWVW VWZ DRY PIPE AIR COMPRESSOR M VWVWVW VWVVVVVVV SVWZ M Z M Z M Z M Z M Z M F BLDG. #1 FIRE ALARM CONTROL PANEL CORR. EMERG. CCT. FS ROOF (GARAGE) (BUILDING #1) FIRST FLOOR FF RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM RISER ROOM . . . . RISER ROOM STAIR 5A EXHAUST FAN #1 EXHAUST FAN #2 EXHAUST FAN #3 EXHAUST FAN #4 EXHAUST FAN #5 EXHAUST FAN #6 CORR. S PIT SSH S F CORR. BLDG. #2 FIRE ALARM CONTROL PANEL EMERG. CCT. ROOF (BUILDING #2) FIRST FLOOR BLDG. #3 FIRE ALARM CONTROL PANEL EMERG. CCT. ROOF (BUILDING #3) FIRST FLOOR BLDG. #4 FIRE ALARM CONTROL PANEL EMERG. CCT. ROOF (BUILDING #4) FIRST FLOOR NOTE: DEVICES TO BE PROVIDED IN FUTURE BUILDING CONSTRUCTION. REFER TO BUILDING FIRE ALARM DRAWINGS FOR ACTUAL NUMBER OF DEVICES. ROOF BLDG. #5 FIRE ALARM CONTROL PANEL EMERG. CCT. ROOF (BUILDING #5) FIRST FLOOR NOTE: DEVICES TO BE PROVIDED IN FUTURE BUILDING CONSTRUCTION. REFER TO BUILDING FIRE ALARM DRAWINGS FOR ACTUAL NUMBER OF DEVICES. NOTE: DEVICES TO BE PROVIDED IN FUTURE BUILDING CONSTRUCTION. REFER TO BUILDING FIRE ALARM DRAWINGS FOR ACTUAL NUMBER OF DEVICES. NOTE: DEVICES TO BE PROVIDED IN FUTURE BUILDING CONSTRUCTION. REFER TO BUILDING FIRE ALARM DRAWINGS FOR ACTUAL NUMBER OF DEVICES. NOTE: DEVICES TO BE PROVIDED IN FUTURE BUILDING CONSTRUCTION. REFER TO BUILDING FIRE ALARM DRAWINGS FOR ACTUAL NUMBER OF DEVICES. TOP OF SHAFT ELEV. MACH. RISER ROOM ELEV. LOBBY F CORR. FS CORR. S PIT SSH S F CORR. TOP OF SHAFT ELEV. MACH. RISER ROOM ELEV. LOBBY F CORR. FS CORR. S PIT SSH S F CORR. TOP OF SHAFT ELEV. MACH. RISER ROOM ELEV. LOBBY F CORR. FS CORR. S PIT SSH S F CORR. TOP OF SHAFT ELEV. MACH. RISER ROOM ELEV. LOBBY F CORR. FS CORR. S PIT SSH S F CORR. TOP OF SHAFT ELEV. MACH. RISER ROOM ELEV. LOBBY FIRE ALARM SYTEM INTENDED OPERTION 1. ACTIVATION OF MANUAL OR AUTOMATIC DETECTION DEVICES LOCATED IN GARAGE SHALL INITIATE NOTIFICATION APPLIANCES IN GARAGE AND ALL OTHER BUILDINGS. 2. ACTIVATION OF MANUAL OR AUTOMATIC DETECTION DEVICES LOCATED IN ANY BUILDING SHALL INITIATE ALARM IN ONLY THE BUILDING IN WHICH THE ALARM INITIATES. 3. SMOKE DETECTORS IN ELEVATOR LOBBIES SHALL ONLY RECALL ELEVATOR IN BUILDING IN WHICH THE ALARM INITIATES. FIRE ALARM GENERAL NOTES 1. VERIFY ALL OUTLET LOCATIONS PRIOR TO ROUGH-IN. 2. REFER TO RELATED ARCHITECTURAL, MECHNICAL, AND STRUCTURAL DRAWINGS FOR RELATED INFORMATION. 3. REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE DRAWINGS. 4. COORDINATE OUTLET BOX LOCATIONS WITH MASONRY TO MINIMIZE CUTTING OF BRICK BLOCK. 5. ALL MOUNTING HEIGHTS TO BOTTOM OF DEVICE UNLESS NOTED OTHERWISE. 6. WHERE AREA SMOKE DETECTORS ARE SHOWN ON THE DRAWINGS ELECTRICAL CONTRACTOR SHALL NOT LOCATE SMOKE DETECTORS CLOSER THAN 3 FEET FROM ANY MECHANICAL AIR SUPPLY OR RETURN DIFFUSER, GRILLE, OR REGISTER PER NFPA. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR LOCATION OF DETECTOR. 7. ALL FIRE ALARM DEVICE LOCATIONS AND DETAILS ARE FOR REFERENCE ONLY. LOCAL GOVERNING CODES AND REQUIREMENTS SHALL TAKE PREFERENCE OVER ALL DETAILS FOR LOCATIONS AND MOUNTING HEIGHTS. VERIFY LOCAL GOVERNING CODES AND REQUIREMENTS WITH LOCAL INSPECTION DEPARTMENT PRIOR TO BID. COMPLETE FIRE ALARM SYSTEM, INSTALLATION AND OPERATION SHALL MEET THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. ALL INITIATING DEVICES MUST BE ADDRESSABLE. "STAND ALONE" DEVICES WILL NOT BE ALLOWED UNLESS REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION. 8. ALL AUDIO DEVICES WITHIN SLEEPING AREAS SHALL PRODUCE A 520 HZ, LOW-FREQUENCY SIGNAL PER N.F.P.A. 72. 9. ALL WALL MOUNTED VISIBLE NOTIFICATION APPLIANCES, LOCATED IN SLEEPING AREAS, SHALL BE NO CLOSER THAN 24" TO THE CEILING AND HAVE A CANDELA RATING NO LESS THAN 110cd. APPLIANCES MOUNTED ON THE WALL CLOSER THAN 24" TO THE CEILING OR ON THE CEILING CHALL HAVE A CANDELA RATING NOT LESS THAN 177cd PER N.F.P.A. 72. Sheet Name: Proj. No.: Date: 02/22/18 - GARAGE PERMIT 074904The Proscenium DevelopmentCarmel Development II, LLC.GarageIntersection of Carmel Dr. and Rangeline Rd.Carmel, Indiana 46032ARCHITECTURE ENGINEERING GEOSPATIAL 03/08/18 1 2 3 4 5 6 7 8 9 A B C D E F G 7635 Interactive Way Suite 100 Indianapolis, IN 46278 317.299.7500 FAX: 317.291.5805 Issuances: REV DESCRIPTION DATE BIM 360://74904 - Proscenium - R18/74904 Garage - ELEC R18.rvt3/13/2018 3:49:32 PMFIRE ALARM RISER AND SCHEDULE EP-602SCALE : N.T.S.1 FIRE ALARM RISER 0 Issued For Garage Permit 02/22/18