HomeMy WebLinkAboutMP-601-HVAC-SCHEDULES-&-SEQUENCE-OF-OPERATIONS-Rev.1Sheet Name:
Proj. No.:
Date:
02/22/18 - GARAGE PERMIT
074904TheProsceniumDevelopmentCarmelDevelopmentII,LLC.GarageIntersectionofCarmelDr.andRangelineRd.Carmel,Indiana46032ARCHITECTURE ENGINEERING GEOSPATIAL
02/22/18
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
G
7635 Interactive Way
Suite 100
Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
Issuances:
REV DESCRIPTION DATE
BIM360://74904-Proscenium-R18/74904Garage-MECHPLUMBR18.rvt7/2/20189:55:21AMHVAC SCHEDULES &
SEQUENCE OF
OPERATIONS
MP-601
PLAN
MARK TYPE
ELECTRICAL
SERVICE CFM ESP
("WC)
WHEEL
SIZE DRIVE SONES
HP VOLT PHASE
NOTES
FAN SCHEDULE
NOTES:
1 PROVIDE WITH MOTOR SAFETY GUARD HOUSING WITH BIRDSCREEN
2 VARIABLE FREQUENCY DRIVE
3 PROVIDE MANUFACTURER APPROVED SUSPENSION WITH VIBRATION ISOLATION
4 INTERFACE WITH CO MONITOR SYSTEM
5 PROVIDE DISCONNECT SWITCH. INSTALLED BY E.C.
6 WALL HOUSING
EF-1 GREENHECK MODEL SE2-48 GARAGE 21,875 0.25"-DIRECT 40 3 480 3 1, 2, 3, 4, 5, 6
PLAN
MARK AREA
SERVED
ELECTRICAL
MFR MODEL TYPE CFM KW
V/PH MCA
NOTES
ELECTRIC HEATER SCHEDULE MARK NO: UH
NOTES:
1 INTERNAL TEMPERATURE DOUBLE POLE THERMOSTAT/CIRCUIT BREAKER DISCONNECT
2 DISCONNECT PROVIDED BY E.C.
3 PROVIDE WALL MOUNTING BRACKET
4 PROVIDE RECESSED WALL MOUNT KIT
5 NEMA PREMIUM EFFICIENCY MOTOR
UH-1 STAIRWELL MARKEL 3450 WALL 245 5 208/3 -1, 2, 4, 5
LENGTH
14 1/4"
DIMENSIONS
HEIGHT
23 1/16"
DEPTH
4 1/4"
RECESS
YES
MARK NO: EF
EF-2 GARAGE 21,875 3 480 3
EF-3 GARAGE 21,875 3 480 3
EF-4 GARAGE 21,875 3 480 3
EF-5 GARAGE 21,875 3 480 3
EF-6 GARAGE 21,875 3 480 3
UH-2 STAIRWELL MARKEL 3450 WALL 5 -YES
UH-3 STAIRWELL MARKEL 3450 WALL 5 -YES
UH-4 STAIRWELL MARKEL 3450 WALL 5 -YES
UH-5 STAIRWELL MARKEL 3450 WALL 5 -YES
UH-6
UH-7
UH-8
STORAGE ROOM MARKEL UH SUSPENDED 400 5 480/3 -20"13"11"NO
UH-9
STORAGE ROOM MARKEL UH SUSPENDED 5 480/3 -NO
STORAGE ROOM MARKEL UH SUSPENDED 5 480/3 -NO
STORAGE ROOM MARKEL UH SUSPENDED 5 480/3 -NO
245
245
245
245
14 1/4"23 1/16"4 1/4"
14 1/4"23 1/16"4 1/4"
14 1/4"23 1/16"4 1/4"
14 1/4"23 1/16"4 1/4"
400
400
400
20"13"11"
20"13"11"
20"13"11"
-
-
-
-
-
MARK MFR
LOUVER SCHEDULE
NOTES:
L-1 AIROLITE 1,2
NOTES
1 COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER STANDARD COLORS.
2 PROVIDE WITH BIRDSCREEN
AREA WELL LOUVER
DESCRIPTION MODEL
K6776
MOUNTING
WALL
FINISH
KYNAR
MATERIAL
ALUM.-
ACCESSORIES
BASIS OF DESIGN
MARK NO: L
208/3
208/3
208/3
208/3
1, 2, 4, 5
1, 2, 4, 5
1, 2, 4, 5
1, 2, 4, 5
1, 2, 3, 5
1, 2, 3, 5
1, 2, 3, 5
1, 2, 3, 5
ELECTRIC UNIT HEATERS (UH-1 THRU UH-9)
FAN:
1.THE FAN SHALL CYCLE ON A CALL FOR HEATING.
HEATING ELEMENT:
1.ON A FALL BELOW THE SPACE HEATING SET POINT OF 60°F(ADJ.), THE
HEATER SHALL TURN ON UNTIL SPACE HEATING SET POINT IS SATISFIED.
MONITORING AND CONTROL POINTS (MINIMUM LISTED, PROVIDE ADDITIONAL
POINTS AS NECESSARY TO PROVIDE THE SPECIFIED SEQUENCE OF OPERATION).
1.FAN STATUS
2.FAN ON/OFF
3.SPACE TEMPERATURE
4.SENSOR NORM/FAIL STATUS
SEQUENCE OF OPERATIONS
EXHAUST FANS (EF-1 THRU EF-6)
1.THREE LEAD EXHAUST FANS SHALL RUN CONTINUOUSLY AT MINIMUM
SPEED. TWO GROUPS OF LEAD EXHAUST FANS SHALL ROTATE WEEKLY
BETWEEN EF-1, EF-3, EF-5 AND EF-2, EF-4, EF-6. MINIMUM GARAGE
EXHAUST CFM SHALL NEVER DROP BELOW 8,750 CFM TOTAL.
2.WHEN CARBON MONOXIDE LEVELS OF 25 PPM OR GREATER ARE
SENSED, LEAD EXHAUST FANS SHALL RAMP UP TO 50% FOR 5 MINUTES
(ADJ.) TO REDUCE LEVELS BELOW 25 PPM. AFTER 5 MINUTES IF THE CO
LEVELS ARE ABOVE 25 PPM THE LEAD FANS SHALL RAMP UP TO 80% FOR
10 MINUTES (ADJ.). ONCE CO LEVELS HAVE BEEN REDUCE TO BELOW 25
PPM, THE LEAD EXHAUST FANS SHALL STAY CONSTANT FOR 20 MINUTES
BEFORE RAMPING BACK DOWN TO MINIMUM SPEED.
3.IF THREE LEAD EXHAUST FANS REACH 80% SPEED WITHOUT
MAINTAINING CO CONCENTRATION FOR 10 MINUTES (ADJ.), THE LEAD
EXHAUST FANS SHALL RAMP DOWN TO 50% SPEED WHILE THE
REMAINING THREE LAG FANS SHALL START AT 50% SPEED. ALL FANS
SHALL SIMULTANEOUSLY RAMP UP FROM 50% AS NEEDED TO MEET
AND MAINTAIN CO CONCENTRATION LEVELS BELOW 25 PPM. ONCE CO
LEVELS ARE REDUCED TO BELOW 25 PPM, THE FANS SHALL REMAIN
CONSTANT FOR 20 MINUTES (ADJ.). AFTER 20 MINUTES, ALL FANS
SHALL RAMP DOWN TO 50% SPEED. ONCE THE FANS HAVE RAMPED
DOWN TO 50% SPEED AND CO LEVELS ARE BELOW 25 PPM, THE LAG
FANS SHALL TURN OFF AND LEAD FANS SHALL RAMP DOWN TO
MINIMUM SPEED.
ALARMS:
ALARMS (MINIMUM LISTED , PROVIDE ADDITIONAL POINTS AS NECESSARY TO
PROVIDE THE SPECIFIED SEQUENCE OR OPERATION)
1.FAN FAILURE (DRIVE OR MOTOR)
MONITORING AND CONTROL POINTS (MINIMUM LISTED, PROVIDE ADDITIONAL
POINTS AS NECESSARY TO PROVIDE THE SPECIFIED SEQUENCE OF OPERATION)
1.FAN STATUS
2.FAN ENABLE/DISABLE
3.FAN VARIABLE FREQUENCY DRIVE OUTPUT (%)
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6
40
40
40
40
40
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
0.25"
0.25"
0.25"
0.25"
0.25"
GREENHECK MODEL SE2-48
GREENHECK MODEL SE2-48
GREENHECK MODEL SE2-48
GREENHECK MODEL SE2-48
GREENHECK MODEL SE2-48
0 Issued for Garage Permit 02/22/18