HomeMy WebLinkAboutNON SPRINKLED BUILDING CODE - Dermatology CarmelCornerstone Design
8481 E. 550 N.
Onerbein, Indiana 47970
Architwmre- Historic Preservation - Planning
November 8, 2018
City of Carmel
Carmel Fire Department
Carmel, Indiana 46032
RE: Dermatology, Inc., 725 Lakefront Court, Carmel, IN.46032
This letter is to clarify for the above mentioned project qty: (2) items as follows:
Draft stops shall be installed in the attic to comply with Section 718.4 of the
Indiana Building Code. Exact locations of the draft stops to be determined when
the truss manufacture submits the final truss layout for review and approval.
Enclosed areas between draft stops are not to exceed 3000 sf.
Sprinklers are not required for this B occupancy since the allowable building area
per section 506.2 Frontage Increase of the BC is 15,750 sf (this building is
11,85t so and this is not an Ambulatory Care Facility with 4 or more patients
that would not be capable of self-preservation per section 903.2.2.1 of the BC.
There will not be any instances in this building where a patient would be under
full anesthetic not being able to leave under their own power.
Please let me know if you need any additional clarification.
Sincerely,
aJ", pkn LES o".
Dann Keiser, RA ,��pP. nsrEq'EN;^',rF