HomeMy WebLinkAboutI36601057.J19901239 (1)16023 Swingley Ridge Rd Chesterfield, MO 63017 314-434-1200 MiTek USA, Inc. Re: The truss drawing(s) referenced below have been prepared by MiTek USA, Inc. under my direct supervision based on the parameters provided by ProBuild (CarterLee Bldg Components). April 2,2019 Garcia, Juan Pages or sheets covered by this seal: I36601057 thru I36601107 My license renewal date for the state of Indiana is July 31, 2020. J19901239 Truss Engineer's responsibility is solely for design of individual trusses based upon design parameters shown on referenced truss drawings. Parameters have not been verified as appropriate for any use. Any location identification specified is for file reference only and has not been used in preparing design. Suitability of truss designs for any particular building is the responsibility of the building designer, not the Truss Engineer, per ANSI/TPI-1, Chapter 2. IMPORTANT NOTE: 97 SUNRISE 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss CG01 Truss Type Diagonal Hip Girder Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601057 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:25 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-aOjRFXONocmg4cMPJz0?RASKmqfmI2mf_n63EKzUpxS Scale = 1:26.6 1 2 3 4 7 6 8 9 10 11 52x4 3x4 2x4 4x6 6-8-11 6-7-15 -1-11-8 1-11-8 6-8-11 6-8-11 1-5-84-5-95.37 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 NO IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.51 0.53 0.04 DEFL. Vert(LL) Vert(TL) Horz(TL) in 0.14 -0.29 -0.00 (loc) 6-7 6-7 5 l/defl >573 >270 n/a L/d 240 180 n/a PLATES MT20 Weight: 29 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 7=390/0-6-5, 5=236/Mechanical Max Horz 7=145(LC 4) Max Uplift 7=-147(LC 5), 5=-121(LC 4) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-7=-315/130 NOTES- (10-11) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone; cantilever left and right exposed ; end vertical left and right exposed; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 5) Refer to girder(s) for truss to truss connections. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 147 lb uplift at joint 7 and 121 lb uplift at joint 5. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 2 lb down and 23 lb up at 2-1-8, and 32 lb down and 69 lb up at 2-3-7, and 44 lb down and 54 lb up at 4-6-5 on top chord, and 2 lb down and 2 lb up at 2-1-8, and 4 lb down and 54 lb up at 2-3-7, and 3 lb down and 38 lb up at 4-6-5 on bottom chord. The design/selection of such connection device(s) is the responsibility of others. 9) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). 10) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 11) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). LOAD CASE(S) Standard 1) Dead + Roof Live (balanced): Lumber Increase=1.15, Plate Increase=1.15 Uniform Loads (plf) Vert: 1-2=-60, 2-3=-60, 3-4=-60, 5-7=-20 Concentrated Loads (lb) Vert: 8=23(B) 10=2(F=-2, B=4) 11=1(B) April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE01 Truss Type GABLE Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601058 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:27 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-XnrBfDPdKD0OJwWoRO3TXbYl7eS6mxByS5bAICzUpxQ Scale = 1:54.4 Sheet Front Full Sheathing 1 Ply 7/16OSB8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 2x4 3x4 4x6 2x4 3x4 3x4 2x42x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 22-7-0 22-7-0 -0-10-8 0-10-8 11-3-8 11-3-8 22-7-0 11-3-8 23-5-8 0-10-8 1-2-08-8-51-2-08.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-R 0.20 0.09 0.11 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.00 -0.00 0.00 (loc) 19 19 20 l/defl n/r n/r n/a L/d 180 120 n/a PLATES MT20 Weight: 356 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud *Except* 10-28: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing. WEBS 1 Row at midpt 10-28 REACTIONS. All bearings 22-7-0. (lb) - Max Horz 37=-207(LC 4) Max Uplift All uplift 100 lb or less at joint(s) 20, 30, 31, 32, 33, 34, 35, 27, 26, 25, 24, 23, 22, 21 except 37=-104(LC 4), 36=-113(LC 5) Max Grav All reactions 250 lb or less at joint(s) 37, 20, 28, 30, 31, 32, 33, 34, 35, 36, 27, 26, 25, 24, 23, 22, 21 FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (12-13) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) Gable requires continuous bottom chord bearing. 5) Truss to be fully sheathed from one face or securely braced against lateral movement (i.e. diagonal web). 6) Gable studs spaced at 1-4-0 oc. 7) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 8) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 9) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 20, 30, 31, 32, 33, 34, 35, 27, 26, 25, 24, 23, 22, 21 except (jt=lb) 37=104, 36=113. 11) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 12) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 13) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE02 Truss Type GABLE Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601059 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:30 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-xLXJIFSWd8OyANEM6WcA8DA4KrIgzBHO82qqvXzUpxN Scale = 1:73.4 Sheet Back Full Sheathing 1 Ply 7/16OSB8 1 2 3 4 5 6 7 8 9 18 17 16 15 14 13 12 11 1059 60 61 62 63 3x6 4x6 3x4 3x6 3x6 4x6 3x6 4x6 3x8 3x6 4x6 3x8 5x12 6-9-0 6-9-0 9-10-8 3-1-8 19-5-8 9-7-0 29-4-0 9-10-8 -0-10-8 0-10-8 7-5-12 7-5-12 14-8-0 7-2-4 21-10-4 7-2-4 29-4-0 7-5-12 30-2-8 0-10-8 1-2-010-11-51-2-08.00 12 Plate Offsets (X,Y)-- [5:0-1-1,0-1-8], [12:0-6-0,0-3-0] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.97 0.87 0.54 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.33 -0.58 0.06 (loc) 11-13 11-13 10 l/defl >808 >467 n/a L/d 240 180 n/a PLATES MT20 Weight: 600 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 *Except* 10-12: 2x4 SPF 2100F 1.8E WEBS 2x4 SPF No.2 *Except* 6-11,4-13,2-18,8-10: 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud *Except* 5-19: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 3-9-9 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 4-18, 6-10 REACTIONS. All bearings 7-0-8 except (jt=length) 10=0-3-8. (lb) - Max Horz 18=259(LC 5) Max Uplift All uplift 100 lb or less at joint(s) 10, 14 except 18=-127(LC 6) Max Grav All reactions 250 lb or less at joint(s) 14, 14, 15, 16, 17 except 18=1328(LC 1), 10=1430(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-4=-427/233, 4-5=-1581/267, 5-6=-1659/250, 6-8=-521/190, 2-18=-444/209, 8-10=-496/185 BOT CHORD 17-18=-87/1314, 16-17=-87/1314, 15-16=-87/1314, 14-15=-87/1314, 13-14=-87/1314, 11-13=0/955, 10-11=0/1379 WEBS 5-11=-91/794, 6-11=-306/229, 5-13=-126/648, 4-13=-304/232, 4-18=-1349/0, 6-10=-1333/0 NOTES- (11-12) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) All plates are 2x4 MT20 unless otherwise indicated. 5) Gable studs spaced at 1-4-0 oc. 6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 7) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 8) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 10, 14 except (jt=lb) 18=127. 10) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. Continued on page 2 April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE02 Truss Type GABLE Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601059 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:30 2019 Page 2 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-xLXJIFSWd8OyANEM6WcA8DA4KrIgzBHO82qqvXzUpxN 11) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 12) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE03 Truss Type GABLE Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601060 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:31 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-PY4iVbS8OSWpoXpZgE7PhRiSVFp_ijJYMiZNR_zUpxM Scale = 1:42.1 Sheet Front Full Sheathing 1 Ply 7/16OSB8 1 2 3 4 5 6 7 8 9 10 11 20 19 18 17 16 15 14 13 12 2x4 3x4 4x6 2x4 3x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 10-1-0 10-1-0 -0-10-8 0-10-8 5-0-8 5-0-8 10-1-0 5-0-8 10-11-8 0-10-8 1-5-86-6-01-5-812.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-R 0.18 0.10 0.23 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.00 -0.01 0.00 (loc) 11 11 12 l/defl n/r n/r n/a L/d 180 120 n/a PLATES MT20 Weight: 138 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing. REACTIONS. All bearings 10-1-0. (lb) - Max Horz 20=-160(LC 4) Max Uplift All uplift 100 lb or less at joint(s) 17, 18, 15, 14 except 20=-163(LC 4), 12=-151(LC 5), 19=-155(LC 5), 13=-147(LC 4) Max Grav All reactions 250 lb or less at joint(s) 20, 12, 16, 17, 18, 19, 15, 14, 13 FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 6-16=-254/0 NOTES- (12-13) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) Gable requires continuous bottom chord bearing. 5) Truss to be fully sheathed from one face or securely braced against lateral movement (i.e. diagonal web). 6) Gable studs spaced at 1-4-0 oc. 7) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 8) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 9) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 17, 18, 15, 14 except (jt=lb) 20=163, 12=151, 19=155, 13=147. 11) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 12) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 13) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE04 Truss Type GABLE Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601061 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:32 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-tke4jwTm9legPhOlDxeeEeFUxf2hRC9hbMJxzQzUpxL Scale = 1:65.1 Sheet Front Full Sheathing 1 Ply 7/16OSB8 1 2 3 4 5 10 9 7 6 8 4x6 3x4 3x6 4x8 4x10 3x4 4x10 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 7-4-8 7-4-8 8-7-0 1-2-8 17-2-0 8-7-0 -0-10-8 0-10-8 8-7-0 8-7-0 17-2-0 8-7-0 18-0-8 0-10-8 1-5-810-0-81-5-812.00 12 Plate Offsets (X,Y)-- [2:0-3-12,0-1-8], [4:0-3-12,0-1-8] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.71 0.51 0.07 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.12 -0.30 0.01 (loc) 6-7 6-7 6 l/defl >999 >393 n/a L/d 240 180 n/a PLATES MT20 Weight: 327 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 *Except* 2-10,4-6: 2x6 SPF No.2 OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 9-5-1 oc bracing. WEBS 1 Row at midpt 2-7, 4-7 REACTIONS. (lb/size) 10=686/7-4-8, 6=700/0-3-8, 8=83/0-3-8 Max Horz 10=-243(LC 4) Max Uplift 10=-66(LC 6), 6=-61(LC 7) Max Grav 10=686(LC 1), 6=700(LC 1), 8=135(LC 2) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-597/135, 3-4=-597/135, 2-10=-623/139, 4-6=-620/140 BOT CHORD 8-10=-368/365, 7-8=-368/365, 6-7=-188/350 WEBS 2-7=-153/371, 4-7=-165/364 NOTES- (10-11) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) Gable studs spaced at 1-4-0 oc. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 10, 6. 9) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 10) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 11) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE05 Truss Type GABLE COMMON Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601062 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:36 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-mVubYIWGD_86uIiWSnjaOUQ7rGP0Nt_HW_H86BzUpxH Scale = 1:70.7 Sheet Front Full Sheathing 1 Ply 7/16OSB8 1 2 3 4 5 6 7 8 9 10 21 20 19 18 17 16 15 14 13 12 11 58 59 60 61 5x12 6x10 6x10 5x12 3x8 3x4 3x4 3x4 3x6 5x8 3x6 5x6 10-6-8 10-6-8 12-2-0 1-7-8 18-9-8 6-7-8 29-4-0 10-6-8 -0-10-8 0-10-8 5-5-0 5-5-0 10-6-8 5-1-8 18-9-8 8-3-0 23-11-0 5-1-8 29-4-0 5-5-0 30-2-8 0-10-8 1-5-812-0-01-5-812-0-012.00 12 Plate Offsets (X,Y)-- [3:0-0-0,0-1-12], [3:0-6-0,0-3-0], [4:0-1-12,0-1-8], [5:0-6-0,0-0-12], [6:0-6-0,0-0-12], [8:0-0-0,0-1-12], [13:0-3-0,0-3-0], [53:0-1-3,0-0-4] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.91 0.62 0.65 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.28 -0.66 0.02 (loc) 11-12 11-12 11 l/defl >716 >309 n/a L/d 240 180 n/a PLATES MT20 Weight: 776 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 *Except* 11-13: 2x4 SPF 2100F 1.8E WEBS 2x4 SPF No.2 *Except* 2-21,4-21,9-11,7-11: 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud *Except* 23-24,33-34,35-36,43-45: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals, and 2-0-0 oc purlins (6-0-0 max.): 5-6. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 4-15, 5-15, 6-15, 7-12, 4-21, 7-11 REACTIONS. All bearings 12-5-8 except (jt=length) 11=0-3-8. (lb) - Max Horz 21=288(LC 5) Max Uplift All uplift 100 lb or less at joint(s) 21, 11 except 15=-110(LC 6), 20=-106(LC 6) Max Grav All reactions 250 lb or less at joint(s) 14, 14, 16, 17, 18, 19 except 15=1144(LC 1), 21=408(LC 10), 11=964(LC 11), 20=260(LC 11) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 6-7=-676/202, 7-9=-436/179, 2-21=-281/219, 9-11=-448/184 BOT CHORD 14-15=-23/410, 12-14=-23/410, 11-12=0/510 WEBS 5-15=-416/114, 6-15=-720/47, 6-12=-42/574, 7-11=-447/33 NOTES- (15-16) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) Provide adequate drainage to prevent water ponding. 5) All plates are 2x4 MT20 unless otherwise indicated. 6) Gable studs spaced at 1-4-0 oc. 7) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 8) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 9) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 21, 11 except (jt=lb) 15=110, 20=106. 11) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 12) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord. 13) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 206 lb down and 129 lb up at 3-0-12 on bottom chord. The design/selection of such connection device(s) is the responsibility of others. Continued on page 2 April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE05 Truss Type GABLE COMMON Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601062 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:36 2019 Page 2 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-mVubYIWGD_86uIiWSnjaOUQ7rGP0Nt_HW_H86BzUpxH NOTES- (15-16) 14) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). 15) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 16) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). LOAD CASE(S) Standard 1) Dead + Roof Live (balanced) + Uninhab. Attic Storage: Lumber Increase=1.15, Plate Increase=1.15 Uniform Loads (plf) Vert: 1-2=-60, 2-5=-60, 5-6=-60, 6-9=-60, 9-10=-60, 21-58=-20, 58-59=-60, 13-59=-20, 12-13=-60, 12-60=-20, 60-61=-60, 11-61=-20 Concentrated Loads (lb) Vert: 20=-206(F) 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE06 Truss Type GABLE Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601063 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:37 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-EiSzmeXv_IGzWSHj0UEpxiyUegu36RNQle0ifdzUpxG Scale = 1:49.1 Sheet Front Full Sheathing 1 Ply 7/16OSB8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 28 27 26 25 24 23 22 21 20 19 18 17 16 153x4 4x6 2x4 2x43x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 18-4-8 18-4-8 10-7-8 10-7-8 18-4-8 7-9-0 0-5-47-6-42-4-48.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.07 0.05 0.20 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 15 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 260 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. All bearings 18-4-8. (lb) - Max Horz 1=193(LC 5) Max Uplift All uplift 100 lb or less at joint(s) 1, 15, 21, 22, 24, 25, 26, 27, 28, 20, 19, 18, 17, 16 Max Grav All reactions 250 lb or less at joint(s) 1, 15, 21, 22, 24, 25, 26, 27, 28, 20, 19, 18, 17, 16 FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (11-12) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) Gable requires continuous bottom chord bearing. 5) Gable studs spaced at 1-4-0 oc. 6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 7) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 8) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 15, 21, 22, 24, 25, 26, 27, 28, 20, 19, 18, 17, 16. 10) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 11) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 12) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE07 Truss Type GABLE Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601064 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:38 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-iu0Lz_YXlbOq8crvaCl2TvVbz4BQrw9ZzImFB4zUpxF Scale = 1:46.9 Sheet Front Full Sheathing 1 Ply 7/16OSB8 1 2 3 4 5 6 7 8 15 14 13 12 11 10 93x6 3x6 3x42x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 12-4-11 12-4-11 8-3-28.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.35 0.17 0.10 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 9 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 167 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 8-9 REACTIONS. All bearings 12-4-11. (lb) - Max Horz 1=236(LC 5) Max Uplift All uplift 100 lb or less at joint(s) 1, 9, 10, 11, 12, 13, 14, 15 Max Grav All reactions 250 lb or less at joint(s) 1, 9, 10, 11, 12, 13 except 15=334(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (10-11) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 3) Gable requires continuous bottom chord bearing. 4) Gable studs spaced at 1-4-0 oc. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 9, 10, 11, 12, 13, 14, 15. 9) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 10) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 11) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss GE08 Truss Type GABLE Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601065 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:39 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-A4ZjBKZ9VvXhlmQ58vGH071lwTWdaN4jCyWojWzUpxE Scale = 1:60.3 Sheet Front Full Sheathing 1 Ply 7/16OSB8 1 2 3 4 5 6 7 8 9 10 11 20 19 18 17 16 15 14 13 12 4x6 3x6 3x6 3x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 14-9-1 14-9-1 14-9-1 14-9-1 9-10-18.00 12 Plate Offsets (X,Y)-- [5:0-2-2,0-0-0], [6:0-2-12,0-2-4], [6:0-0-0,0-1-12] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.40 0.24 0.12 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 12 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 234 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud *Except* 1-6: 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 OTHERS 2x4 SPF-S Stud *Except* 10-13: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 11-12, 10-13 REACTIONS. All bearings 14-9-1. (lb) - Max Horz 1=284(LC 5) Max Uplift All uplift 100 lb or less at joint(s) 12, 1, 13, 14, 15, 16, 17, 18, 19, 20 Max Grav All reactions 250 lb or less at joint(s) 12, 1, 13, 14, 15, 16, 17, 18, 19 except 20=303(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-255/147 NOTES- (10-11) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 3) Gable requires continuous bottom chord bearing. 4) Gable studs spaced at 1-4-0 oc. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 12, 1, 13, 14, 15, 16, 17, 18, 19, 20. 9) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 10) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 11) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss J03 Truss Type Jack-Open Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601066 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:40 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-eH75OfZnGDfYNw?HhdoWYKazrtuDJr9sRcFMGyzUpxD Scale = 1:15.5 1 2 5 3 4 2x4 2x4 2-11-13 2-11-13 -0-10-8 0-10-8 2-11-13 2-11-13 1-0-42-6-32-1-82-6-36.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-R 0.20 0.09 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.00 -0.01 -0.01 (loc) 4-5 4-5 3 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 9 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 2-11-13 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 5=184/0-3-8, 3=71/Mechanical, 4=29/Mechanical Max Horz 5=77(LC 6) Max Uplift 5=-19(LC 6), 3=-37(LC 6) Max Grav 5=184(LC 1), 3=71(LC 1), 4=52(LC 2) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 5) Refer to girder(s) for truss to truss connections. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 5, 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss J04 Truss Type Jack-Open Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601067 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:40 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-eH75OfZnGDfYNw?HhdoWYKazatuwJr9sRcFMGyzUpxD Scale = 1:15.7 1 2 5 3 43x4 3x4 1-0-11 1-0-11 -0-10-8 0-10-8 1-0-11 1-0-11 1-5-82-6-31-11-112-6-312.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-R 0.22 0.11 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in 0.00 -0.00 -0.01 (loc) 5 5 3 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 6 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 1-0-11 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 5=132/0-3-8, 3=-2/Mechanical, 4=3/Mechanical Max Horz 5=91(LC 6) Max Uplift 3=-38(LC 6), 4=-50(LC 6) Max Grav 5=132(LC 1), 3=11(LC 4), 4=16(LC 2) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 5) Refer to girder(s) for truss to truss connections. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 4. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss J05 Truss Type Jack-Open Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601068 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:41 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-6ThUc?aP1WnO?3aUFKJl5Y774HDV2HP0gG?voOzUpxC Scale = 1:20.8 1 2 5 3 4 3x4 3x6 2-0-11 2-0-11 -0-10-8 0-10-8 2-0-11 2-0-11 1-5-83-6-312.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-R 0.30 0.15 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.00 -0.00 -0.02 (loc) 5 4-5 3 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 8 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 2-0-11 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 5=152/0-3-8, 3=40/Mechanical, 4=17/Mechanical Max Horz 5=121(LC 6) Max Uplift 3=-61(LC 6), 4=-28(LC 6) Max Grav 5=152(LC 1), 3=40(LC 1), 4=35(LC 2) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 5) Refer to girder(s) for truss to truss connections. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 4. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss M01 Truss Type MONO TRUSS Qty 5 Ply 1 97 SUNRISE Job Reference (optional) I36601069 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:41 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-6ThUc?aP1WnO?3aUFKJl5Y73wHA42HP0gG?voOzUpxC Scale = 1:26.0 1 2 3 5 4 3x4 3x6 3x4 3x8 -0-10-8 0-10-8 6-11-8 6-11-8 1-0-44-6-04-2-80-3-84-6-06.00 12 Plate Offsets (X,Y)-- [4:0-3-8,Edge] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-R 0.56 0.37 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.08 -0.21 0.00 (loc) 4-5 4-5 4 l/defl >999 >385 n/a L/d 240 180 n/a PLATES MT20 Weight: 22 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 5=333/0-3-8, 4=262/0-1-8 Max Horz 5=135(LC 5) Max Uplift 5=-37(LC 6), 4=-41(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-5=-282/149 NOTES- (9-10) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 5) Bearing at joint(s) 4 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 6) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 4. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 5, 4. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 10) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss M02 Truss Type MONO TRUSS Qty 3 Ply 1 97 SUNRISE Job Reference (optional) I36601070 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:42 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-afFspLb1oqvFcD9gp2q_elfJDhaNnkf9uwkTKrzUpxB Scale = 1:19.3 1 2 3 5 4 2x4 3x4 2x4 2x4 -0-10-8 0-10-8 4-6-8 4-6-8 1-0-43-3-83-0-00-3-83-3-86.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-R 0.21 0.11 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.01 -0.03 0.00 (loc) 4-5 4-5 4 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 15 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 4-6-8 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 5=239/0-3-8, 4=163/0-1-8 Max Horz 5=97(LC 5) Max Uplift 5=-33(LC 6), 4=-28(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (9-10) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 5) Bearing at joint(s) 4 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 6) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 4. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 5, 4. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 10) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss M03 Truss Type MONO TRUSS Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601071 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:43 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-3spE0hcfZ816ENksNlLDAzCUZ5vwWBvJ7aU0sHzUpxA Scale = 1:19.3 1 2 4 3 2x4 2x4 3x4 2x4 4-6-8 4-6-8 1-0-43-3-83-0-00-3-83-3-86.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-R 0.23 0.15 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.01 -0.03 0.00 (loc) 3-4 3-4 3 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 14 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 4-6-8 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 4=170/0-3-8, 3=170/0-1-8 Max Horz 4=90(LC 5) Max Uplift 3=-29(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (9-10) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 5) Bearing at joint(s) 3 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 6) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 3. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 10) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss M04 Truss Type Monopitch Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601072 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:43 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-3spE0hcfZ816ENksNlLDAzCQt5tbWAzJ7aU0sHzUpxA Scale = 1:68.4 1 2 3 6 5 47 5x6 3x8 3x82x4 3x6 4x6 5-4-12 5-4-12 10-9-8 5-4-12 5-4-12 5-4-12 10-9-8 5-4-12 1-5-812-3-012.00 12 Plate Offsets (X,Y)-- [3:0-5-7,Edge] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.47 0.30 0.12 DEFL. Vert(LL) Vert(TL) Horz(TL) in 0.04 -0.05 -0.00 (loc) 4-5 4-5 4 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 64 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud *Except* 3-4,2-4: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 9-10-15 oc bracing. WEBS 1 Row at midpt 3-4, 2-4 REACTIONS. (lb/size) 4=472/0-3-8, 6=454/0-3-8 Max Horz 6=353(LC 5) Max Uplift 4=-164(LC 5), 6=-4(LC 4) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-431/94, 1-6=-415/60 BOT CHORD 5-6=-344/279 WEBS 2-4=-374/193 NOTES- (7-8) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 4) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 6 except (jt=lb) 4=164. 6) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 7) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 8) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss PB01 Truss Type Piggyback Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601073 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:44 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-X2NcE1cIKR9zsXJ3wTsSjAlfwUGzFePSMEDZPjzUpx9 Scale = 1:23.0 1 2 3 4 6 5 2x4 2x42x42x4 2x4 4-3-0 4-3-0 0-1-8 0-1-8 0-5-34-0-00-1-83-8-90-1-812.00 12 Plate Offsets (X,Y)-- [2:0-2-6,0-1-0] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.20 0.04 0.05 DEFL. Vert(LL) Vert(TL) Horz(TL) in 0.00 0.00 0.00 (loc) 1 1 5 l/defl n/r n/r n/a L/d 180 120 n/a PLATES MT20 Weight: 16 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 4-3-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 5=64/3-8-5, 2=64/3-8-5, 6=175/3-8-5 Max Horz 2=112(LC 5) Max Uplift 5=-32(LC 5), 2=-31(LC 4), 6=-85(LC 6) Max Grav 5=64(LC 1), 2=83(LC 5), 6=175(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (9-10) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 5, 2, 6. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) See Standard Industry Piggyback Truss Connection Detail for Connection to base truss as applicable, or consult qualified building designer. 9) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 10) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss PB02 Truss Type GABLE Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601074 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:45 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-?Ex_RNdw5lHqThuFUANhFOHsduc5_5lbauz7xAzUpx8 Scale = 1:27.9 Sheet Front Full Sheathing 1 Ply 7/16OSB8 2 3 4 5 6 10 9 8 1 7 4x6 2x4 2x4 2x4 2x4 2x4 2x4 2x4 8-3-0 8-3-0 4-1-8 4-1-8 8-3-0 4-1-8 -0-0-44-1-44-1-80-1-00-1-812.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.07 0.04 0.04 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 6 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 61 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. All bearings 8-3-0. (lb) - Max Horz 1=-90(LC 4) Max Uplift All uplift 100 lb or less at joint(s) 1, 7, 2, 6, 10, 8 Max Grav All reactions 250 lb or less at joint(s) 1, 7, 2, 6, 9, 10, 8 FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (12-13) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) Gable requires continuous bottom chord bearing. 5) Gable studs spaced at 1-4-0 oc. 6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 7) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 8) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 7, 2, 6, 10, 8. 10) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 11) See Standard Industry Piggyback Truss Connection Detail for Connection to base truss as applicable, or consult qualified building designer. 12) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 13) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss PB03 Truss Type Piggyback Qty 8 Ply 1 97 SUNRISE Job Reference (optional) I36601075 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:46 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-TQUNfjeYs3Ph5rTR2tvwobq?9IwnjYwlpYigTczUpx7 Scale = 1:27.3 1 2 3 45 6 4x6 2x4 2x42x4 8-3-0 8-3-0 4-1-8 4-1-8 8-3-0 4-1-8 0-5-34-0-00-1-80-5-30-1-812.00 12 Plate Offsets (X,Y)-- [2:0-2-6,0-1-0], [4:0-2-6,0-1-0] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.21 0.14 0.05 DEFL. Vert(LL) Vert(TL) Horz(TL) in 0.01 0.01 0.00 (loc) 5 5 4 l/defl n/r n/r n/a L/d 180 120 n/a PLATES MT20 Weight: 25 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 2=200/7-1-10, 4=200/7-1-10, 6=210/7-1-10 Max Horz 2=-86(LC 4) Max Uplift 2=-35(LC 6), 4=-41(LC 7) Max Grav 2=200(LC 1), 4=200(LC 1), 6=219(LC 2) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (10-11) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Gable requires continuous bottom chord bearing. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 6) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 4. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) See Standard Industry Piggyback Truss Connection Detail for Connection to base truss as applicable, or consult qualified building designer. 10) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 11) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T01 Truss Type Common Qty 7 Ply 1 97 SUNRISE Job Reference (optional) I36601076 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:46 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-TQUNfjeYs3Ph5rTR2tvwobqq0IsBjKulpYigTczUpx7 Scale = 1:69.7 1 2 3 4 5 6 7 8 9 15 14 13 12 11 1016 17 18 3x8 4x6 3x8 3x4 3x64x6 3x6 3x8 3x6 4x6 6x6 3x4 6x6 6-10-12 6-10-12 14-8-0 7-9-4 21-10-4 7-2-4 29-4-0 7-5-12 -0-10-8 0-10-8 7-5-12 7-5-12 14-8-0 7-2-4 21-10-4 7-2-4 29-4-0 7-5-12 30-2-8 0-10-8 1-2-010-11-51-2-08.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.93 0.44 0.94 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.07 -0.19 0.02 (loc) 10-11 10-11 10 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 134 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud *Except* 3-13,5-13,7-13: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 4-10-13 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 7-13 REACTIONS. (lb/size) 15=278/0-3-8, 14=1364/0-3-8, 10=1008/0-3-8 Max Horz 15=259(LC 5) Max Uplift 15=-53(LC 6), 14=-34(LC 6), 10=-82(LC 7) Max Grav 15=309(LC 10), 14=1364(LC 1), 10=1008(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 3-5=-694/176, 5-7=-694/176, 7-8=-1183/122, 2-15=-262/101, 8-10=-943/135 BOT CHORD 14-15=-274/315, 11-13=0/888, 10-11=-52/253 WEBS 3-14=-1092/130, 3-13=0/473, 5-13=-63/288, 7-13=-559/159, 7-11=0/252, 8-11=0/640 NOTES- (8-9) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 15, 14, 10. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T02 Truss Type COMMON Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601077 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:47 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-xd2ls3fAdMXYj_2ecbQ9KpN3AiCPSmnu2CSE?2zUpx6 Scale = 1:69.5 1 2 3 4 5 6 7 13 12 11 10 9 814 15 16 3x8 4x6 3x8 3x4 3x64x6 3x6 3x8 3x6 4x6 5x6 3x4 5x6 6-10-12 6-10-12 14-8-0 7-9-4 21-10-4 7-2-4 29-4-0 7-5-12 7-5-12 7-5-12 14-8-0 7-2-4 21-10-4 7-2-4 29-4-0 7-5-12 1-2-010-11-51-2-08.00 12 Plate Offsets (X,Y)-- [1:Edge,0-1-12], [7:Edge,0-1-12] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.64 0.44 0.97 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.07 -0.19 0.02 (loc) 8-9 8-9 8 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 132 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud *Except* 2-11,4-11,6-11: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 4-8-2 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 6-11 REACTIONS. (lb/size) 13=201/0-3-8, 12=1385/0-3-8, 8=942/0-3-8 Max Horz 13=257(LC 5) Max Uplift 13=-12(LC 7), 12=-48(LC 6), 8=-46(LC 7) Max Grav 13=234(LC 10), 12=1385(LC 1), 8=942(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-4=-691/170, 4-6=-691/169, 6-7=-1178/114, 7-8=-877/97 BOT CHORD 12-13=-256/292, 9-11=0/891 WEBS 2-12=-1120/152, 2-11=0/478, 4-11=-59/289, 6-11=-569/163, 7-9=0/707 NOTES- (8-9) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 13, 12, 8. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T03 Truss Type Common Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601078 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:48 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-Ppc74PgoOgfPK8cq9IxOt0vIS6ctBRl2HsBnYUzUpx5 Scale = 1:41.6 1 2 3 4 7 6 5 5x6 4x6 2x4 2x43x8 5x6 5-0-8 5-0-8 10-1-0 5-0-8 5-0-8 5-0-8 10-1-0 5-0-8 10-11-8 0-10-8 1-5-86-6-01-5-812.00 12 Plate Offsets (X,Y)-- [1:0-2-12,0-1-8], [3:0-2-12,0-1-8] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.42 0.17 0.09 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.01 -0.03 0.00 (loc) 6-7 6-7 5 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 47 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 7=388/0-3-8, 5=456/0-3-8 Max Horz 7=-172(LC 4) Max Uplift 7=-18(LC 7), 5=-35(LC 7) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-347/77, 2-3=-354/83, 1-7=-345/62, 3-5=-412/94 NOTES- (8-9) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 7, 5. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T04 Truss Type Common Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601079 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:49 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-t?AVHkgQ9_nGyIB0j0SdQESPoVt6wuSBVWxK4xzUpx4 Scale = 1:62.1 1 2 3 4 8 7 6 5 5x12 4x6 3x4 3x4 4x8 3x4 4x10 8-7-0 8-7-0 17-2-0 8-7-0 8-7-0 8-7-0 17-2-0 8-7-0 18-0-8 0-10-8 1-5-810-0-81-5-812.00 12 Plate Offsets (X,Y)-- [1:0-5-4,Edge], [3:0-3-12,0-1-8] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.70 0.49 0.12 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.09 -0.24 0.01 (loc) 5-6 5-6 5 l/defl >999 >847 n/a L/d 240 180 n/a PLATES MT20 Weight: 83 lb FT = 20% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 2100F 1.8E *Except* 2-4: 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 *Except* 1-8,3-5: 2x6 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 5-11-3 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 3-6 REACTIONS. (lb/size) 8=666/0-3-8, 5=737/0-3-8 Max Horz 8=-257(LC 4) Max Uplift 8=-26(LC 7), 5=-45(LC 7) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-635/104, 2-3=-649/113, 1-8=-593/88, 3-5=-663/122 BOT CHORD 6-8=-283/333, 5-6=-186/338 WEBS 2-6=0/347, 1-6=-102/275, 3-6=-147/377 NOTES- (8-9) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 8, 5. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T05 Truss Type Piggyback Base Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601080 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:50 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-LCktU4h2wHv7aSmCHjzsyR?YDvBGfEXLkAgucNzUpx3 Scale = 1:67.7 1 2 3 4 5 6 7 8 9 10 15 14 13 12 1116 17 18 19 5x12 4x6 6x8 5x12 3x4 3x8 3x4 3x6 5x6 5x6 3x6 10-6-8 10-6-8 18-9-8 8-3-0 29-4-0 10-6-8 -0-10-8 0-10-8 5-5-0 5-5-0 10-6-8 5-1-8 18-9-8 8-3-0 23-11-0 5-1-8 29-4-0 5-5-0 30-2-8 0-10-8 1-5-812-0-01-5-812-0-012.00 12 Plate Offsets (X,Y)-- [3:0-0-0,0-1-12], [6:0-4-12,0-1-8], [8:0-0-0,0-1-12] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.78 0.62 0.52 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.30 -0.69 0.04 (loc) 14-15 14-15 11 l/defl >999 >507 n/a L/d 240 180 n/a PLATES MT20 Weight: 158 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF 2100F 1.8E WEBS 2x4 SPF No.2 *Except* 4-15,7-11: 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 4-9-14 oc purlins, except end verticals, and 2-0-0 oc purlins (4-2-6 max.): 5-6. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 4-14, 6-14, 7-12, 4-15, 7-11 REACTIONS. (lb/size) 15=1478/0-3-8, 11=1497/0-3-8 Max Horz 15=288(LC 5) Max Uplift 15=-53(LC 6), 11=-53(LC 7) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-4=-502/180, 4-5=-1323/232, 5-6=-866/220, 6-7=-1349/232, 7-9=-500/180, 2-15=-498/185, 9-11=-497/185 BOT CHORD 14-15=-175/924, 12-14=-23/885, 11-12=0/940 WEBS 5-14=-29/450, 6-12=-51/503, 4-15=-1037/39, 7-11=-1066/39 NOTES- (10-11) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Provide adequate drainage to prevent water ponding. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 6) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 15, 11. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord. 10) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 11) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T06 Truss Type Piggyback Base Qty 6 Ply 1 97 SUNRISE Job Reference (optional) I36601081 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:50 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-LCktU4h2wHv7aSmCHjzsyR?Y8vBGfE7LkAgucNzUpx3 Scale = 1:67.7 1 2 3 4 5 6 11 10 9 8 712 13 14 15 3x6 4x6 6x8 3x6 3x43x8 4x6 3x4 4x6 5x6 4x8 10-6-8 10-6-8 18-9-8 8-3-0 29-4-0 10-6-8 5-5-0 5-5-0 10-6-8 5-1-8 18-9-8 8-3-0 23-11-0 5-1-8 29-4-0 5-5-0 1-5-812-0-01-5-812-0-012.00 12 Plate Offsets (X,Y)-- [4:0-4-12,0-1-8] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.79 0.62 0.55 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.30 -0.69 0.04 (loc) 10-11 10-11 7 l/defl >999 >506 n/a L/d 240 180 n/a PLATES MT20 Weight: 155 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF 2100F 1.8E WEBS 2x4 SPF No.2 *Except* 2-11,5-7: 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 4-9-11 oc purlins, except end verticals, and 2-0-0 oc purlins (4-1-14 max.): 3-4. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 2-10, 4-10, 5-8, 2-11, 5-7 REACTIONS. (lb/size) 11=1416/0-3-8, 7=1436/0-3-8 Max Horz 11=285(LC 5) Max Uplift 11=-22(LC 6), 7=-22(LC 7) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-455/121, 2-3=-1329/231, 3-4=-868/218, 4-5=-1355/231, 5-6=-452/121, 1-11=-396/106, 6-7=-394/106 BOT CHORD 10-11=-186/931, 8-10=-34/887, 7-8=-2/948 WEBS 3-10=-29/456, 4-8=-51/509, 2-11=-1091/49, 5-7=-1120/49 NOTES- (10-11) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Provide adequate drainage to prevent water ponding. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 6) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 11, 7. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord. 10) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 11) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T07 Truss Type Common Qty 14 Ply 1 97 SUNRISE Job Reference (optional) I36601082 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:51 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-qOIGiQihhb1_BcLPrRU5VfXikJToOkfUzqQR8pzUpx2 Scale = 1:46.0 1 2 3 4 7 6 56x6 4x6 5x8 3x4 2x4 2x43x8 10-7-8 10-7-8 18-4-8 7-9-0 5-5-9 5-5-9 10-7-8 5-1-15 18-4-8 7-9-0 0-5-47-6-42-4-48.00 12 Plate Offsets (X,Y)-- [1:0-1-11,Edge], [4:0-3-8,Edge] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.86 0.79 0.33 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.26 -0.68 0.02 (loc) 1-7 1-7 5 l/defl >846 >318 n/a L/d 240 180 n/a PLATES MT20 Weight: 69 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 5-2-5 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=723/0-3-8, 5=723/0-3-8 Max Horz 1=193(LC 5) Max Uplift 1=-33(LC 6), 5=-22(LC 7) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-947/121, 2-3=-679/110, 3-4=-715/93, 4-5=-667/81 BOT CHORD 1-7=-82/737 WEBS 2-7=-326/151, 3-7=0/403, 4-7=0/413 NOTES- (8-9) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 5. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T08 Truss Type Piggyback Base Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601083 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:52 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-IasevmjJSv9rpmwbO8?K1s4sZjot7CfdBT9?hGzUpx1 Scale = 1:68.0 1 2 3 4 7 6 58 9 10 3x4 4x6 3x6 4x6 4x8 5x8 5x8 10-6-8 10-6-8 14-9-8 4-3-0 5-5-0 5-5-0 10-6-8 5-1-8 14-9-8 4-3-0 1-5-812-0-012.00 12 Plate Offsets (X,Y)-- [3:0-4-4,0-1-12] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.92 0.87 0.29 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.37 -0.85 0.01 (loc) 6-7 6-7 5 l/defl >465 >206 n/a L/d 240 180 n/a PLATES MT20 Weight: 97 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 *Except* 1-7,2-7: 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals, and 2-0-0 oc purlins (6-0-0 max.): 3-4. BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing. WEBS 1 Row at midpt 4-5, 2-6, 3-6, 2-7 REACTIONS. (lb/size) 5=731/Mechanical, 7=689/0-3-8 Max Horz 7=352(LC 5) Max Uplift 5=-143(LC 5) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-389/112, 2-3=-418/172, 4-5=-716/115, 1-7=-343/99 BOT CHORD 6-7=-187/351 WEBS 4-6=-107/641 NOTES- (10-11) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Provide adequate drainage to prevent water ponding. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Refer to girder(s) for truss to truss connections. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb) 5=143. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord. 10) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 11) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T09 Truss Type Common Qty 2 Ply 1 97 SUNRISE Job Reference (optional) I36601084 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:53 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-mnQ076jxCCHiRvVnyrXZa4d5o7E5sVtnQ7vYDizUpx0 Scale = 1:68.6 1 2 3 4 5 6 7 13 12 11 10 9 814 3x8 4x6 3x8 3x4 3x4 3x6 4x6 3x8 3x6 4x6 5x6 3x4 5x6 7-5-12 7-5-12 14-8-0 7-2-4 21-0-12 6-4-12 29-4-0 8-3-4 7-5-12 7-5-12 14-8-0 7-2-4 21-10-4 7-2-4 29-4-0 7-5-12 1-2-010-11-51-2-08.00 12 Plate Offsets (X,Y)-- [1:Edge,0-1-12], [7:Edge,0-1-12] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.63 0.48 0.93 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.11 -0.27 0.02 (loc) 8-9 8-9 8 l/defl >900 >363 n/a L/d 240 180 n/a PLATES MT20 Weight: 133 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud *Except* 2-10,4-10,6-10: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 4-10-4 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing, Except: 6-0-0 oc bracing: 9-10. WEBS 1 Row at midpt 2-10, 7-9 REACTIONS. (lb/size) 13=890/0-3-8, 9=1221/0-3-8, 8=313/0-3-8 Max Horz 13=-257(LC 4) Max Uplift 13=-40(LC 6), 9=-34(LC 7), 8=-23(LC 7) Max Grav 13=890(LC 1), 9=1221(LC 1), 8=332(LC 11) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-1103/107, 2-4=-599/164, 4-6=-600/164, 1-13=-828/92, 7-8=-256/68 BOT CHORD 12-13=-246/304, 10-12=-78/829 WEBS 2-12=0/265, 2-10=-585/161, 6-10=-1/576, 6-9=-1065/163, 1-12=0/650 NOTES- (8-9) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 13, 9, 8. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss T10 Truss Type Common Qty 3 Ply 1 97 SUNRISE Job Reference (optional) I36601085 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:54 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-EzzOKSkZzWPY234_WZ2o7H9ENWa0b1Gwfne5l8zUpx? Scale = 1:68.6 1 2 3 4 5 6 7 13 12 11 10 9 81415 3x8 4x6 3x8 3x4 3x4 3x8 3x6 5x6 3x6 5x6 5x6 3x4 5x6 7-5-12 7-5-12 14-8-0 7-2-4 21-10-4 7-2-4 29-4-0 7-5-12 7-5-12 7-5-12 14-8-0 7-2-4 21-10-4 7-2-4 29-4-0 7-5-12 1-2-010-11-51-2-08.00 12 Plate Offsets (X,Y)-- [1:0-3-0,0-1-8], [7:0-3-0,0-1-8] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.71 0.50 0.60 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.10 -0.22 0.04 (loc) 10-12 10-12 8 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 132 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud *Except* 4-10,6-10,2-10: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 3-9-3 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 6-10, 2-10 REACTIONS. (lb/size) 13=1262/0-3-8, 8=1262/0-3-8 Max Horz 13=-257(LC 4) Max Uplift 13=-48(LC 6), 8=-48(LC 7) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-1662/138, 2-4=-1215/197, 4-6=-1215/197, 6-7=-1662/138, 1-13=-1197/113, 7-8=-1197/113 BOT CHORD 12-13=-243/308, 10-12=-64/1293, 9-10=-7/1293 WEBS 4-10=-89/820, 6-10=-536/161, 2-10=-536/161, 1-12=0/1097, 7-9=0/1097 NOTES- (8-9) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 13, 8. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss TG01 Truss Type Piggyback Base Girder Qty 1 Ply 2 97 SUNRISE Job Reference (optional) I36601086 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:55 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-i9XmYolBkqYPgDfA4GZ1fViUzwwWKVN4uROfHbzUpx_ Scale = 1:68.0 1 2 3 4 5 6 11 10 9 8 712 13 14 15 16 3x4 4x6 4x8 3x4 4x6 3x8 4x6 3x6 4x6 4x6 4x6 10-6-8 10-6-8 18-9-8 8-3-0 29-4-0 10-6-8 5-5-0 5-5-0 10-6-8 5-1-8 18-9-8 8-3-0 23-11-0 5-1-8 29-4-0 5-5-0 1-5-812-0-01-5-812-0-012.00 12 Plate Offsets (X,Y)-- [3:0-4-4,0-1-12], [4:0-6-4,0-1-12] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 NO IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.40 0.49 0.54 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.09 -0.16 0.02 (loc) 8-10 8-10 7 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 340 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x6 SPF No.2 WEBS 2x4 SPF-S Stud *Except* 3-10,4-10,4-8: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals, and 2-0-0 oc purlins (6-0-0 max.): 3-4. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 4-10 REACTIONS. (lb/size) 11=1674/0-3-8, 7=1684/0-3-8 Max Horz 11=282(LC 4) Max Uplift 11=-105(LC 5), 7=-102(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-411/134, 2-3=-1699/264, 3-4=-1133/243, 4-5=-1711/259, 5-6=-414/133, 1-11=-366/117, 6-7=-368/117 BOT CHORD 10-11=-259/1169, 8-10=-112/1141, 7-8=-48/1177 WEBS 3-10=-106/717, 4-8=-124/745, 2-11=-1509/147, 5-7=-1518/142 NOTES- (13-14) 1) 2-ply truss to be connected together with 10d (0.131"x3") nails as follows: Top chords connected as follows: 2x4 - 1 row at 0-9-0 oc. Bottom chords connected as follows: 2x6 - 2 rows staggered at 0-9-0 oc. Webs connected as follows: 2x4 - 1 row at 0-9-0 oc. 2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to ply connections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated. 3) Unbalanced roof live loads have been considered for this design. 4) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone; cantilever left and right exposed ; end vertical left and right exposed; Lumber DOL=1.60 plate grip DOL=1.60 5) Provide adequate drainage to prevent water ponding. 6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 7) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 8) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb) 11=105, 7=102. 10) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 11) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord. 12) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 510 lb down and 163 lb up at 14-5-0 on bottom chord. The design/selection of such connection device(s) is the responsibility of others. 13) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 14) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). LOAD CASE(S) Standard Continued on page 2 April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss TG01 Truss Type Piggyback Base Girder Qty 1 Ply 2 97 SUNRISE Job Reference (optional) I36601086 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:55 2019 Page 2 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-i9XmYolBkqYPgDfA4GZ1fViUzwwWKVN4uROfHbzUpx_ LOAD CASE(S) Standard 1) Dead + Roof Live (balanced) + Uninhab. Attic Storage: Lumber Increase=1.15, Plate Increase=1.15 Uniform Loads (plf) Vert: 1-3=-60, 3-4=-60, 4-6=-60, 11-12=-20, 12-13=-60, 9-13=-20, 8-9=-60, 8-15=-20, 15-16=-60, 7-16=-20 Concentrated Loads (lb) Vert: 14=-510(B) 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss TG02 Truss Type Flat Girder Qty 1 Ply 2 97 SUNRISE Job Reference (optional) I36601087 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:55 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-i9XmYolBkqYPgDfA4GZ1fViYqwxEKdg4uROfHbzUpx_ Scale = 1:23.0 1 2 4 35 2x4 3x4 2x4 4x6 4-3-0 4-3-0 4-3-0 4-3-0 4-0-0LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 NO IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.15 0.44 0.01 DEFL. Vert(LL) Vert(TL) Horz(TL) in -0.02 -0.03 0.00 (loc) 3-4 3-4 3 l/defl >999 >999 n/a L/d 240 180 n/a PLATES MT20 Weight: 47 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x6 SPF No.2 WEBS 2x4 SPF-S Stud BRACING- TOP CHORD 2-0-0 oc purlins: 1-2, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 4=1177/Mechanical, 3=570/Mechanical Max Horz 4=-105(LC 3) Max Uplift 4=-277(LC 3), 3=-151(LC 4) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (13-14) 1) 2-ply truss to be connected together with 10d (0.131"x3") nails as follows: Top chords connected as follows: 2x4 - 1 row at 0-9-0 oc. Bottom chords connected as follows: 2x6 - 2 rows staggered at 0-9-0 oc. Webs connected as follows: 2x4 - 1 row at 0-9-0 oc. 2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to ply connections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated. 3) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone; cantilever left and right exposed ; end vertical left and right exposed; Lumber DOL=1.60 plate grip DOL=1.60 4) Provide adequate drainage to prevent water ponding. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 8) Refer to girder(s) for truss to truss connections. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb) 4=277, 3=151. 10) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 11) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord. 12) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 719 lb down and 151 lb up at 0-1-12, and 712 lb down and 155 lb up at 2-5-4 on bottom chord. The design/selection of such connection device(s) is the responsibility of others. 13) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 14) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). LOAD CASE(S) Standard 1) Dead + Roof Live (balanced): Lumber Increase=1.15, Plate Increase=1.15 Continued on page 2 April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss TG02 Truss Type Flat Girder Qty 1 Ply 2 97 SUNRISE Job Reference (optional) I36601087 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:56 2019 Page 2 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-AM59l8mpV7gGINEMd_4GCiFjZKHT34wD657Cp1zUpwz LOAD CASE(S) Standard Uniform Loads (plf) Vert: 1-2=-60, 3-4=-20 Concentrated Loads (lb) Vert: 4=-719(B) 5=-712(B) 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V01 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601088 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:56 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-AM59l8mpV7gGINEMd_4GCiFfnKJu32kD657Cp1zUpwz Scale = 1:38.9 1 2 3 5 43x8 3x4 2x4 2x4 2x4 10-4-11 10-4-11 0-0-46-11-28.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.39 0.28 0.15 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 4 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 35 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=188/10-4-5, 4=157/10-4-5, 5=590/10-4-5 Max Horz 1=196(LC 5) Max Uplift 4=-29(LC 5), 5=-130(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 2-5=-352/172 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except (jt=lb) 5=130. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V02 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601089 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:46:57 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-eYfXyUnRGRo7vXoZBhbVkwnrkkg0oW2MLltlLTzUpwy Scale = 1:32.4 1 2 3 5 4 2x4 2x4 2x4 2x4 2x4 8-4-11 8-4-11 0-0-45-7-28.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.38 0.16 0.09 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 4 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 28 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=118/8-4-5, 4=115/8-4-5, 5=388/8-4-5 Max Horz 1=156(LC 5) Max Uplift 1=-1(LC 4), 4=-24(LC 5), 5=-100(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 2-5=-291/167 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 4, 5. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V03 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601090 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:00 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-37LfbVpKZMAim_X7sq9CMYPJ9xZ3?t6p1j5QyozUpwv Scale = 1:24.7 1 2 3 2x4 2x4 2x4 6-4-11 6-4-11 0-0-44-3-28.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.56 0.72 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 18 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-4-11 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=231/6-4-5, 3=231/6-4-5 Max Horz 1=116(LC 5) Max Uplift 3=-39(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V04 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601091 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:00 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-37LfbVpKZMAim_X7sq9CMYPKUxgU?t6p1j5QyozUpwv Scale = 1:17.5 1 2 3 2x4 2x4 2x4 4-4-11 4-4-11 0-0-42-11-28.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.48 0.31 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 11 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 4-4-11 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=151/4-4-5, 3=151/4-4-5 Max Horz 1=76(LC 5) Max Uplift 3=-26(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V05 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601092 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:01 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-XJu2orqyKgIZO86KQXgRvmyb3L3SkKMyGNrzUEzUpwu Scale = 1:10.8 1 2 3 2x4 2x4 2x4 2-4-11 2-4-11 0-0-41-7-28.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.10 0.07 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 6 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 2-4-11 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=71/2-4-5, 3=71/2-4-5 Max Horz 1=35(LC 5) Max Uplift 3=-12(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V06 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601093 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:02 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-?VSQ0Bqa5zQQ0IhW_EBgRzUizlO3Tl86V1aW0hzUpwt Scale = 1:43.9 1 2 3 4 7 6 53x4 3x4 3x42x4 2x4 2x4 2x4 11-9-1 11-9-1 0-0-47-10-18.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.35 0.17 0.16 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 5 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 42 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. All bearings 11-8-11. (lb) - Max Horz 1=224(LC 5) Max Uplift All uplift 100 lb or less at joint(s) 1, 5, 6, 7 Max Grav All reactions 250 lb or less at joint(s) 1, 5 except 6=441(LC 1), 7=303(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 3-6=-261/128 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 5, 6, 7. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V07 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601094 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:02 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-?VSQ0Bqa5zQQ0IhW_EBgRzUhwlOwTm86V1aW0hzUpwt Scale = 1:33.7 1 2 3 5 4 6 2x4 2x4 2x4 2x4 2x4 8-9-1 8-9-1 0-0-45-10-18.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.42 0.18 0.09 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 4 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 29 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=127/8-8-11, 4=172/8-8-11, 5=447/8-8-11 Max Horz 1=163(LC 5) Max Uplift 4=-25(LC 5), 5=-104(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 2-5=-305/174 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except (jt=lb) 5=104. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V08 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601095 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:03 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-Ti0oDXrCsHYHdSGiYyiv_B1lL9d6CEsFjhK4Z7zUpws Scale = 1:22.0 1 2 3 2x4 2x4 2x4 5-9-1 5-9-1 0-0-43-10-18.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.89 0.57 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 15 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=205/5-8-11, 3=205/5-8-11 Max Horz 1=103(LC 5) Max Uplift 3=-35(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V09 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601096 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:04 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-xuaAQtsqdbg8Fcrv5fD8XOa5YY4hxh5OyL3d5ZzUpwr Scale: 1"=1' 1 2 3 2x4 2x4 2x4 2-9-1 2-9-1 0-0-41-10-18.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.15 0.10 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 7 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 2-9-1 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=85/2-8-11, 3=85/2-8-11 Max Horz 1=43(LC 5) Max Uplift 3=-15(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V10 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601097 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:04 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-xuaAQtsqdbg8Fcrv5fD8XOa2jY2oxhSOyL3d5ZzUpwr Scale: 1/2"=1' 1 2 3 4 2x4 4x6 2x42x4 6-11-11 6-11-11 6-11-15 0-0-4 3-6-0 3-6-0 6-11-15 3-6-0 0-0-43-6-00-0-412.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.33 0.22 0.04 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 18 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=150/6-11-7, 3=150/6-11-7, 4=203/6-11-7 Max Horz 1=-73(LC 4) Max Uplift 1=-25(LC 7), 3=-25(LC 7) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (9-10) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Gable requires continuous bottom chord bearing. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 6) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 3. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 10) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V11 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601098 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:05 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-P48YeDtTOuo?tlQ5fNkN3c6HxyNug8LYB?pBd?zUpwq Scale = 1:13.6 1 2 3 2x4 3x4 2x4 4-3-11 4-3-11 4-3-15 0-0-4 2-2-0 2-2-0 4-3-15 2-2-0 0-0-42-2-00-0-412.00 12 Plate Offsets (X,Y)-- [2:0-2-0,Edge] LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.11 0.29 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 9 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 4-3-15 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=145/4-3-7, 3=145/4-3-7 Max Horz 1=-42(LC 4) Max Uplift 1=-4(LC 6), 3=-4(LC 7) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (9-10) 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Gable requires continuous bottom chord bearing. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 6) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 3. 8) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 9) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 10) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V12 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601099 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:05 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-P48YeDtTOuo?tlQ5fNkN3c6DuyOkg8LYB?pBd?zUpwq Scale: 3/4"=1' 1 2 3 2x4 2x4 2x4 3-11-5 3-11-5 0-0-42-7-98.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.37 0.24 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 10 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 3-11-5 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=133/3-10-15, 3=133/3-10-15 Max Horz 1=67(LC 5) Max Uplift 3=-23(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V13 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601100 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:06 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-tHiwrYt59CwrVv_HD4FccpfJtMaDPbbhQfYk9SzUpwp Scale = 1:26.0 1 2 32x4 2x4 2x4 6-11-5 6-11-5 0-0-44-7-98.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.68 0.86 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 20 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-11-5 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 8-9-0 oc bracing. REACTIONS. (lb/size) 1=253/6-10-15, 3=253/6-10-15 Max Horz 1=127(LC 5) Max Uplift 3=-43(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V14 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601101 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:07 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-MTGJ3uujvW2i63ZUnonr81CZmm3v80qreJIHiuzUpwo Scale = 1:38.1 1 2 3 5 43x8 3x4 2x4 2x4 2x4 9-11-5 9-11-5 0-0-46-7-98.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.35 0.26 0.13 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 4 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 33 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=173/9-10-15, 4=167/9-10-15, 5=560/9-10-15 Max Horz 1=187(LC 5) Max Uplift 4=-28(LC 5), 5=-122(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 2-5=-332/164 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except (jt=lb) 5=122. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V15 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601102 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:07 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-MTGJ3uujvW2i63ZUnonr81CYnm5K8?jreJIHiuzUpwo Scale: 1/4"=1' 1 2 3 4 7 6 583x6 3x6 3x42x4 2x4 2x4 2x4 12-11-5 12-11-5 0-0-48-7-98.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.41 0.17 0.20 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 5 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 48 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 1 Row at midpt 4-5 REACTIONS. All bearings 12-10-15. (lb) - Max Horz 1=247(LC 5) Max Uplift All uplift 100 lb or less at joint(s) 1, 5, 6, 7 Max Grav All reactions 250 lb or less at joint(s) 1, 5 except 6=503(LC 1), 7=411(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 2-7=-271/147 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 5, 6, 7. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V16 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601103 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:08 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-qfqhGEvLgpAZkD8gKVI4hEkmUARxtV5_tz1rEKzUpwn Scale = 1:13.5 1 2 3 2x4 2x4 2x4 3-2-3 3-2-3 0-0-42-1-88.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.22 0.14 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 8 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 3-2-3 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=102/3-1-13, 3=102/3-1-13 Max Horz 1=51(LC 5) Max Uplift 3=-17(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V17 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601104 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:09 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-IsN3UawzR7IQMNjsuDpJESHpkZiNcyL86dnOmnzUpwm Scale = 1:20.1 1 2 3 2x4 2x4 2x4 5-2-3 5-2-3 0-0-43-5-88.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.70 0.45 0.00 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 13 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF-S Stud BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 5-2-3 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=182/5-1-13, 3=182/5-1-13 Max Horz 1=92(LC 5) Max Uplift 3=-31(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V18 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601105 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:09 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-IsN3UawzR7IQMNjsuDpJESHvMZmQcxI86dnOmnzUpwm Scale = 1:27.5 1 2 3 5 42x4 2x4 2x42x4 2x4 7-2-3 7-2-3 0-0-44-9-88.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-P 0.28 0.25 0.07 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 4 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 22 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF-S Stud WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=65/7-1-13, 4=124/7-1-13, 5=336/7-1-13 Max Horz 1=132(LC 5) Max Uplift 1=-13(LC 4), 4=-20(LC 5), 5=-86(LC 6) Max Grav 1=68(LC 5), 4=124(LC 1), 5=336(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 2-5=-252/149 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 4, 5. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V19 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601106 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:10 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-m2xRhwxbCRQHzXI2SwKYmfq51z5ULO0HKHWxIDzUpwl Scale = 1:35.3 1 2 3 5 4 6 3x6 3x4 2x4 2x4 2x4 9-2-3 9-2-3 0-0-46-1-88.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.22 0.20 0.10 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 4 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 31 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (lb/size) 1=147/9-1-13, 4=176/9-1-13, 5=475/9-1-13 Max Horz 1=172(LC 5) Max Uplift 4=-26(LC 5), 5=-109(LC 6) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 2-5=-301/150 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except (jt=lb) 5=109. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks 16023 Swingley Ridge Rd Chesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE. Job J19901239 Truss V20 Truss Type Valley Qty 1 Ply 1 97 SUNRISE Job Reference (optional) I36601107 8.220 s Nov 16 2018 MiTek Industries, Inc. Tue Apr 2 07:47:10 2019 Page 1 ProBuild (Carter-Lee), Mooresville, IN - 46158, ID:YMR9tkxfWOb?4FSdPy6y9PzwQBq-m2xRhwxbCRQHzXI2SwKYmfq4Uz6_LNPHKHWxIDzUpwl Scale = 1:41.8 1 2 3 4 7 6 53x4 3x4 3x42x4 2x4 2x4 2x4 11-2-3 11-2-3 0-0-47-5-88.00 12 LOADING (psf) TCLL TCDL BCLL BCDL 20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IRC2003/TPI2002 CSI. TC BC WB Matrix-SH 0.32 0.17 0.14 DEFL. Vert(LL) Vert(TL) Horz(TL) in n/a n/a 0.00 (loc) - - 5 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 40 lb FT = 20% GRIP 169/123 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF-S Stud OTHERS 2x4 SPF-S Stud BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. All bearings 11-1-13. (lb) - Max Horz 1=212(LC 5) Max Uplift All uplift 100 lb or less at joint(s) 1, 5, 6, 7 Max Grav All reactions 250 lb or less at joint(s) 1, 5 except 6=447(LC 1), 7=275(LC 1) FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 3-6=-264/131 NOTES- (8-9) 1) Wind: ASCE 7-05; 90mph; TCDL=6.0psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (low-rise) gable end zone and C-C Exterior(2) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Gable requires continuous bottom chord bearing. 3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 4) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, with BCDL = 10.0psf. 5) All bearings are assumed to be SPF No.2 crushing capacity of 425 psi. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 5, 6, 7. 7) This truss is designed in accordance with the 2003 International Residential Code sections R502.11.1 and R802.10.2 and referenced standard ANSI/TPI 1. 8) Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI-B1 9) It is extremely important to properly install temporary lateral restraint and diagonal bracing, in accordance with BCSI-B2 or using proprietary methods (e.g. Stabilizer, etc.). April 2,2019 04/08/19 Mike Sheeks PRODUCT CODE APPROVALS LATERAL BRACING LOCATION Indicates location where bearings(supports) occur. Icons vary butreaction section indicates jointnumber where bearings occur.Min size shown is for crushing only.Indicated by symbol shown and/orby text in the bracing section of theoutput. Use T or I bracingif indicated.The first dimension is the platewidth measured perpendicularto slots. Second dimension isthe length parallel to slots.Center plate on joint unless x, yoffsets are indicated.Dimensions are in ft-in-sixteenths.Apply plates to both sides of trussand fully embed teeth.1. Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI.2. Truss bracing must be designed by an engineer. For wide truss spacing, individual lateral braces themselves may require bracing, or alternative Tor I bracing should be considered.3. Never exceed the design loading shown and never stack materials on inadequately braced trusses.4. Provide copies of this truss design to the building designer, erection supervisor, property owner and all other interested parties.5. Cut members to bear tightly against each other.6. Place plates on each face of truss at each joint and embed fully. Knots and wane at joint locations are regulated by ANSI/TPI 1.7. Design assumes trusses will be suitably protected from the environment in accord with ANSI/TPI 1.8. Unless otherwise noted, moisture content of lumber shall not exceed 19% at time of fabrication.9. Unless expressly noted, this design is not applicable for use with fire retardant, preservative treated, or green lumber.10. Camber is a non-structural consideration and is the responsibility of truss fabricator. General practice is to camber for dead load deflection.11. Plate type, size, orientation and location dimensions indicated are minimum plating requirements.12. Lumber used shall be of the species and size, and in all respects, equal to or better than that specified.13. Top chords must be sheathed or purlins provided at spacing indicated on design.14. Bottom chords require lateral bracing at 10 ft. spacing, or less, if no ceiling is installed, unless otherwise noted.15. Connections not shown are the responsibility of others.16. Do not cut or alter truss member or plate without prior approval of an engineer.17. Install and load vertically unless indicated otherwise.18. Use of green or treated lumber may pose unacceptable environmental, health or performance risks. Consult with project engineer before use.19. Review all portions of this design (front, back, words and pictures) before use. Reviewing pictures alone is not sufficient.20. Design assumes manufacture in accordance with ANSI/TPI 1 Quality Criteria.Failure to Follow Could Cause PropertyDamage or Personal Injury (Drawings not to scale)© 2012 MiTek® All Rights ReservedMiTek Engineering Reference Sheet: MII-7473 rev. 10/03/2015edge of truss.from outside" 16/1-0ICC-ES Reports:ESR-1311, ESR-1352, ESR1988ER-3907, ESR-2362, ESR-1397, ESR-3282JOINTS ARE GENERALLY NUMBERED/LETTERED CLOCKWISE AROUND THE TRUSS STARTING AT THE JOINT FARTHEST TO THE LEFT.CHORDS AND WEBS ARE IDENTIFIED BY END JOINT NUMBERS/LETTERS.W4 - 6 W3-6W3 -7 W2-7W1-7C1-8 C5-6C6-7C7-8 C4-5 C3-4C2-3C1-2 TOP CHORD TOP CHORD 8 7 6 54321 BOTTOM CHORDSTOP CHORDSBEARING4 x 4PLATE SIZEThis symbol indicates therequired direction of slots inconnector plates."16/1For 4 x 2 orientation, locateplates 0- 1" 4/3PLATE LOCATION AND ORIENTATION Symbols Numbering System General Safety Notes* Plate location details available in MiTek 20/20 software or upon request.Industry Standards:ANSI/TPI1: National Design Specification for Metal Plate Connected Wood Truss Construction.DSB-89: Design Standard for Bracing.BCSI: Building Component Safety Information, Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses.6-4-8 WEBS Trusses are designed for wind loads in the plane of thetruss unless otherwise shown.Lumber design values are in accordance with ANSI/TPI 1section 6.3 These truss designs rely on lumber valuesestablished by others.dimensions shown in ft-in-sixteenths 04/08/19 Mike Sheeks