HomeMy WebLinkAboutNON SPRINKLED BUILDING CODE - Dermatology CarmelCornerstone Design 8481 E. 550 N. Onerbein, Indiana 47970 Architwmre- Historic Preservation - Planning November 8, 2018 City of Carmel Carmel Fire Department Carmel, Indiana 46032 RE: Dermatology, Inc., 725 Lakefront Court, Carmel, IN.46032 This letter is to clarify for the above mentioned project qty: (2) items as follows: Draft stops shall be installed in the attic to comply with Section 718.4 of the Indiana Building Code. Exact locations of the draft stops to be determined when the truss manufacture submits the final truss layout for review and approval. Enclosed areas between draft stops are not to exceed 3000 sf. Sprinklers are not required for this B occupancy since the allowable building area per section 506.2 Frontage Increase of the BC is 15,750 sf (this building is 11,85t so and this is not an Ambulatory Care Facility with 4 or more patients that would not be capable of self-preservation per section 903.2.2.1 of the BC. There will not be any instances in this building where a patient would be under full anesthetic not being able to leave under their own power. Please let me know if you need any additional clarification. Sincerely, aJ", pkn LES o". Dann Keiser, RA ,��pP. nsrEq'EN;^',rF eoi ee no. OVA 'Rf arm<a Ar MSTATE of i '•wti,dM)rknq,•}�,;' �n r RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Camel DATE: 03/27/19 crsmnedesip@hughcs.net