HomeMy WebLinkAboutMP-001-HVAC-LEGEND-&-PROJECT-NOTES-Rev.1S
H
T
1-01
RTU
12
4
H-100
4
H-100
ANNOTATION SYMBOL LEGEND
A-8"ø
250
8"ø
24x12
THERMOSTAT OR TEMP. SENSOR
HUMIDISTAT
SWITCH
KEYNOTE DESIGNATION
VAV TERMINAL UNIT MARK
AIR DEVICE MARK - NECK SIZE
AIRFLOW
ROUND DUCT SIZE
RECTANGULAR DUCT SIZE
POINT OF NEW CONNECTION
EQUIPMENT PLAN MARK
SECTION SYMBOL
DETAIL SYMBOL
AIR DEVICE AND DUCT ACCESS. LEGEND
SUPPLY AIR DIFFUSER
(HARD CONNECTION)
RETURN OR EXH. GRILLE
(HARD CONNECTION)
RETURN AIR GRILLE
SIDEWALL DIFFUSER
SUPPLY AIR DIFFUSER WITH FLEXIBLE
RUNOUT AND DAMPER
SUPPLY AIR DIFFUSER
(HARD CONNECTION)
RETURN OR EXHAUST GRILLE
(HARD CONNECTION)
14X14 TRANSFER OPENING IN WALL
TRANSFER OPENING IN WALL
OUTDOOR UNITODU
PC PLUMBING CONTRACTOR
PRESSURE DROPPD
PAINT GRIP GALVANIZED STEELPGGS
PP POLYPROPYLENE
PARTS PER MILLIONPPM
PRESS.PRESSURE
PRESSURE REGULATING VALVEPRV
PS PRESSURE SENSOR
POLY VINYL CHLORIDEPVC
PVCGS PVC COATED GALVANIZED STEEL
RETURN AIRRA
REFRIG.
RECT
RC ROOM CRITERIA LEVEL
RECTANGULAR
REFRIGERANT
MATT FACED FIBERGLASSMFF
A AMPS
HVAC ABBREVIATION LEGEND
ROOF MOUNTED CENTRIFUGAL FAN
RETURN OR RELIEF FAN
RMC
RF
SQUARESQ
LEAVING WET BULB TEMPERATURELWB
HEATING HOT WATERHW
FLOW SWITCH
FEED WATER
NATURAL GASG
FW
FS
SWEAT CONNECTION
SOLVENT WELD
THERMOSTATT
SWLD
SW
CONDENSER WATER PUMPCWP
CONDENSER WATERCW
CU COPPER
CHILLED WATER PUMPCHP
CHILLED WATER SUPPLYCHWS
CHILLED WATER RETURNCHWR
CUBIC FEET PER MINUTECFM
MANUAL DAMPERMD
MINIMUM CIRCUIT AMPSMCA
MECHANICAL CONTRACTORMC
1000 BTUHMBH
MATERIALMAT.
MOTORIZEDM
LEAVING WATER TEMPERATURELWT
LOUVERLVR
LOW PRESSURE STEAMLPS
LIQUID PROPANELP
LEAVING DRY BULB TEMPERATURELDB
LEAVING AIR TEMPERATURELAT
INLINE CENTRIFUGAL FANILC
HOT WATER SUPPLYHWS
HOT WATER RETURNHWR
HOT WATER PUMPHWP
HOT WATER BOILERHWB
HEATING/VENTILATING UNITHV
HUMIDITY SENSORHS
HIGH PRESSURE STEAMHPS
HORSE POWERHP
HOT GAS (REFRIGERANT)HG
HEAT FUSIONHF
HEATING CONTRACTORHC
HUMIDIFIER (HUMIDITY)H
GALVANIZED STEELGS
GROOVED PIPEGRV
GALLONS PER MINUTEGPM
GALLONS PER HOURGPH
GENERAL CONTRACTORGC
GALVANIZEDGALV
GA GAGE (GAUGE)
DRAIND
TC TOTAL CAPACITY
DB DECIBELS
TEMP.TEMPERATURE
DCW DOMESTIC COLD WATER
TH THICKNESS
DDC DIRECT DIGITAL CONTROLS
THRD THREADED
DHW DOMESTIC HOT WATER
TOD TOP OF DUCT
DMPR DAMPER
TOJ TOP OF JOIST
DS DUCT SILENCER (SOUND ATTENUATOR)
TOS TOP OF STEEL
DT DUAL TEMPERATURE
TS TEMPERATURE SENSOR
DTP DUAL TEMPERATURE PUMP
T/S PIPE TYPE OR SCHEDULE
DTR DUAL TEMPERATURE RETURN
UBC UPBLAST CENTRIFUGAL FAN
DTS DUAL TEMPERATURE SUPPLY
UC FLEXIBLE UNICELLULAR
E-AL EMBOSSED ALUMINUM
UH UNIT HEATER
EAT ENTERING AIR TEMPERATURE
UV UNIT VENTILATOR
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB TEMPERATURE
EF EXHAUST FAN
EH ELECTRIC HEATER
V VOLTS
EWB ENTERING WET BULB TEMPERATURE
VAV VARIABLE AIR FLOW
EWT ENTERING WATER TEMPERATURE
VC VENTILATING CONTRACTOR
EXH EXHAUST
WCS WROUGHT CARBON STEEL
F FURNACE
WCU WROUGHT COPPER
FCU FANCOIL UNIT
WLD WELDED CONNECTION
FD FIRE DAMPER
WMP WALL MOUNTED PROPELLER FAN
FFJ FOIL FACED JACKET
WPD WATER PRESSURE DROP
FG FIBERGLASS
WT WEIGHT (OR DENSITY)
FGB FIBERGLASS BOARD INSULATION
FGW FIBERGLASS WRAP
FLA FULL LOAD AMPS
FLG FLANGE
FLGD FLANGED
FMG FOAM GLASS
FPM FEET PER MINUTE
FPP FAN POWERED PARALLEL VAV
FPS FAN POWERED SERIES VAV
STAINLESS STEELSS
COOLING TOWERCT
SHUT OFF VALVE TERMINALSO
CARBON STEELCS
SUPPLY FANSF
CONDENSATE RETURN PIPECRP
SCREWED (THREADED)SCR
STEAM CONDENSATE RETURNCR
SCHEDULESCH
CHLORINATED PVCCPVC
SENSIBLE CAPACITYSC
CONCRETECONC.
SUPPLY AIRSA
CEILING MOUNTED CENTRIFUGAL FANCMC
SWITCHS
CENTERLINE OF PIPECLP
RELIEF VALVERV
CENTERLINECL
CAST IRONCI
ROOF TOP UNITRTU
ROOF MOUNTED PROPELLER FANRMP
CHILLED WATERCHW
REFRIGERANT LIQUIDRL
CHILLERCH
CUBIC FEETCF
CALCIUM CARBONATE POWDERCCP
CALCIUM SILICATE INSULATIONCAL
CORRUGATED ALUMINUMC-AL
BRAZEDBR
BOTTOM OF PIPEBOP
BOTTOM OF DUCTBOD
BRAKE HORSE POWERBHP
BACKDRAFT DAMPERBDD
BUILDING AUTOMATION SYSTEMBAS
STEAM BOILERB
ON CENTERO.C.
ALL SERVICE INSULATION JACKETASJ
OPPOSED BLADE DAMPEROBD
AIR PRESSURE DROPAPD
OUTSIDE AIROA
ALUMINUMALUM
NOISE CRITERIA LEVELNC
ABOVE FINISHED FLOORAFF
MAKE UP AIRMUA
ACR COPPER REFRIG PIPEACR
MALLEABLE IRONMI
AIR COOLED CONDENSING UNITACC
HEAT RECLAIM WATERHRC
PIPE SYMBOL LEGEND
FEED WATER PIPEFW
CR
NATURAL GAS PIPE
VENT PIPE
LPS
MPS
RL
RS
RHG
LPG
DTS
DTR
DHW
CHWS
CHWR
HWS
HWR
DCW
CWR
CWS
G
V
HPS
DUAL TEMPERATURE SUPPLY PIPE
DUAL TEMPERATURE RETURN PIPE
HEATING HOT WATER SUPPLY PIPE
HEATING HOT WATER RETURN PIPE
CONDENSATE RETURN PIPE
CONDENSER WATER RETURN PIPE
CONDENSER WATER SUPPLY PIPE
LOW PRESSURE STEAM PIPE
MEDIUM PRESSURE STEAM PIPE
REFRIGERANT LIQUID PIPE
REFRIGERANT SUCTION PIPE
REFRIGERANT HOT GAS PIPE
LIQUID PROPANE GAS PIPE
DOMESTIC HOT WATER PIPE
CHILLED WATER SUPPLY PIPE
DOMESTIC COLD WATER PIPE
CHILLED WATER RETURN PIPE
HIGH PRESSURE STEAM PIPE
30-240deg. F
UNION
TEE DOWN
PIPE UP
PIPE DOWN
CAPPED PIPE
TEE UP
BALL VALVE
BUTTERFLY VALVE
GAS SHUT-OFF VALVE
CALIBRATED BALANCE VALVE
PRESSURE REGULATING VAVLE
GATE VAVLE
GLOBE VALVE
STRAINER
BLIND FLANGE
PIPE BREAK (FOR CLARITY)
STRAINER WITH BLOW DOWN VALVE
MOTORIZED 2-WAY VALVEM
M
MOTORIZED 3-WAY VALVE
PRESSURE RELIEF VALVE
0-100psig PRESSURE
GAGE THERMOMETER
M
RETURN OR EXHAUST AIR DUCT DOWN
DUCTWORK SYMBOL LEGEND
FIREDAMPER
MOTORIZED DAMPER
MANUAL BALANCING DAMPER
SUPPLY/ OUTSIDE AIR DUCT OFFSET
RETURN AIR DUCT OFFSET
RETURN OR EXHAUST AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
RECTANGULAR BRANCH TAKEOFF
RECTANGULAR DUCT TERMINATION
ROUND DUCT TERMINATION
ROUND WYE
ROUND ELBOW
ROUND OFFSET
ROUND DUCT DOWN
SUPPLY OR OUTSIDE AIR ROUND
DUCT UP
RADIUS RECTANGULAR ELBOW
STANDARD RECTANGULAR ELBOW
RECTANGULAR TRANSITION
RECTANGULAR TO ROUND TRANSITION
A-24x12
250
GLYS
GLYR
ICE WATER SUPPLY PIPE
ICE WATER RETURN PIPE
SCHEMATIC SYMBOL LEGEND
M AUTOMATIC 2-WAY CONTROL VALVE
AUTOMATIC 3-WAY CONTROL VALVEM
AUTOMATIC FLOW CONTROLLER
CHECK VALVE
FLEXIBLE CONNECTION
GAUGE, T-TEMPERATURE; P-PRESSURE
T/P
MANUAL BALANCE VALVE
PIPE REDUCER/INCREASER
PRESSURE REDUCING VALVE
SHUTOFF VALVE
COMBINATION BALANCE-SHUTOFF VALVE
TRIPLE DUTY VALVE;
SHUTOFF-BALANCE-CHECK
TDV
DIRECTION OF FLOW
AIR VENT, MV-MANUAL VENT; AV-
AUTOMATIC VENT
MV/AV
SAFETY RELIEF VALVE
AHU-1 EQUIPMENT MARK
RETURN OR EXHAUST AIR ROUND
DUCT UP
XXX
1.INSTALL THE H.V.A.C. SYSTEM AS INDICATED IN ACCORDANCE WITH ALL STATE AND LOCAL CODES.
2.COORDINATE ALL WORK WITH OTHER TRADES. REWORK OF PIPING, DUCTWORK, EQUIPMENT LOCATION, CONDUIT, ETC. AS
A RESULT OF POOR PLANNING. COORDINATION OR SCHEDULING SHALL BE THE RESPONSIBILITY OF THE INVOLVED
CONTRACTORS. NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS PRIOR TO START OF WORK.
3.THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ANY FRAMING REVISIONS,
EQUIPMENT LOCATIONS, ADDITION OF CONTROLS, ELECTRICAL CIRCUITING REVISIONS, ETC. THAT RESULT FROM
4.USING EQUIPMENT OTHER THAN THOSE INDICATED ON THE DRAWINGS. APPROVAL OF THE SHOP DRAWINGS BY THE
ARCHITECT/ENGINEER WILL NOT WAIVE THE CONTRACTOR OF THIS RESPONSIBILITY.
5.THE MECHANICAL CONTRACTOR SHALL HAVE THE FINAL RESPONSIBILITY FOR SYSTEM START UP, TRAINING, WARRANTY
AND TURN OVER TO THE OWNER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTRUCTING THE OWNER ON ANY
ROUTINE MAINTENANCE REQUIRED DURING THE WARRANTY PERIOD.
6.ALL ITEMS INCLUDED ON THESE DRAWINGS AND THE SPECIFICATIONS SHALL BE INCLUDED IN THE CONTRACTORS BID. ANY
ITEMS THAT ARE UNCLEAR OR FOUND TO BE INCORRECT BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION
OF THE ARCHITECT/ENGINEER PRIOR TO THE BID DUE DATE. EXCLUSIONS OF WORK FROM THE BID ARE NOT ACCEPTABLE.
7.ALL WORK INDICATED ON THE MECHANICAL DRAWINGS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR UNLESS
SPECIFICALLY NOTED OTHERWISE.
8.THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL FIRESTOPPING FOR DUCT AND PIPE PENETRATIONS THAT
PENETRATE FIRE RATED ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS OR REFER TO THE OWNERS RECORD DRAWINGS
FOR LOCATIONS OF FIRE RATED ASSEMBLIES. ALL FLOOR PENETRATIONS SHALL BE FIRESTOPPED AND SEALED WATER
TIGHT WITH A FLEXIBLE SEALANT. INSTALL PER MFG. RECOMMENDATIONS.
9.THE MECHANICAL CONTRACTOR SHALL COORDINATE ANY ROOF PATCHING FOR ANY MECHANICAL ROOF PENETRATIONS
NOT SPECIFICALLY IDENTIFIED ON THE ARCHITECTURAL DRAWINGS. ALL PATCHING SHALL BE PROVIDED BY GENERAL
CONTRACTOR AND BE PERFORMED IN A MANNER CONSISTENT WITH THE ROOF SYSTEMS CURRENT WARRANTY
REQUIREMENTS AND MANUFACTURERS RECOMMENDATIONS.
10.THE MECHANICAL CONTRACTOR SHALL NOT PERFORM ANY WELDING OR TORCH CUTTING OPERATIONS WITHIN THE
OCCUPIED BUILDING WITHOUT OBTAINING PERMISSION OR A BURN PERMIT FROM THE OWNER.
GENERAL:
1.THE H.V.A.C. EQUIPMENT AND SYSTEM SHALL NOT BE USED TO DURING CONSTRUCTION. THE WARRANTY PERIOD SHALL
NOT BEGIN UNTIL SUBSTANTIAL COMPLETION. THE CONTRACTOR SHALL EXTEND THE EQUIPMENT WARRANTY PERIOD AS
NECESSARY WHEN EQUIPMENT IS USED AFTER INITIAL START UP AND PRIOR TO SUBSTANTIAL COMPLETION.
EQUIPMENT - GENERAL
1.ALL DUCTWORK SHALL BE CONSTRUCTED, INSTALLED AND SUPPORTED PER THE LATEST VERSION OF THE S.M.A.C.N.A.
H.V.A.C. DUCT CONSTRUCTION STANDARDS. UNLESS SPECIFIED MORE STRINGENTLY IN THESE CONSTRUCTION
DOCUMENTS.
2.COORDINATION OF DUCT SYSTEM INSTALLATION WITH OTHER TRADES SHALL BE PERFORMED PRIOR TO THE FABRICATION
OF ANY DUCTWORK. VERIFY DUCT CLEARANCES PRIOR TO FABRICATION. NOTIFY THE ARCHITECT/ENGINEER OF ANY
CONFLICTS THAT REQUIRE DIMENSIONAL CHANGES OR REQUIRE MAJOR RELOCATION OF DUCTWORK.
3.ALL DUCTWORK SHALL BE SUPPORTED FROM ROOF OR FLOOR STRUCTURE ABOVE. DUCTWORK SHALL NOT LAY ON TOP
OF CEILING OR LIGHT FIXTURES.
4.ALL DUCTWORK SIZES SHOWN ARE EXTERNAL DIMENSIONS. ALLOWANCE HAS BEEN MADE FOR 1" DUCTLINER WHERE AND
IF REQUIRED.
5.RECTANGULAR DUCTWORK SHALL BE SUPPORTED PER THE S.M.A.C.N.A. STANDARDS AND AT EACH CHANGE IN DIRECTION.
DUCTWORK - GENERAL:
PROJECT NOTES
1.PROVIDE PROJECT SPECIFIC CONTROL SYSTEM MANUAL FOR THE BUILDING. THE MANUAL SHALL
CONTAIN A DIAGRAM OF THE CONTROL SYSTEM ARCHITECTURE, WIRING DIAGRAMS AND A SEQUENCE
OF OPERATION. THE MANUAL SHALL ALSO INCLUDE AN 11 X 17 FLOOR PLAN INDICATING THE MAJOR
EQUIPMENT AND PANEL LOCATIONS. THE MANUAL SHALL BE BOUND IN A HARD BACK 3 RING BINDER
WITH DIVIDERS. BINDER SHALL BE LABELED "H.V.A.C TEMPERATURE CONTROL MANUAL" AND INCLUDE
THE PROJECT NAME AS WELL AS THE BUILDING NAME, NUMBER AND ADDRESS.
2.LABEL ALL CONTROL PANELS, ACTUATORS, SENSORS, ETC WITH 1/8" THICK PLASTIC LAMINATE SIGNS.
SEE DRAWINGS FOR LABEL AND LETTERING REQUIREMENTS. LABEL DESIGNATIONS SHALL BE
CONSISTENT WITH THE DRAWINGS, TEMPERATURE CONTROL SYSTEM MANUAL AND DIAGRAMS.
3.MOUNT WALL MOUNTED THERMOSTATS, TEMPERATURE SENSORS AND CARBON MONOXIDE SENSORS
4'-0" ABOVE FINISH FLOOR. DO NOT MOUNT THERMOSTATS OR TEMPERATURE SENSORS IN DIRECT
SUNLIGHT OR NEAR HEAT PRODUCING EQUIPMENT.
4.THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY AND ALL INTERFACE
WIRING REQUIRED BETWEEN THE TEMPERATURE CONTROL SYSTEM AND THE FIRE ALARM SYSTEM.
THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE INTERFACE TERMINALS AS PART OF THE FIRE
ALARM SYSTEM AS REQUIRED TO PROVIDE THE SPECIFIED SEQUENCE OF OPERATION.
5.THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL MOTOR STARTERS AND DISCONNECT SWITCHES
FOR H.V.A.C. EQUIPMENT UNLESS THEY ARE INCLUDED WITH THE EQUIPMENT AS INDICATED ON THE
DRAWINGS AND IN THE SPECIFICATIONS. COORDINATE STARTER REQUIREMENTS WITH THE
ELECTRICAL CONTRACTOR AND THE CONTRACTOR PRIOR TO ORDERING.
6.WHERE AUXILIARY CONTACTS ARE REQUIRED IN STARTERS PROVIDED BY THE ELECTRICAL
CONTRACTOR, THE MECHANICAL CONTRACTOR SHALL COORDINATE THE QUANTITY AND TYPE OF
CONTACTS WITH THE E.C. PRIOR TO PURCHASE.
7.THE ELECTRICAL CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS IN THE ELECTRICAL PANELS THAT
ARE SPECIFICALLY DEDICATED FOR THE TEMPERATURE CONTROL SYSTEM. COORDINATE THE
QUANTITY AND SIZES WITH THE CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR LOCATION.
8.THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL TEMPERATURE CONTROL SYSTEM WIRING AND
CONDUIT REGARDLESS OF VOLTAGE AS REQUIRED TO PROVIDE THE SPECIFIED SEQUENCE OF
OPERATION OR SATISFY ANY MANUFACTURER REQUIREMENTS. POWER AND CONTROL WIRING AND
CONDUIT FOR VALVE ACTUATORS, DAMPER ACTUATORS, CARBON MONOXIDE SENSORS,
TEMPERATURE CONTROL PANELS, RELAYS, INDICATOR LIGHTS, REMOTE CONTROL PANELS, SOLENOID
VALVES AND OTHER SIMILAR DEVICES THAT ARE PART OF THE H.V.A.C SYSTEM SHALL BE PROVIDED
BY THE MECHANICAL CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR THE LOCATION OF CIRCUIT
BREAKERS SPECIFICALLY DEDICATED FOR TEMPERATURE CONTROL SYSTEM COMPONENTS. ALL 120 V
CONTROL WIRING SHALL BE INSTALLED IN CONDUIT. CONCEALED ABOVE CEILING PLENUM RATED LOW
VOLTAGE (24 VOLTS OR LESS) CONTROL WIRING DOES NOT REQUIRE TO BE INSTALLED IN CONDUIT.
9.THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL CONTROLS, RELAYS, SENSORS, CONTROLLERS,
CONTROL TRANSFORMERS, CONTROL INTERFACE COMPONENTS, SOFTWARE, HARDWARE,
ACTUATORS, SWITCHES AND ANY OTHER CONTROL COMPONENTS REQUIRED TO PROVIDE THE
SPECIFIED SEQUENCE OF OPERATIONS ON PLANS, TO INTEGRATE PROJECT CONTROLS AND SYSTEM,
AND TO MEET EQUIPMENT MANUFACTURER'S INSTALLATION AND OPERATION REQUIREMENTS,
UNLESS NOTED OTHERWISE ON PLANS.
10.IT SHALL BE THE MECHANICAL CONTRACTORS RESPONSIBILITY TO COORDINATE ALL TEMPERATURE
CONTROL SYSTEM REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR PRIOR TO THE PURCHASE
OR INSTALLATION OF ANY OF THE ELECTRICAL POWER OR TEMPERATURE CONTROL SYSTEM
COMPONENT.
11.ALL DAMPERS ON THE INLET OR OUTLET OF THE FAN SHALL BE OPEN PRIOR TO STARTING THE FAN.
PROVIDE ANY TIME DELAYS OR END SWITCHES AS REQUIRED.
12.PROVIDE CLEAR PLASTIC VENTED IMPACT RESISTANT LOCKABLE GUARDS ON ALL WALL MOUNTED
THERMOSTATS OR SENSORS WITH ADJUSTABLE SET-POINTS.
PROJECT NOTES
CONTROL NOTES:
1.PROVIDE PLASTIC LAMINATE IDENTIFICATION LABELS ON ALL EQUIPMENT SCHEDULED ON THE
DRAWINGS. THE IDENTIFICATION SHALL BE CONSISTENT WITH THE PLANMARKS SHOWN ON THE
DRAWINGS AND THE BAS SYSTEM USER INTERFACE. SEE DETAILS ON DRAWINGS REGARDING COLOR,
SIZE, TEXT HEIGHT, ETC.
2.PROVIDE PLASTIC LAMINATE IDENTIFICATION LABELS ON ALL TEMPERATURE CONTROL COMPONENTS
SUCH AS CONTROL PANELS, TEMPERATURE SENSORS, HUMIDITY SENSORS, ETC. THE IDENTIFICATION
SHALL BE CONSISTENT WITH THE PLANMARKS SHOWN ON THE DRAWINGS WHERE AVAILABLE AND
THE BAS SYSTEM USER INTERFACE. SEE DETAILS ON DRAWINGS REGARDING COLOR, SIZE, TEXT
HEIGHT, ETC.
3.PLASTIC LAMINATE SIGNS AND LABELS ON OUTDOOR EQUIPMENT SHALL BE FIXED TO EQUIPMENT
WITH STAINLESS STEEL OR ALUMINUM RIVETS OR STAINLESS STEEL OR PLATED SCREWS.
4.CLEAN EQUIPMENT AND PIPING PRIOR TO AFFIXING ADHESIVE TYPE LABELS AND SIGNS.
IDENTIFICATION:
DESIGN CRITERIA
INDOOR DESIGN CONDITIONS
STAIRWELL WINTER DRY BULB:60.0°FBUILDING
LOCATION:
LATITUDE:
LONGITUDE:
ELEVATION:
SUMMER DRY
BULB:
SUMMER WET
BULB:
WINTER DRY
BULB:
OUTDOOR DESIGN CONDITIONS
GENERAL DESIGN INFORMATION
CARMEL, INDIANA
39.97
86.13
853
91.3°F (0.4% ASHRAE DESIGN
CONDITION)
75.0°F (0.4% ASHRAE DESIGN
CONDITION)
2.6°F (99.6% ASHRAE DESIGN
CONDITION)
Sheet Name:
Proj. No.:
Date:
02/22/18 - GARAGE PERMIT
074904TheProsceniumDevelopmentCarmelDevelopmentII,LLC.GarageIntersectionofCarmelDr.andRangelineRd.Carmel,Indiana46032ARCHITECTURE ENGINEERING GEOSPATIAL
02/22/18
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
G
7635 Interactive Way
Suite 100
Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
Issuances:
REV DESCRIPTION DATE
BIM360://74904-Proscenium-R18/74904Garage-MECHPLUMBR18.rvt7/2/20189:55:19AMHVAC LEGEND &
PROJECT NOTES
MP-001
0 Issued for Garage Permit 02/22/18