HomeMy WebLinkAboutP401 - PLUMBING DETAILS (2018 12 22 City Comments Rev1)WAyaTER HEATING EQUIPMENT DETAILS &NOTES
TEMPERATURE &
CHECKVALVE
PRESSURE BELIEF
♦tyI
PRESSURE RELIEF VALVED WATER FLOW SWITCH
TEMPERA RE ® CIRCULATINGPUMP
i
HOT WATER TO
CONTROL
FIXTURES AS SHOWN
ra DRAIN FULL PORT BALL VALVE
ON PLANS
PROVIDE FULL FORT
BALL SHUT#F
VALVES
PROVIDE PIPE
UNIONS, DIELECTRIC
IF REQUIRED FOR
DISSIMILAR METALS
PROVIDE A HARD COPPER 1-112"
RELIEF VALVE. DISCHARGE LINE
FULL SIZE OF VALVE OUTLET TO
TERMINATE e" ABOVE DRAIN PAN
WITH A VISIBLE Al RGAP PER
LOCAL PLUMBING CODE
SECTION 504.6 (5)-
TERMINATE CONDENSATE LINE
ABOVE FLOOR ORAIN
EXPANSION TANK
PROVIDE 4" DEEP OVERFLOW
PANS PER LANDLORD'S =
REQUIREMENTS & ROUTE
HEATER RELIEF It PAN TO
NEAREST DRAIN. PROVIDE
WITH APPROVED INDIRECT /
WASTE.
Manufacturer Info Manufacturer Info
K15 Cook & Hold
KI08 Combi-Oven
Manufacturer: Alto-Shaam
Manufacturer: Alto-Shaam
Model: 750-TH-II
Model: CTX4-10EC
Amps: 14.5
Amps: 23.6
Volts: 208
Vots: 208V
Phase:1
Phase:1
NEMA: 6J0R (cord not
NEMA: L6-30P
included with appliance)
Electrical AFF: 48"
EledncalAFF: 24"
Remarks: Direct Connect
Remarks: Secure to bldg
wl flexible connector
3 Water Connections
Cold Water Size: 3/4"
Water AFF: 48"
K708
CornbiOven
15
Cook & Hold
yluaa�avatla.:
STRAP-0 AWASTATSET
5 DEGREES LOWERTHAN
HEATERTEMPERATURE
V-4"min. clearance
Provide standoffs
D: 3/4" untreated mid water inlet
I C:3Wtreated cold water met -
1 C K108 COMBI OVEN - RETROFIT
J NOT TO SCALE
RECIRCULATING PUMP
REMRTOPLUMNNG
SPECIFICATIONS
3" WATER HEATER COMMON FRESH AIR
INTAKE & EXHAUST PVC, OR CPVC. REFER
—I
TO TABLES AND MANUF.
RECOMMENDATO43. TERMINATE
SIDE WALL WITH T FLUSH MOUNT VENT KIT.
MAINTAIN A 1T MIN. FROM EDGE OF AIR
INLET AND ADJACENT VENT (EXHAUST)
—
OUTLET.
BACKROW PREVENTER
COORDINATE TYPE AND SIZE
WITH WATER SOFTENER
PROVIDE A 21WF
MANUFACTURER.
TEMP, AND
PRESSURE RELIEF
VALVE WITH TEST
LEVER SIZED WITH
AGAICGA TEMP.
STEAM RATING 10%
OVER HEATER
INPUT.
NOTES:
VENT 1. PREFERRED PIPING METHOD
ADAPTER 2, THE TEMPERATURE AND PRESSURE
RELIEF VALVE SETTING SHALL NOT
EXCEED PRESSURE RATING OF ANY
COMPONENT IN THE SYSTEM.
3. SERVICE VALVES ARE SHOWN FOR
SERVICING UNIT. HOWEVER LOCAL
GAS CODES SHALL GOVERN THEIR
SUPPLY USAGE.
r 4. SET WATER HEATER TEMP TO 14TF
WAMRSOFTENER
PIPE TO FLOORDRAIN.
12x12 access
panel shutoff
valves waterEr
2" to 3" adapter (funnel)
2" drain line to floor sink
E: 1-112" hot water drain
"Provide standoff from FRP wall"
Route drain line between equip legs and wall"
**Drain should route to floor sink under prep table""
F: Sprayer Connection
PAVEMENT
OR GRADE
24" DIAMETER CAST IRON MANHOLE RINGS
WITHHEAVYDUTYCOVERS. MNIMUMTWO
REQUIRED.
]
CONCRETE
'
ADJUSTMENT RINGS
TOSUIT DEPTH OF
INTERCEPTOR.,:
].••
OPEN
LIQUID LEVEL
II_�I'IT�gI
4-INLET
1T'
LJ
REINFORCED
PRECAST
1T'MIN.
BAFFLES -
CONCRETE
_
4" SAMPLING FORT
24" l 24' X 24" X 8"
MIN.II��I CONCRETE PAD
2" VENT. SEE PLAN FOR
CONTINUATION
STRAIGHT �S
MITRAIGHT TEE
4" X4"SANITARYTEE
- SEAL WATERTIGHT
4"
OUTLET
RELEASED FOR CONSTRUCTION DETAIL SHOWS GENERAL SCHEMATIC REQUIREMENTS, CONTRACTOR SHALL SUBMIT PROPOSED
1 GREASE INTERCEPTOR INSTALLATION PLANS AND SPECIFICATIONS TO LOCAL AUIHORITES FOR
VAL BEFORE ACQUISITION OF INTERCEPTOR.
Subject tacompliance d Local Coall regulatims 2500 ALLON GREASE INTERCEPTOR
of Sete and Local Codes
City
LLooff Camlel �E
�1�TTW \IT
VENTING NOTES
1, THE VENT AND INTAKE AIR PIPING MOST TERMINATE OUTDOORS.
2, THE MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR THE VENT(EXHAUST)AND
INTAKE AIR BEING SHALL BE O INCHES VENT PIPING PASSING THROUGH A COMBUSTIBLE
WALL OR CEILING MUST BE A CONTINUOUS RUN (NO JOINTS).
3, THE WATER HEATER MUST BE PROTECTED FROM FREEZING DOWNDRAFTS DURING SHUTDOWN
PERIODS.
4, THE VENT )EXHAUST) PIPE MUST NOT BE COMBINED OR CONNECTED TO ANY OTHER
APPLIANCE'S VENT SYSTEM OR CHIMNEY.
5, THE INTAKE AIR PIPE MUST NOT BE COMBINED OR CONNECTED TO MY OTHER APPLIANCE'S
INTAKE AIR BEING.
5. LOCATE THE WATER HEATER WHERE THE VENT EXHAUST) AND INTAKE AIR PIPING WILL REMAIN
WITHIN THE MAXIMUM EQUIVALENT LENGTHS ALLOWED.
7, DO NOT INSTALL THE VENT OR INTAKE AIR PIPING IN A MANNER THAT WILL ALLOW WATER TO
BE TRAPPED IN PIPING.
e. VENT PIPES MOST BE PITCHED A MINIMUNLANCH PER FOOT BACK TO THE WATER
HEATER (TO ALLOW DRAINAGE OF CONDENSATE).
9, DO NOT ANCHOR THE VENT OR INTAKE MR PIPE DIRECTLY TO FRAMED WALLS FLOORS OR
CEILINGS UNLESS RUBBER ISOLATION PIPE HANGERS ARE USED TO PREVENT VIBRATION NOSE
FROM BEING TRANSMITTED.
10, USE ONLY APPROVED VENT/INTAKE AIR PIPE SIZES AND MATERIALS.
11. USE ONLY FACTORY SUPPLIED VENT AND INTAKE AIR OR CONCENTRIC TERMINATIONS.
12, DIRECT VENTING I WO DEAD AIR SPACES SUCH AS ALLEYS. ATRIUMS. AND INSIDE CORNERS
CAN CAUSE RECIRCULATION OF FLUE GASES. RECIRCULATION OF FLUE GASES WILL CAUSE
SOOTING PREMATURE FAILURE OF THE HEAT EXCHANGER AND IGNG OF THE COMBUSTION AIR
INTAKE DURING SEVERE COLD WEATHER TO PREVENT THE RECIRCULATION OF FLUE GASES,
MAINTAIN AS MUCH DISTANCE AS POSSIBLE BETWEEN THE AIR INTAKE AIR AND VENT
TERMINATIONS.
NUMBER OF WEl
INSTALLED SFEET
'METERS)
ONE 1
TWO 2
2
JMETERS)
THREE (3)
FOUR(4)
.1
FIVE 5SIX
6
NOTE: WHEN 3 INCH INTAKE AIR OR VENT FEE IS INSTALLED, FACTORY SUPPLIED 3"
TERMINATIONS MUSTBE USED. CONTACTYOURLOCPL DISTRIBUTORORCALL THE
PARTS DEPARTMENT TO ORDER 31NCH TERMINATIONE).
THREE COMPARTMENT
SINK
ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDIMMS OR
MEET LOCAL CODE REQUIREMENTS. UTILIZE HUBLESS CAST IRON PIPE, FITTINGS
AND CONNECTORS FOR SINK CONNECTIONS.
13 UTILITY SINK
NOT TO SCALE
TWO COMPARTMENT SINK
ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD
COMMONS OR MEET LOCAL CODE REQUIREMENTS. UTILIZE
HUBLESS CAST IRON PIPE, FITTINGS AND CONNECTORS FOR SINK
CONNECTIONS
7 7 PREP SINK
L NOT TO SCALE
FlLTERED WATER SUPPLY
PRWIDESHUTOFFVALVEONROUGHJN\ DOWN IN PARTITION
\\ WHERE SHOWN ON PLAN
ADAPTER AND SIX FOOT
LONG 112'(MIN, 3B"I.O.)
REINFORCED FOOD
GRADE PLASTIC TUBING
TO CURER WATER INLET
A
USE HOSE CLAMPS AS
REWIRED.
INDIRECT DRAIN OPEN
TOATMOSPHEREAT
UPPER END
NNEOTTOCURERPNUICEBIN
GRAIN OUTLETS AS
FLOORREWIRED
ROVIDE AIR GAP OF 2
�T�F PIPE DIAMETER
FLOORSINK� LJ MINIMUM
PROVIDE FLUOR SINK AT FRONT EDGE OR SIDE EDGE OF ICE MACHINE,
WHERE ACCESSIBLE FOR CLEANING -NOT UNDER ANY EQUIPMENT
PROVIDE COLD WATER ROUGHPN AT TOP OF ICE MACHINE. ARRANGEMENT SHOWN IS
SCHEMATC. ADJUST AS REQUIRED TO SUIT CONDITIONS. VERIFY CONNECTIONS WITH
MANUFACTURER.
11 ICE MACHINE CONNECTIONS
NOT TO SCALE
tr—G
SCREWED FITTNGSIPIPE
IN CEILING PLENUM
OONOTINST&I
VALVES IN CEILING
EXHAUST HOW
TYPICAL PIPE
ANCHORED TO W&L WALL
MANUAL GAS VALVE
GAS SHUTOFF VALVE,
PROVIDEO BY HOGo
VENDOR, INSTALLED BY PC
FLEXIBLE APPLIANCE
INTERCONNECTED TO
CONNECTOR FURNISHED
I
HOOD FIRE SUPPRESSION
BY FSEC AND INSTALLED
SYSTEM BY FPO.
BY PLUMBING
CONTRACTOR.
GAS FEE HEADER ALONG TOP
OF WALL APPROXIMATELY 48"
ABOVE FINISHED FLOOR, WITH
PROVIDE WICK
DISCONNECT FITTING
PRIOR TO CONNECTION
SCREWED FITTINGS, SIZE AS
KITCHEN GAS APPLIANCE
SHOWN ON PLANS. PROVIDE
QUANTITY AND SIZE OF
CONNECTIONS AS REQUIRED
FOR EQUIPMENT BEING SERVED.
MANUAL GAS VALVE (TYP.)
6" DIRT LEG TO 6" ABOVE
KITCHEN GAS
FLOOR MP)
APPLIANCE
RESTRATNINGCHATN
ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT ACTUAL CONDITIONS. MAKEFINAL
CONNECTION TO EQUIPMENT AS RECOMMENDED BY MANUFACTURER. PROVIDE WELDED
FlTTINGSOCINTS IN MY CONOEALEO UNSLEEVED LOCATION
A IA COOKING APPLIANCE GAS
V NOTTOSCALE
PROVIDE CLEANOUTS IN ����OOISCHARGE INTO CENTER HOLE OF
HITTING IFS OF IS LARGE THADVVVN
—a / GRAIEOFWAST TO REMOVE ACLE
TURNSISIFSIOF PIM USE
THAN T' / GAP SUFFICIENTWASTO REMOVE GRATE AND
STRAINER. MINIMUM GAP =TWO PIPE
DIAMETERS
SLOPE PIPE AS //�\ AUEOONNTO
MUCHASPOSSIBLE\`\III///JJ EQUIPMENTT AASS REQUIRED
TowAEO
DISCHARGE
MAKE PIPE MINIMUM ME SIZE LARGER ' VERI FY WITH LOCAL CODES
THAN EQUIPMENT CONNECTION, MINIMUM IF/WHEN TRAP ANDIOR VENT
314". USE TYPE"M'HARD COPPERUPTO ARE REWIRED FOR THE
VANDTYPEDWFORLARGI LENGTH OF GRAIN PIPE
INSTALLED
ROUTE PIPE INCONSPICUOUSLY AND UNOBTRUSIVELY. HANG PIPE AS
REWIRED. DO NOT INSULATE INDIRECT DRAIN PIPE WHEN INSTALLED EXPOSED
IN FOOD SERVICE FACILITY REFER TO LOCAL CODES FOR FURTHER
INFORMATION.
09 INDIRECT DRAIN
NOTTO SCALE
DO NOT PROVIDETRAP ON UNITS WHICH HAVE AN
INTERNAL TRAP, BUT 00 DISCHARGE AWAY FROM IT PIPE REDUCER FROM
THREADED PIPE TO BRANCH PIPE SIZE TO
PVC ADAPTER ON UNIT CONNECTION SIZE,
CONDENSATE WASTE ATUNITCONNECTION
CONNECTON(S)
GROUND JOINT PIPE UNION
TEE OPEN TO
ATMOSPHERE GASSHUr#F
COND DRAIN TO ROOFTOP COCK
CH PIK.
DISCHARGETO UNIT SEEBRAPLAN FOR SIZE
SPLASHBLOCK SEE PLAN
BRANCH OFF TOP
OF GAS PIPE MAIN
EQUIPMENT DOUBLE
GROUND CURB BLOCK
1TR12' SPLASH BLOCK %PE
SUPPORT
PVC PIPE TRAP / SEE DETAIL
6" LONG DIRT LEG BULL SIZE OF BRANCH PIPE J
NOTE:
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED,
PVC CONDENSATE DRAINAGE PIPING ON ROOF TO BE UV RATED.
n4 MECHANICAL UNIT CONNECTIONS
V V NOT TO SCALE
SWEET AR NV543-0,
PROVIDE ONE PIECE SPUN
CARBON FILTER VENT UNIT
ALUMINUM BASE WITH,
AS MANUFACTURED BY
GRADULATED STEPPED PVC
SWEETSEPTICSYSTEMS
BOOT AND ADJUSTABLE
(aW)6223]fi6
STAINLESS STEEL CLAMPS.
SET BASE IN BED OF MASTC
PROVIDESLEEVEIF
REWIRED BY TYPE OF
J
APPLICATIONn
21
VENT PIPE BOOT
\ Z
INNSTALLATION WITH
ROOFING MATERIAL
III III
II III
ROOF DECK
ANCHOR PIPE TO ROOF DECK
OR JOISTS WITH LLBCLT
AROUND PIPE AND ANGLE IRON
WELDED OR SCREWED TO
PROVIDE PIPE INCREASER
DECK OR JOIST
WHERE REWt RED TO MAKE
HUBLESS PIPE CONNECTORS
MINIMUM 4"VENT THRU ROOF
ON PVC PIPE
REFER TO PLANS FOR VIE PPE SIZES AND LOCATIONS.
LOCATE WR MINIMUM TEN
FEET HORIZONTAL OR THREE FEET VERTICAL ABOVE ANY BUILDING OPENING OR
FRESH AIR INTAKE, AND ONE FOOT FROM ANY VERTICAL
SURFACE. PROVIDE V
FIBERGLASS INSULATION WITH ALL -SERVICE JACKET ON VENT PIPE INSIDE BUILDING
WITHIN SIX FEET OF VENT THRU ROOF LOCATION. VERIFY FLASHING AND
COUNTERRASHING WITH ROOFING CONTRACTOR.
07 VENT THRU ROOF (VTR)
W/ SWEET VENT
I NOTTOSCALE
PROVIDE ROUND SECURED NICKEL BRONZE ADJUSTABLE TOP WITH "CO"
CAST IN COVER. PROVIDE OLEANOUT TOP WITH VARIATO43 SUITABLE
FOR FLOOR COVERING (CARPET MARKER, RECESSED FOR TLE,
SCORIATED FOR UNFINISHED FLOORS). PROVIDE BRONZE RUG IN CAST
IRON BODY,
MEMBRMECLAM' FLOORSLPBONGRADE
A���. A: . ' .. ...
j�AME SIM AS SEWER UPSIM AS SEWER UP
HUB AND SPIGOT CAST I
IRON PIPE BELOW ROOT L ENO OR TURN OFRUN
SANITARY BINATION WYE AND
OR STOW EIGHTH BEND IN RUN.
SEWER LINE ENTER TOP OF PIPE
DIRECTION OF FLOW
LOCATE AT BUILDING EAT, AT ENDS OF RUNS, AT TURNS OF PIPE GREATER
THAN 45 DEGREES, AT W INTERVALS ON STRAIGHT RUNS, AND WHERE SHOWN
ON PLANS. PROVIDE BACKFILL PER ARCHITECTURAL SPECIFICATIONS. LOCATE
CLEANOUFS WHERETHERE IS W CLEAR AROUND. CONSULT LOCAL CODES
FOR OTHER BOO
REQUIREMENTS.
OG FLOOR CLEANOUT
J NOT TO SCALE
STEPPED FLEXIBLE PVC BOOT CLAMPED TO FLASHING
BASE AND PIPE WITH STAINLESS STEEL SCREW
rr
m
�
T
r Nr
U
H NDo
j
=TIN
0
u
op0
Or
N UOT
of
aas
UU
3
� W
>
LL
U
U �
p6
0 3
O
s
O
p
o
2U
I —I ROUND-,X)IM PIPE UNION �./I / �'
LBOWS TO
COMPENSATE
LLY
YL
PROVIDE SPUN RUOFlNG OVER FOR PIPE /
ALUMINUMBASE METAL EXPANSION
IN BED OF MASTIC FLASHING BY
COORDINATE RUOFlNG BE SUPPORT
WITH ROOFER COMRACTOR
�� 1 REFER TOOETAIL
�� �� ROOF INSULATION
II II ROOF DECK
SLEEVE ROOF `ANCHOR PIPE TO RCOF DECK OR JOI STS
IF REQUIRED
REFERTOPLANS FOR PIPE SIZE(S) AND LOCATONDO USEWELDEDORSCREWED
FITTINGS AS SPECIFIED FOR PIPE SIZE. LOCATE PENETRATION MINIMUM 18" FROM
ADJACENT WALLS.
O A ROOF PENETRATION
'•F NOT TO SCALE
HOT OR COLD WATER SUPPLY
IN
PER P01
IF HM
STANDARDS AND HORIZONTAL BRANCH IS LESS THAN
PDI SIZE MANUFACTURER W LONG, PROVIDE ME WHA AT END OF
S INSTRUCTIONS I INF
IF BRANCH IS GREATERTHAN 2U LONG,
PROVIDE ANOTHER WHA IN MIDDLE,
EACH SIZED FOR HALF THE FIXTURE
UNITS
SINGLEFIXNRE MULTIPLE FIXTURES
Ml
SIZE
PIPE
SIZE
FIXTURE
UNIT LOAD
A
la.
1-11
B
SAID
1252
C
P'
S
0
1-114"
61-113
E
1 112"
114-154
F
2"
156330
FIXTURE UNIT TABULATON
FIXTURE
COLD
HOT
VALVE WATER CLOSET
5
-
URINAL
5
-
COUNTERSINK
1S
1.5
LAVATORY
IS
IS
MOP BASIN
2.25
2.25
WATER COOLER
.25
-
PROVIDE WATER HAM,4ER ARRESTERS BY SI WX CHIEF, PRECISION PLUMBING PRODUCTS, WATTS
OR APPROVED EQUAL WITH PISTON AND O RING CONSTRUCTION, HAVING P01 MWH-20T ABBE M1010
AND ANSI i1A112.28.1M CERTIFICATION. INSTALL IN HORIZONTAL OR VERTICAL POSITION, BUT NEVER
UPSIDE DOWN. INSTALL INLINE WITH WATER FLOW DIRECTION IF POSSIBLE. SIZE UNITS MR
TABLES ABOVE.
0 WATER HAMMER ARRESTORS
NOT TO _�ALE
TAPE JOIMS1
COVER VALVE BODIES WITH
INSULATION, BUT NOT
FlBERGLASS
INSULATION
ZMOVIDE
UNIONS
MITER THE INSULATION AT TEES AND
A ME FOOT LENGTH
ELBOWS SO THAT THERE ME NO GAPS
NON-COWRESSIBLEINSULAT
AT JOINTS. PROVIDE ONEPIECE PRE-
AT HANGERS FOR ALL PIPE Z' 1
MOULDED PVC FITTING COVERS
LARGER
PROVIDE INSULATON ON DOMESTIC
HOTICOLD WATER PIPE S, STORM WATER
REFER TO OTHER DETAILS
PIPES, AND CONDENSATE DRAIN PIPING IN
FOR TREATMENT OF
WALLS AND CHASES
INSULATION AT PENETRATION
OF WALLS AND FIREW&I-S
Ar
PROVIDE FIBERGLASS INSULATION WITH ALL -SERVICE JACKET WITH VAPOR BARRIER ON ALL
CCLDRbT WATER PIPING AND CONDENSATE BRAIN PIPE. REFER TO SPECIFICATIONS FOR
FURTHER INFORMATION REGARDING INSULATION. INSTALL ALL ITEMS PER SPECIFICATIONS
AND MANUFACTURERS INSTRUCTIONS. MAINTAIN VAPOR BARRIER ON COLD PIPING BY MEANS
OF SEALANT AND TAPE. FLAME SPREAD AND SMOKE -DEVELOPED INDEXES SHALL NOT
EXCEED 25150. SEAL EXPOSED ENDS OF FIBERGLASS INSULATION WITH ADHESIVE MASTIC.
A7 PIPE INSULATION DETAIL
VKEE NOT TO SCALE
—ALL-THREAD ROD.
LENGTH AS
REQUIRED FOR PIPE
SLOPE
PROVIDE COPPER OR
NON-METALLIC
COATING WHERE
HANGERS
CONTACTBARE
COPPERPIPE
OF
xN
NO
Carmel
(Zionsville), IN
10325 N. Michigan RD.
Carmel, IN 46032
Owner:
Choy's OPCO
1623 Toomy Road
Austin, TX.78704
Ph: (512) 473-2783
Contact: Michael Hatcher
Architect:
Parkway C&A, LP
1000 Civic Circle
Lewisville, TX. 75067
Ph:(469)322-3714
Project Contact: Bill Pounds, AIR
MEP Enaineer:
Dialecitc, Inc
210 W. 20th St. Suite 200
Kansas City, MO 64108
Ph: (816) 997-9627
Project Contact: Joe Hillebrenner, P.E.
Structural Enginesr
Armstrong -Douglas
6060 N. Central Expressway
Suite 800
Dallas, TX 76206
Ph' (214) 237-7022
Contact: Scett Armstrong, P.E.
Landscape Architect
Belle Firma, Inc.
4245 North Central Espy.
Suite 501
Dallas, Texas 75205
Ph: (214) 865-7192
Contact: Kon Haug, ASIA, CLARB
PIPE SIZE AS REQUIRED
SEEDRAWINGS
DO NOT HANG PIPE LARGER THAN -PROVIDE GALVANIZED STEEL SADDLE FOR ALL
3'FR0MB0TTOMCFJOSTS INSULATED%PELARGERTHAN3I4'.VERFY
INSULATION THICKNESS WHEN SI➢NG HANGERS
CENTER DECK PLATE BELOW
%PESTANO
DECK PLATE, RIGID
PROVIDE UPPER ATTACHMENT AS REQUIRED FOR CASES NOT SHOWN HERE. 00 NOT INSTALL
18
NLESS
DRAINAGE PORTS ON TWO
HANGER INSIDE INSULATION H OTHERWISETRAFENETRAR VAPOR BARREN. OONOT HANG ONE PIPE
MAY FOR MULTIPLE
FROM ANOTHER EXCEPT I N OHASES.IZE
IGA TE01L
SIDES OFFEE STAND BASE
p-PARALLEL
COEHANGERS
-114' '=
8-0E5.1HANGER SPACINGZOR PIPE SIZET'=14
MIR, NUUSTRES
TU
WAND ONE2NEAR-11 JOINS.=TEEL..
ALL JOINTS. STEEL: 4"=14L 3"=12';
MOP-I2-SS, SIZE IT'
2-112"=11'; 2"=10`, 1-112"=9', T'=]', 3I4'-Ya'; 12"=5l LOCATE HANGERS AS CLOSE AS POSSIBLE TO
SQUARE TURNS AND TEES OF PIPE. PROVIDE SUPPLEMENTARY STEEL STRUTS BETWEEN JOISTS IF
REQUIRED, LOCATE FEE AGAINST SWAYING DUE TO CHANGES IN WATER VELOCITY PROVIDE
PILLOW BLOCK PIPE
STAND OF
FOLYCPRBONATE RE SIN
MATERIAL, MIND
INDUSTRIES Mi.&3R PLAN
ALUMINUM PPE STRAPS,
/// FASTEN TO PIPE STAND
WITH STAIN STEEL
SCREWS, MIRO
INDUSTRIES, Mt&3-R
SEISMIC BRACING IFIAS REWIRED BY LOCAL AUTHORITIES. CHAINS OR PERFORATED STRAP IRON
OR STEEL IS NOT ACCEPTABLE. REFER TO CODES AND SPECIFICATIONS FOR FURTHER
INFORMATION.
PIPE HANGERS
t
CRY Comment
12-22-18
PILLOW BLOCK /
PIPE STAND
PIPE STRAPS
PIPE SHALL REST
FIRMLY ON PIPE STAND
WITHOUT GAPS
01
NOT TO SCALE
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS OTHER SHEETS INCLUDING
SPECIFICATIONS APPLY. THAT SHOWN HERON IS SCHEMATIC IN NATURE AND NOT TO
USED AS A SHOP DRAWINGS; THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO
A
PermB Sat
2018.10.23
No.
Description
P
Date
:Pp. „P, BY: MDB
PIPE STANDS ARE CONFORM TO SITE CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY
DECK PLATE
STACKAELE FOR
PROPER ELEVATION OF
LOCATIONS AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS
SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR
=lti'.KES BP. JMB
ROOF
VARIOUS SIZE PIPE TO
MAINTAIN LEVEIJ30FE
BEING. MIRO
INO JSTRIES, Mtsl3-R
REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE ENGINEER
ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS. NO DESIGN
RESPONSIBILITY ISASSUMED FOR ANY PORTION OF THE WORKTHATTHE PROFESSIONAL
04-97221
yYTfl 'ATKVIAY 20180
ELEVATION
SPACER
PLUMBING DETAILS
PIPE STAND GOOD FOR 112" TO MIT STEEL PIPE SIZES ONLY.
SUPPORTO
ND FREE DE: 1PLAT S, LARGER-ESTAND MACE
RATES ROOFIGG, SET PIPE STAND WITH
PLATES ON ROOFING SET PIPE STPNOFREE ON DECK PLATES, STACK PIPE STAND WITH
SPACERS, WHERE REQUIRED TO ELEVATE BEING. INSTALL GAS PIPE TO ALLOW FOR
T0%H HI11111"
A Ngg9,,
SY•"'•. / ��i
Dialectic
}
401
EXPANSION AND CONTRATION. PRIMER COAT AND PAINT EXTERIOR GAS PIPE LIGHT GREEN v ] Na 080888E
COLOR, Z.ai STATEOF :qcZ
OC ROOF BLOCKING PIPE SUPPORT Dialectic, Inc. T816-997-9601 %9� •(NPl,N•P•:'t1SO .`
V NOTTOSCUE 310 W 20th Street, So de 200 F816997-9602
Kansas City, MO 64108 DialecticEng.mm '' MrYr111111rR� ,
DATE: V,5/ZD/-1U