HomeMy WebLinkAboutEP-602-FIRE-ALARM-RISER-AND-SCHEDULE-Rev.1INPUTS
FIRE ALARM MATRIX
OUTPUTSCOMMONAREAACTUATE COMMON ALARM SIGNAL LAMPACTUATE COMMON SUPERVISORY SIGNAL LAMPACTUATE COMMON TROUBLE SIGNAL LAMPACTUATE PIEZO - FACP \ ANNUNCIATORACTUATE AUDIO\VISUAL DEVICES - GENERAL ALARMACTUATE FIRE\SMOKE DAMPERS BY LOCATIONACTUATE SMOKE RELIEF DAMPER TOP OF ELEVATOR SHAFTSHUTDOWN AIR HANDLER EQUIPMENT WITH ASSOCIATED DUCT DETECTORUNLOCK ACCESS CONTROLLED DOORSRELEASE ELECTROMAGNETICALLY CLOSED DOORSRECALL ELEVATOR TO PRIMARY RECALL FLOORRECALL ELEVATOR TO ALTERNATE RECALL FLOORACTIVATE ELEVATOR WARNING LIGHTSACTIVATE ELEVATOR SHUNT TRIPTRANSMIT SIGNAL TO CENTRAL STATIONAMANUAL PULL BOX
SMOKE DETECTOR
HEAT DETECTOR
DUCT DETECTOR
ELEVATORELEVATOR LOBBY SMOKE - NOT FLOOR 1
ELEVATOR LOBBY SMOKE - FLOOR 1
SMOKE DETECTOR ELEVATOR MACHINE ROOM
HEAT DETECTOR ELEVATOR MACHINE ROOM
SMOKE DETECTOR ELEVATOR PIT
HEAT DETECTOR ELEVATOR PIT
SMOKE DETECTOR ELEVATOR TOP OF SHAFT
HEAT DETECTOR ELEVATOR TOP OF SHAFT
FLOW SWITCH ELEVATOR MACHINE ROOM
TAMPER SWITCH ELEVATOR MACHINE ROOM
FLOW SWITCH TOP OF SHAFT
TAMPER SWITCH TOP OF SHAFT
FIRESPRINKLERFLOW SWITCH
TAMPER SWITCH
DRY SYSTEM LOW HI\LOW
HEAT TRACE FAULT
SYSTEMSYSTEM ALARM
SYSTEM SUPERVISORY
SYSTEM TROUBLE
GROUND FAULT
FIRE ALARM SYSTEM LOW BATTERY
FIRE ALARM AC POWER FAILURE
NOTIFICATION APPLIANCE SHORT CIRCUIT
OPEN CIRCUIT
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
AA
BB
FFF F F F F F F
GARAGE
FIRE
ALARM
CONTROL
PANEL
V
F
GARAGE
FFF
GRP-5
NOTE:
POWER CIRCUIT FOR FIRE ALARM PANELS LISTED BELOW
EQUIPMENT. ALL DEVICES REQUIRE A CIRCUIT BREAKER W ITH A
RED MARKING AND LOCKING DEVICE.
OUTSIDE
WP
GARAGEGARAGE GARAGEGARAGEGARAGEGARAGEGARAGE
F
GARAGEGARAGEGARAGEGARAGEGARAGE
F
GARAGE
F
GARAGE
F
GARAGE
B
VVVVWVW VWZ
DRY PIPE
AIR
COMPRESSOR
M
VWVWVW VWVVVVVVV
SVWZ
M
Z
M
Z
M
Z
M
Z
M
Z
M
F
BLDG. #1
FIRE
ALARM
CONTROL
PANEL
CORR.
EMERG. CCT.
FS
ROOF
(GARAGE)
(BUILDING #1) FIRST FLOOR
FF
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
RISER
ROOM
.
.
.
.
RISER
ROOM
STAIR
5A
EXHAUST
FAN #1
EXHAUST
FAN #2
EXHAUST
FAN #3
EXHAUST
FAN #4
EXHAUST
FAN #5
EXHAUST
FAN #6
CORR.
S
PIT
SSH
S
F
CORR.
BLDG. #2
FIRE
ALARM
CONTROL
PANEL
EMERG. CCT.
ROOF
(BUILDING #2) FIRST FLOOR
BLDG. #3
FIRE
ALARM
CONTROL
PANEL
EMERG. CCT.
ROOF
(BUILDING #3) FIRST FLOOR
BLDG. #4
FIRE
ALARM
CONTROL
PANEL
EMERG. CCT.
ROOF
(BUILDING #4) FIRST FLOOR
NOTE: DEVICES TO BE PROVIDED IN FUTURE
BUILDING CONSTRUCTION. REFER TO
BUILDING FIRE ALARM DRAWINGS FOR
ACTUAL NUMBER OF DEVICES.
ROOF
BLDG. #5
FIRE
ALARM
CONTROL
PANEL
EMERG. CCT.
ROOF
(BUILDING #5) FIRST FLOOR
NOTE: DEVICES TO BE PROVIDED IN FUTURE
BUILDING CONSTRUCTION. REFER TO
BUILDING FIRE ALARM DRAWINGS FOR
ACTUAL NUMBER OF DEVICES.
NOTE: DEVICES TO BE PROVIDED IN FUTURE
BUILDING CONSTRUCTION. REFER TO
BUILDING FIRE ALARM DRAWINGS FOR
ACTUAL NUMBER OF DEVICES.
NOTE: DEVICES TO BE PROVIDED IN FUTURE
BUILDING CONSTRUCTION. REFER TO
BUILDING FIRE ALARM DRAWINGS FOR
ACTUAL NUMBER OF DEVICES.
NOTE: DEVICES TO BE PROVIDED IN FUTURE
BUILDING CONSTRUCTION. REFER TO
BUILDING FIRE ALARM DRAWINGS FOR
ACTUAL NUMBER OF DEVICES.
TOP OF
SHAFT
ELEV.
MACH.
RISER
ROOM
ELEV.
LOBBY
F
CORR.
FS
CORR.
S
PIT
SSH
S
F
CORR.
TOP OF
SHAFT
ELEV.
MACH.
RISER
ROOM
ELEV.
LOBBY
F
CORR.
FS
CORR.
S
PIT
SSH
S
F
CORR.
TOP OF
SHAFT
ELEV.
MACH.
RISER
ROOM
ELEV.
LOBBY
F
CORR.
FS
CORR.
S
PIT
SSH
S
F
CORR.
TOP OF
SHAFT
ELEV.
MACH.
RISER
ROOM
ELEV.
LOBBY
F
CORR.
FS
CORR.
S
PIT
SSH
S
F
CORR.
TOP OF
SHAFT
ELEV.
MACH.
RISER
ROOM
ELEV.
LOBBY
FIRE ALARM SYTEM INTENDED OPERTION
1. ACTIVATION OF MANUAL OR AUTOMATIC DETECTION DEVICES LOCATED IN GARAGE SHALL
INITIATE NOTIFICATION APPLIANCES IN GARAGE AND ALL OTHER BUILDINGS.
2. ACTIVATION OF MANUAL OR AUTOMATIC DETECTION DEVICES LOCATED IN ANY BUILDING
SHALL INITIATE ALARM IN ONLY THE BUILDING IN WHICH THE ALARM INITIATES.
3. SMOKE DETECTORS IN ELEVATOR LOBBIES SHALL ONLY RECALL ELEVATOR IN BUILDING IN
WHICH THE ALARM INITIATES.
FIRE ALARM GENERAL NOTES
1. VERIFY ALL OUTLET LOCATIONS PRIOR TO ROUGH-IN.
2. REFER TO RELATED ARCHITECTURAL, MECHNICAL, AND STRUCTURAL DRAWINGS FOR
RELATED INFORMATION.
3. REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE DRAWINGS.
4. COORDINATE OUTLET BOX LOCATIONS WITH MASONRY TO MINIMIZE CUTTING OF BRICK
BLOCK.
5. ALL MOUNTING HEIGHTS TO BOTTOM OF DEVICE UNLESS NOTED OTHERWISE.
6. WHERE AREA SMOKE DETECTORS ARE SHOWN ON THE DRAWINGS ELECTRICAL
CONTRACTOR SHALL NOT LOCATE SMOKE DETECTORS CLOSER THAN 3 FEET FROM ANY
MECHANICAL AIR SUPPLY OR RETURN DIFFUSER, GRILLE, OR REGISTER PER NFPA.
ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR LOCATION OF
DETECTOR.
7. ALL FIRE ALARM DEVICE LOCATIONS AND DETAILS ARE FOR REFERENCE ONLY. LOCAL
GOVERNING CODES AND REQUIREMENTS SHALL TAKE PREFERENCE OVER ALL DETAILS FOR
LOCATIONS AND MOUNTING HEIGHTS. VERIFY LOCAL GOVERNING CODES AND
REQUIREMENTS WITH LOCAL INSPECTION DEPARTMENT PRIOR TO BID. COMPLETE FIRE
ALARM SYSTEM, INSTALLATION AND OPERATION SHALL MEET THE REQUIREMENTS OF THE
LOCAL AUTHORITY HAVING JURISDICTION. ALL INITIATING DEVICES MUST BE ADDRESSABLE.
"STAND ALONE" DEVICES WILL NOT BE ALLOWED UNLESS REQUIRED BY LOCAL AUTHORITY
HAVING JURISDICTION.
8. ALL AUDIO DEVICES WITHIN SLEEPING AREAS SHALL PRODUCE A 520 HZ, LOW-FREQUENCY
SIGNAL PER N.F.P.A. 72.
9. ALL WALL MOUNTED VISIBLE NOTIFICATION APPLIANCES, LOCATED IN SLEEPING AREAS,
SHALL BE NO CLOSER THAN 24" TO THE CEILING AND HAVE A CANDELA RATING NO LESS
THAN 110cd. APPLIANCES MOUNTED ON THE WALL CLOSER THAN 24" TO THE CEILING OR ON
THE CEILING CHALL HAVE A CANDELA RATING NOT LESS THAN 177cd PER N.F.P.A. 72.
Sheet Name:
Proj. No.:
Date:
02/22/18 - GARAGE PERMIT
074904The Proscenium DevelopmentCarmel Development II, LLC.GarageIntersection of Carmel Dr. and Rangeline Rd.Carmel, Indiana 46032ARCHITECTURE ENGINEERING GEOSPATIAL
03/08/18
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
G
7635 Interactive Way
Suite 100
Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
Issuances:
REV DESCRIPTION DATE
BIM 360://74904 - Proscenium - R18/74904 Garage - ELEC R18.rvt3/13/2018 3:49:32 PMFIRE ALARM RISER
AND SCHEDULE
EP-602SCALE : N.T.S.1 FIRE ALARM RISER
0 Issued For Garage Permit 02/22/18