HomeMy WebLinkAboutMHEAT PUMP, AIR HANDLING ANC HEATING EOJIPMENT SCHEDULE
DE5CRIP7ION
SUPPLY FAN
COOLING
HEATING
FILTERS
CONDENSER SECTION
ELECTRICAL
COOL
UNIT
MARK
MANF.
MODEL
NUMBER
TOTAL
G.F.M.
O.A.
G.F.M.
ESP
MOTOR
H.P.
E.A.T.
MBH
TYPE
OUTPUT
MBH S' ST&
TYPE
THK.
O.A.
TEMP
LOW
O.A.
CONDENSERt15
PRESSOR
VLT
PH
MCA
BKR
TON
WEIGHT
DB
WB
TH
SH
AREA
FAN H
KW
STEPS
BTU 1
TRANE
YHC048F3# A0000
1,600
20%
0.8
3/4
T-A
(1) 1
70
36
11,98
2510,1
1
208
3
28.3
40A
4.0
869
67
80
50
42
96 / 80 2
L
ELI I ES: 1.
ALL UNITS TN HAVE ECONOMIZER PROVIDED
S INSTALLED.
KIM
IL!
2.
ALL UNITS SHALL BE SET IN DRIP PAN W/
DRAIN LINE TO EXTERIOR OF BUILDING.
SPECIFIC CHART VALUES ARE FOR REFERENCE ONLY
3.
ALL UNITS SHALL BE COMPLETE WITH 7-DAY
ELECTRONIC FULLY PROGRAMMABLE THERMOSTAT w/ LOCKABLE COVER
ALL PERFORMANCE SHALL BE VERIFIED AGAINST
EXISTING EQUIPMENT INSPECTIONS
4.
ALL UNITS SHALL BE EQUIPPED WITH SMOKE
DETECTOR IN RETURN AIR DUCT, PRIOR TO ENTERING UNIT,
VOLUME DAMPER
SG THAT IN THE EVENT OF FIRE, DETECTOR
SHALL DEACTIVATE BLOWER MOTOR & SOUND ALARM.
5.
COIL SHALL BE CONNECTED TO SAIL SWITCH
IN RETURN AIR DUCT SO THAT IN THE EVENT BLOWER MOTOR IS
DEACTIVATED, COIL SHALL BE DEACTIVATED
AS WELL, TO PREVENT 'FREEZE-UP'.
EXHAUST PAN SCHE:r%LE:
MARK
MANUFACTURER
MODEL
NUMBER
CFM
DUCT
SIZE
APPROX.
SP
MAX. SONE
LEVEL
MOTOR
VOLTS
PHASE
REMARKS
RPM
HP
OF 1
BROAN
HDBOL
75
40
0,125
80
1500
1/8
115
1
II
NLJ I t_S
1, DUCTS TO BE COMBINED AS SHOWN,
2, TIE ACTIVATION OF FAN INTO LIGHT SWITCH FOR SIMULATENOUS
OPERATION OF FAN AND LIGHTS
H\/AG GENERAL= NOTES:
I. The heating, air conditioning equipment and installation shall
conform to all current National, State and Local Godes.
2. The Mechanical Contractor to clearly label each unit by area
served using I" stencil or engraved plastic.
B. The Mechanical Contractor shall coordinate supply air and
return air ducts with General Contractor so duct encasements
may ber installed at the proper locations as not to affect the
y P lc
structural system of the building.
4. The Mechanical Contractor Is to coordinate gas piping with
Plumbing Contractor to assure correct size and final locations
of the units, and piping servicing the units. Piping in attlo, to be
suspended from trusses a minimum of 12" above Insulation for
proper leak test and future service and Inspection. The M.G.
to verify all aspects of gas service with local utility.
5. The Mechanical Contractor shall be responsible for pouring
concrete pad For units. Chits to be 30" clear of building or
at manufacturer's recommendations, which ever Is greater.
6. The Mechanical Contractor shall coordinate all electrical
requirements of all units with the Electrical Contractor to
assure final correct locations of the unit's disconnects.
All equipment to be provided with Internal fuse protection,
per N.E.G., State and locol Codes.
T. All Exhaust Fans and Ventilators shall have back draft dampers.
Units provided and Installed by the Mechanical Contractor, power
and wiring by the Electrical Contractor.
0. Ductwork shall be Insulated. See Ductwork General Ni
9. The Mechanical Contractor to provide 3/4" PVG condensate drains
with slope to positive drainage outside of building. Provide sheet
metal auxiliary drain pan, at attic units, 2" deep under each cooling
coil. Provide 5/4" condensate drain separated from cooling coil
drain. Slope to positive drain with straps at 45" o.c. to ovoid
sagging of lines. Pitch auxiliary drain pans and cooling coils slightly
In direction of condensate flow.
10. The Mechanical Contractor shall install fire dampers In all ducts
passing through Fire Rated Walls and Ceilings (denoted as "F I' on
these Drawings) and all other locations specified by the State Fire
Marshall or Authority Having Jurlsdictlon.
11. Mechanical equipment shall be base bid as 3m power supply.
Mechanical contractor shall be responsible for verifying available
power supply prior to ordering and Installing equipment.
12. The Mechanical Contractor to provide and install specified
control devices and Law Voltage Wiring. Thermostats to be
Fully Programmable 7 Day. Provide "tamperprooF" Govern with
lock for all thermostats.
B. Fresh / Outslde Air shall conform to A51PRAE 62 'Ventilation
For Acceptable Indoor Air Quality" and all State and Locol Codes.
14. SEER. / E.E.R. - as rated in accordance with 0.5. Government
D.O.E. Test procedure and A.R.I. Standard 210-19.
15. A.F.U.E. - Annual Fuel Utilization Efficiency as established by
U.S. Government Standard D.O.E. Test.
RELEASED FOR CONSTRUCTION `""art prior
Subject to romp Dew ith all regulations
of State and Local Codes
THESE NOTES SHALL APPLY UNLESS OTHERWISE INDICATED BY DRAWINGS
OR SPECIFICATIONS.
I Duct dimensions are shown as clear Inside dimensions. Mere internal
insulation is Dolled for, dimensions shell be increased by the thickness
of InSUlatlon.
2 Portions of ducts visible through diffusers, grilles and registers in
finished areas shall be painted flat black.
5 coordinate exact locations of all selling diffusers, registers and
exhaust grilles, ductwork, etc. with lighting layout, reflected ceiling plan
and owner's layout, so they will remain unobstructed.
4 Coordinate all duct penetrations with Structural Drawings.
5 Supply and return ducts shall be sheet metal with I" thick Internal
acoustical lining.
-OR-
hred all supply and return ductwork with 2" thick, 3/4 Is. density foil
faced insulation.
-OR-
Where applicable, Owens Corning I" fiberglass duct board.
6 All ductwork shall be fabricated and installed in accordance with
5MAGNA Duct Manual and URFA 90-A.
T Flexible ductwork not to exceed 6'. When longer runs occur, use 26 Ga.
round ductwork to obtain requlred lengths.
5 Provide flexible connection where supply and return air ducts connect
to unit,
cl Ductwork openings shall be coordinated with MEd,[ for Inetallotlon by this
Contractor. The M.G. to provide ductwork for exterior, insulated and
weather -protected and Install return air ductwork as required.
10 These al l q5 Indicate duct for size and approximate location. Ducts
may need to be moved slightly to Insure no obstruction In Installation.
DUCT
BRANCH FLEX DUCT
SUSPENDED ACOUSTICAL
CEILING PANEL
DIFFUSER
SUPPORT
STRAP
HANGERS (TYPJ
MAXIMUM ALLOWABLE
LENGTH OF FLEX. DUCT
10'-0"
O.B. DAMPER
INSULATION
NOTE: FLEX DUCT TO BE SAME SIZE AS DIFFUSER NECK.
fi`wi� FLEX DUCT : EETAL NOT TO A
A SQUARE ELBOW IS PERMISSIBLE ONLY
WHERE SHOWN ON DRAWINGS OR BY REQUEST
W
R=W
W
R-W R
R=W W
PERMISSIBLE ELBOWS
O
R
AIR FLOW AIR FLOW
w - -
R=W o
20° MAX. ON DIVER&INIS 300 MAX. ON CONVER&IN&
PERMISSIBLE TRANSITIONS
AIR FLOW AIRFLOW
pS FS
ROUND TO ROUND RECTANbULAR TO ROUND
RECTAN&ULAR TO RECTAN&ULAR
PERMISSIBLE DUCT BRANCH TAKEOFF
7YPIGALE ELE30 $
7RAN5MON r�)E7,ii
NOT TO SCALE:
MECHANICAL SYMBOL LEGEND
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
®
CEILING SUPPLY DIFFUSER ( SAD )
S-12x8
SUPPLY DUCT - WIDTH x DEPTH
0
ROUND CEILING SUPPLY DIFFUSER ( SAR )
R-12x8
RETURN DUCT - WIDTH x DEPTH
®
CEILING SUPPLY GRILLE ( SAG )
®
SQUARE / RECTANGLE SUPPLY DUCT SECTION
®
CEILING / FLOOR SLOT DIFFUSER ( SAS )
ROUND SUPPLY DUCT SECTION
T1
WALL SUPPLY GRILLE ( SAG )
L]
SQUARE / RECTANGLE RETURN DUCT SECTION
CEILING RETURN EGG -CRATE REGISTER ( MAD )
ROUND RETURN DUCT SECTION
r-t
WALL RETURN GRILLE ( RAG)
®
SQUARE -TO -ROUND TRANSITION
RFD
FIRE DAMPER
® FAN
EXHAUST FAN
1 VD
VOLUME DAMPEREXH
®L FAN
EXHAUST FAN WITH LIGHT
No
MOTORIZED DAMPER
_E-6x4 _
EXHAUST DUCT - WIDTH x DEPTH
(C�10
THERMOSTAT WITH UNIT I.D. CONTROLLED
[]
EXHAUST WALL CAP
CityofCamele
at
wv mmDOe"mmlmmOrtlew"P",u�,"r,."nm,=.m
y
Oftkr.id
bmium. tm,l aim a rcrn,a.,,"mwm:.,:
m m� I.iwnmu,mn,mnw n"uemmiwm,i =rat,&r1midO
ne:m"r.,."amri m, md
)11{) �l
®:uy wlwa":&Wren all work mwo-m a mu wrtumm"a,m
.e m:w,:m" mn:.":..xml mmmx,n e,m. aaomam: m,
DATE: 04/22/19
O,nd M.PiOrin..mz
ISSUE:
HANGER STRAPS SPACING
TO BE 8'-0' MAX.
3" OVERLAP c/w (2)
1/V°0 BOLT FASTENERS —
V x 18 ga GALV, SHEET
METAL STRAP c/w (1) 1/4"0
BOLT RATED FASTENER
w/o DISFIGURING SHAPE,
UP TO 18"0 DUCT
ROUND DUCT DETAIL
EXHAUST DUCT UP
THRU ROOF WITH
GAP
6`0
III (u�
I� N
I
R-20X14
2OX14 DROP FROM
NIT
16XI6 DROP FROM UNIT
SAD
400
3' OVERLAP c/w (2)
3/8'0 BOLT FASTENERS,
FOR DUCT OVER 18'0
1 Va°x16 ga GALV
SHEET METAL STRAP
w/o DISFIGURING SHAPE
)
BLANKET INSULATION SEALED \
VAPOR TIGHT c/w MASTIC &
FABRIC TAPE 4' WIDE
YFIG�t� 1U�7 5UFFOR7 �E:Tfi
NOT TO SCALE; MECHANICAL FLAN
SCALE: 3/I6" = I'-0"
_+
rin.e: SHEET:
MECHANICAL FLANS ANC
will
U
N
U
,id�
4
IN
W
a
w
11
o
h
//��
PiH
Q
to
d
On
e
�U
z
C
O
e
U
Q:
se
N
t.
L
51111
ix
O
�
AND
M
S
A
M
Aa�i,�
W
JW
a
rd
E
NATURED/
— CBD —
PH: