HomeMy WebLinkAboutP-100-UNDERGROUND-PLUMBING-AND-FIRE-PROTECTION-PLAN---OVERALL-Rev.1A
B
C
D
E
F
H
J
K
L
M
N
1 2 3 4 5 6 7 14
17 18 19 20 21 22 23 24
G
AREA A-DRAWING P-101 AREA B-DRAWING P-102
AREA C-DRAWING P-103
AREA D-DRAWING P-104
AREA E-DRAWING P-105 AREA F-DRAWING P-106
13.9 14.1 16.6 17.6 18.6 19.6 20.62.5 2.9
2
P-501
P-502
2
K.6
FUTURE BLDG. #1 FUTURE BLDG. #4
PROVIDE CAPPED ROUGH-IN FOR
FUTURE DRY PIPE SPRINKLER SYSTEMS
IN THESE AREAS FROM GARAGE.
1
9 10 11 12
16
84.53.4 13 15
Sheet Name:
Proj. No.:
Date:
02/22/18 - GARAGE PERMIT
074904TheProsceniumDevelopmentCarmelDevelopmentII,LLC.GarageIntersectionofCarmelDr.andRangelineRd.Carmel,Indiana46032ARCHITECTURE ENGINEERING GEOSPATIAL
02/22/18
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
G
7635 Interactive Way
Suite 100
Indianapolis, IN
46278
317.299.7500
FAX: 317.291.5805
Issuances:
REV DESCRIPTION DATE
BIM360://74904-Proscenium-R18/74904Garage-MECHPLUMBR18.rvt5/8/20181:17:13PMUNDERGROUND
PLUMBING AND FIRE
PROTECTION PLAN -
OVERALL
P-100
1" = 20'-0"1
GARAGE UNDERGROUND PLUMBING AND FIRE PROTECTION
PLAN - OVERALL
KEY PLAN
A
E F
B C
NORTH
D
NOTES:
1.THE INTENT OF THIS DRAWING (SHEET P-100) IS TO PROVIDE AN OVERALL VIEW OF ALL PIPING SYSTEMS LOCATED BELOW FLOOR AND EXTENDING TO ABOVE THE GARAGE FLOOR.
2.DRAWING P-100 INCLUDES BOTH PLUMBING AND FIRE PROTECTION DATA. SYSTEMS ARE COMBINED ON ONE PLAN IN ORDER TO PROVIDE COORDINATION. PLUMBING INCLUDES SANITARY, STORM AND DOMESTIC WATER. FIRE PROTECTION INCLUDES UNDERGROUND FIRE LINES SERVING EACH BUILDING LOCATED ON PODIUM.
3.ALL DOMESTIC WATER AND FIRE SERVICES SHALL EXTEND FROM WATER SERVICES ROOM AS INDICATED ON ENLARGED PLAN DRAWING P -502. THESE SERVICES ARE TO BE RUN BELOW GARAGE FLOOR AT A MINIMUM COVER OF 48" TO TOP OF PIPES. DEPTHS/ELEVATIONS CAN CHANGE AS NECESSARY TO AVOID CONFLICTS WITH SANITARY OR
STORM PIPING. IN ALL CASES WHERE ELEVATION MUST BE CHANGED, DOMESTIC WATER AND FIRE MAINS SHOULD DROP BELOW OBSTRUCTIONS.
4.DOMESTIC WATER AND FIRE PROTECTION EXTENDING FROM WATER SERVICES ROOM IN DRAWING P-502 SHALL EXTEND TO BUILDING STAIRWELLS AND RISE IN STAIR WELLS TO THE ELEVATION OF THE PODIUM DECK UNDER THE GARAGE PROJECT.
5.ALL SANITARY AND STORM PIPING SHALL EXTEND FROM BELOW GARAGE FLOOR AT COLUMNS PER DETAIL 1 ON DRAWING P-501 TO 6" ABOVE PODIUM DECK. PIPING SHALL BE CAPPED FOR FUTURE BUILDING CONSTRUCTION OR SHALL EXTEND TO PODIUM DECK DRAINS PER PLUMBING P-300 SERIES DRAWINGS. ELEVATIONS OF DRAINS IN OR
ABOVE PODIUM DECK SHALL BE AS INDICATED ON CIVIL DRAWING C200.
6.FIRE PROTECTION DRY PIPE SYSTEM SHALL ALSO EXTEND FROM WATER SERVICES ROOM AT GARAGE CEILING. THIS DRAWING INDICATES SHADED ARES WHERE DRY PIPE SYSTEMS WITHIN GARAGE SHALL ALSO EXTEND TO BUILDINGS 1 & 4 PARKING AREAS AS CONSTRUCTION PROGRESSES.
0 Issued for Garage Permit 02/22/18
1 Issued for General Revisions 05/08/18