Mechanical Compliance Certificate
Project Title:
2012 IECC
Project Type:Alteration
Location:Carmel, Indiana
Climate Zone:5a
Construction Site:
10325 N. MICHIGAN RD.
CARMEL, IN 46032
Owner/Agent:
Chuy's
1623 Toomey Road
Austin, TX 75067
514.473.2783
Designer/Contractor:
Dialectic, Inc
310 W 20th St
Suite 200
Kansas City, MO 64108
816.997.9601
Project Information
Energy Code:
Chuy's
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each - Central Furnace, Gas, Capacity = 240 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency: 80.00 % Et
Cooling: 1 each - Single Package DX Unit, Capacity = 118 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 12.00 EER, Required Efficiency: 11.00 EER + 11.2 IEER
Fan System: RTU-1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Single-Zone VAV, 3200 CFM, 2.0 motor nameplate hp
1 RTU-1 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 240 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency: 80.00 % Et
Cooling: 1 each - Single Package DX Unit, Capacity = 100 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 12.20 EER, Required Efficiency: 11.00 EER + 11.2 IEER
Fan System: RTU-2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Single-Zone VAV, 3000 CFM, 2.0 motor nameplate hp
1 RTU-2 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 150 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency: 80.00 % Et (or 78% AFUE)
Cooling: 1 each - Single Package DX Unit, Capacity = 68 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 12.00 EER, Required Efficiency: 11.00 EER + 11.2 IEER
Fan System: RTU-3 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 3 Supply, Single-Zone VAV, 1920 CFM, 2.0 motor nameplate hp
1 RTU-3 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 180 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency: 80.00 % Et (or 78% AFUE)
Cooling: 1 each - Single Package DX Unit, Capacity = 117 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 12.00 EER, Required Efficiency: 11.00 EER + 11.2 IEER
Fan System: RTU-4&5 -- Compliance (Motor nameplate HP method) : Passes
Fans:
2 RTU-4&5 (Single Zone):
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
111 ofPage
Quantity System Type & Description
FAN 4 Supply, Single-Zone VAV, 3200 CFM, 2.0 motor nameplate hp
Heating: 1 each - Central Furnace, Gas, Capacity = 288 kBtu/h
Proposed Efficiency = 92.00% Et, Required Efficiency: 80.00 % Et
Fan System: MAU-1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 6 Supply, Constant Volume, 3698 CFM, 3.0 motor nameplate hp
1 MAU-1 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 252 kBtu/h
Proposed Efficiency = 92.00% Et, Required Efficiency: 80.00 % Et
Fan System: MAU-2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 7 Supply, Constant Volume, 3240 CFM, 2.0 motor nameplate hp
1 MAU-2 (Single Zone):
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.1.0.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
112 ofPage
Elizabeth Elliott, PE 10/22/2018
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.0.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2012 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
113 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C403.2.4.
5
[FO9]3
Freeze protection and snow/ice
melting system sensors for future
connection to controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
114 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.5.
1
[ME59]1
Demand control ventilation provided
for spaces >500 sq.ft. and >25
people/1000 sq.ft. occupant density
and served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.7
[ME60]2
HVAC ducts and plenums insulated.
Where ducts or plenums are installed
in or under a slab, verification may
need to occur during Foundation
Inspection.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.8.
1
[ME7]3
Piping Insulation exposed to weather
is protected from damage (due to sun,
moisture, wind, etc.).
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.8
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7
[ME10]2
Ducts and plenums sealed based on
static pressure and location.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.7.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
115 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.3.1,
C403.3.1.
1
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3.1,
C403.3.1.
1
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3.1,
C403.3.1.
1
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3.1,
C403.3.1.
1
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.2
[ME66]2
VAV fan motors >=7.5 hp to be driven
by variable speed drive, have a vane-
axial fan with variable pitch blades, or
have controls to limit fan motor
demand.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.2
[ME66]2
VAV fan motors >=7.5 hp to be driven
by variable speed drive, have a vane-
axial fan with variable pitch blades, or
have controls to limit fan motor
demand.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.2
[ME66]2
VAV fan motors >=7.5 hp to be driven
by variable speed drive, have a vane-
axial fan with variable pitch blades, or
have controls to limit fan motor
demand.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.2
[ME66]2
VAV fan motors >=7.5 hp to be driven
by variable speed drive, have a vane-
axial fan with variable pitch blades, or
have controls to limit fan motor
demand.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.2
[ME66]2
VAV fan motors >=7.5 hp to be driven
by variable speed drive, have a vane-
axial fan with variable pitch blades, or
have controls to limit fan motor
demand.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.2
[ME66]2
VAV fan motors >=7.5 hp to be driven
by variable speed drive, have a vane-
axial fan with variable pitch blades, or
have controls to limit fan motor
demand.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
116 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.6
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.6
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.11
[ME71]2
Unenclosed spaces that are heated
use only radiant heat.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
117 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
3
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
3
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
3.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
118 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
3.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
3.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
3.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
3.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
3.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
119 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
3
[FI32]1
Economizers have been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
1110 ofPage
Project Title:
Data filename:
Chuy's
Y:\_Projects\Active\2018\01201828.31\01201828.31.Calcs and Support\182831 COMCHECK.cck
10/22/18Report date:
1111 ofPage