HomeMy WebLinkAboutE-001 ELECTRICAL SYMBOLS, ABBREVIATIONS AND SCHEDULESNOTE: NOT ALL SYMBOLS AND ABBREVIATION MAY APPLY TO THIS PROJECT
LIGHTING FIXTURE SCHEDULE
TYPE
DESCRIPTION
MOUNTING
TYPE
VOLT
MANUFACTURER
WATT
NOTES
F1
LENSED LED SHOWER LIGHT
CEILING
277
12
6R LED SURFACE DOWNLIGHT DESIGNED FOR
900- 1100
EQUALTO
MOUNTING DNA RECESSED JUNCTION BOX. DIE-
LUMEN LED
CREE #LR610L-4OK-277V AND RC6-277V
CASTALUMINUM TRIM RING, WAVESTREAM LENS,
4000K
WET LOCATION RATING. COORDINATE REWIRED
JUNCTION BOX DIMENSIONS WITH PRODUCT
INSTALLATION DOCUMENTS.
F2
DIMMABLE LED DOWNLIGHT
CEILING
1201277
15
6" APERATURE LED DOWNLIGHT WITH MEDIUM
1000-1300
ECLALTO
DISTRIBUTION, CLEAR REFLECTOR, WHITE
LUMEN LED
CREE #S-DL6-15L-40K WITH SDL6T-Ml SS-C-
FLANGE, >80CRI, SHIELDING MEDIA, AND DIMMIMG
4000K
WF
DRVIER
F3
SMALL APERATURE LED RECESSED CAN LIGHT
CEILING
120/277
12
4" APERATURE LED DOWNLIGHT WITH NARROW
900-1100
EQUALTO
DISTRIBUTION, CLEAR REFLECTOR, WHITE
LUMEN LED
CREE#SDL411 L-40K WITH SDL4T-NLSSLC-
FLANGE, >80CRI, SHIELDING MEDIA, AND 1%
4000K
WE
DIMMIMG DRVIER
F4
PENDANT MOUNT DIRECT/INDIRECT
PENDANT
1201277
6W
FT
2'Wx3'H CONTINUOUS PENDANT MOUNTED
375 UP-375 ON
EQUALTO
DIRECT/INDI RECT LED FIXTURE IN LENGTHS
LUMENFT LED
LUX#EOS2.0-P-DI SERIES
SHOWN ON THE PLANS. FIXTURE SHALL HAVE
4000K
WHITE FINISH, 1%DIMMING DRIVER BATWING
DISTRIBUTION.
F4A
PENDANT MOUNT DIRECT/INDIRECT
PENDANT
120/277
LOW
FT
20Wx0'H CONTINUOUS PENDANT MOUNTED
375 LUP-750 ON
EQUAL TO
DIRECT/INDIRECT LED FIXTURE IN LENGTHS
UMENIFT LED
LUX#EOS2.0-P-DI SERIES
SHOWN ON THE PLANS. FIXTURE SHALL HAVE
4000K
WHITE FINISH, 1%DIMMING DRIVER BATWING
DISTRIBUTION.
F5
LED WALL WASH POCKET
WALL
1201277
6W
FT
3"WxTH CONTINUOUS LED WALL GRAZE FIXTURE
500 LUMEWFT
EQUAL TO
IN LENGTHS SHOWN ON THE PLANS. FIXTURE
LED 4000K
LUX #EOS3.0-R-GRZ SERIES
SHALL RAVE INTEGRAL RECESSED POCKET,
WHITE FINISH 1%DIMMING DRIVE
F6
LED UNDERCABINET LIGHT
SURFACE
120/277
27
1 6" FN5"Dx46L" HARDWIRED LINKABLE LED UNDER
2600 LUMEN
EQUALTO
CABINET LIGHT,>BOCRI, 12" LINKING EXTENSION,
LED
HEALTHCARE LIGHTING
ON/OFF ROCKER SWITCH, DIMMABLE DRIVER
4000K
4HU%546-MVOLT-LED4000K-S1LX12-GW
HIGH IMPACTACRYLIC LENS, AND WHITE FINISH
F7
2X4 LENSED LED VOLUMETRIC TROFFER
CEILING
1201277
30
2YA'x4"D, STEEL HOUSING, SMOOTH FROSTED LOW
4000 LUMEN
EQUAL TO
GLARE LENS, MATTE WHITE FINISH, 0-1 OV
LED
CREE *ZR24M-4OL-4OK-CMA-FD
DIMMABLE DRIVER TO 5% LUMEN OUTPUT, 80A
4000K
CRT. PROVIDE WITH SMARTCAST CONTROL.
F8
2X2 LENSED LED VOLUMETRIC TROFFER
COILING
120/277
35
2S07t5"D, STEEL HOUSING, SMOOTH FROSTED LOW
32DO LUMEN
EQUAL TO
GLARE LENS, MATTE WHITE FINISH, 010V
LED
CREE #ZR22-32L-00K-CMA-FD
DIMMABLE DRIVER TO 5% LUMEN OUTPUT, 80+
4000K
CRT. PROVIDE WITH SMARTCAST CONTROL.
S1
EXTERIOR WALL MOUNTED LED
1201277
18
TFM6'W)6.5"D DIE CAST ALUMINUM LED WALL
2000-2200
EQUALTO
LIGHT WITH INTEGRAL BACK BOX, SEALED
LUMEN LED
LUMARK #XTOR2B-W
OPTICAL COMPARTMENT, WET LOCATION IP66
4000K
LISTED, DARK BRONZE POWDERCOAT FINISH_
L1
I LED LANDSCAPE LIGHT
120
1
10
3" DIAMETER x 21"H LOW BOLLARD WITH
800 - 1000
FOUAL TO
ALUMINUM HOUSING AND BASE, HIGH IMPACT UV
LUMEN LED
LUMINIS #CL313-10120-BZT
STABILIZED WHITE ACRYLIC CYLINDRICAL
4000K
DIFFUSER DIMMIMG DRIVER BRONZE POLYESTER
PAINTFINISH_ CONFIRM VOLTAGE.
X
LED EXIT LIGHT
120/277
UNIVERSAL MOUNT, HICH IMPACT WHITE ASS
UNIVERSAL
LED
EQUALTO
THERMOPLASTIC HOUSING, DIRECTIONAL
MOUNT, TOP-
DUALL ITE#EVE-U-R-W-E-1
CHEVRONS, END OR CEILING OR WALL MOUNT,
BACKEND
RED LETTERING, SELF -DIAGNOSTICS,
EMERGENCY BATTERY, SINGLE OR DOUBLE FACE
WITH CHEVRONS AS SHOWN ON THE DRAWINGS
OR REQUIRED BY THE INSTALLATION, UL 924
,LISTED_
XE
LED EXIT LIGHT WITH EGRESS LIGHT HEADS
120/277
UNIVERSAL MOUNT, HIGH IMPACT WHITE ASS
UNIVERSAL
LED
EQUALTO
THERMOPLASTIC HOUSING, DIRECTIONAL
MOUNT, TOP-
DUAL-LITE#EVGLLR-W-I
CHEVRONS, END OR CEILING OR WALL MOUNT,
BACKEND
RED LETTERING, SELF -DIAGNOSTICS,
EMERGENCY BATTERY, SINGLE OR DOUBLE FACE
WITH CHEVRONS AS SHOWN ON THE DRAWINGS
OR REQUIRED BY THE INSTALLATION, TWO
ADJUSTABLE INTEGRAL LED LAMP HEADS, UL 924
LISTED.
PANEL SCHEDULE
PANEL NAME: RPS
VOLTAGE: 120/208 VOLT, THREE PHASE,
RATING: IOUAMP MLO
ENCLOSURE: NEMA 1
FOUR WIRE
LOCATION: 1ST FUR ELEC
MOUNTING. SURFACE
KAIC RATING 10
GROUND BUS: YES
CKT
DESCRIPTION
BREAKER
LOAD IN KVA
LOAD IN KVA
BREAKER
DESCRIPTION
CKT
POLE
TRIP
LTS
RECP
MOTOR
MISO "A" "B" "C" LTS
RECP
MOTOR
MISC
POLE
TRIP
1
3
5
VAV-04
1
1
1
25
30
20
2.00
2.50
2.00
250
0.00
1
20
DISHWASHER
2
VAV-05
SPARE
1
20
UC ICE
4
1
20
CAFE RECEPTACLES
6
7
9
11
REF
REF
NEE
1
1
1
20
20
20
O.OU
000
0.00
1
20
MICROWAVE
8
1
1
20
20
MICROWAVE
CAFE RECEPTACLES
10
12
13
15
17
NAC PANELS
SPARE
ISPARE
1
1
1
20
20
20
0.00
COO
O.00
1
1
20
20
DISPOSAL
COFFEE
14
16
1
20
ICEIWATER
18
19
21
23
SPARE
SPARE
SPARE
1
1
1
20
20
20
0.00
000
O.00
1
1
20
20
SPARE
SPARE
20
22
1
20
SPARE
24
25
27
29
SPARE
SPARE
SPARE
1
1
1
20
20
20
O.OD
0.00
0.00
1
1
1
20
20
20
SPARE
SPARE
SPARE
26
28
30
2.130
2SOI 0.00
TOTAL CONNECTED LIGHTING LOAD
TOTAL CONNECTED RECP LOAD
TOTAL CONNECTED MOTOR LOAD
TOTAL CONNECTED MSC. LOAD
1100 KVA
0 00 KVA
0.00 KVA
450 KVA
TOTAL DEMAND LIGHDNG LOAD
TOTAL DEMAND RECEPTACLE LOAD
TOTAL DEMAND MOTOR LOAD
TOTAL DEMAND MISC. LOAD
10
NEC
1
1.0
000 KVA _
' 0 00 KVA
0,00 KVA
450 KVA
TOTAL CONNECTED LOAD 4.50 KVA
TOTAL DEMAND LOAD OF 4.50 KVA
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Cannel �
TYPICAL ABBREVIATIONS:
A
AMPS OR AMPACITY
AFF
ABOVE FINISHED FLOOR
AIC
AMPERAGE INTERRUPTING CAPACITY
AV
AUDIO—VISUAL
C
CONDUIT
CB
CIRCUIT BREAKER
CCTV
CLOSED CIRCUIT TELEVISION SYSTEM
CKT
CIRCUIT
COMB
COMBINATION
CU
COPPER
E—G
ENGINE —GENERATOR
EC
ELECTRICAL CONTRACTOR
EM
ON EMERGENCY SYSTEM
EMT
ELECTRIC METAWC TUBING
EWC
ELECTRIC WATER COOLER
EXP
EXPLOSION —PROOF
FA
FIRE ALARM
FOS
FUSIBLE DISCONNECT SWITCH
GC
GENERAL CONTRACTOR
CFI
GROUND FAULT INTERRUPT
GND
GROUND
G
GREEN GROUND CONDUCTOR
HP
HORSE POWER
IMC
INTERMEDIATE METAL CONDUIT
JB
JUNCTION BOX
KV
KILOVOLTS
KVA
KILOVOLT AMPERES
KW
KILOWATTS
MAN
MASTER ANTENNA TELEVISION SYSTEM
MC
MECHANICAL CONTRACTOR
MH
MAN HOLE
MTR
MOTOR
NEC
NATIONAL ELECTRICAL CODE
NEMA
NATION ELECTRICAL MANUR ASSOC.
NIC
NOT IN THIS CONTRACT
0
PHASE
PBS
PUSH BUTTON STATION
PC
PULL CHAIN
PNL
PANEL
PP
DOOR OPERATOR PUSH PLATE
PVC
POLYVINYLCHLORIDE
RGS
RIGID GALVANIZED STEEL CONDUIT
RM
ROOM
STO
STANDARD
SS
STAINLESS STEEL
TV
TELEVISION
TYP
TYPICAL
US
UNGROUNDED
UNO
UNLESS NOTED OTHERWISE
UON
UNLESS OTHERWISE NOTED
V
VOLTS
W
WATTS
IMP
WEATHERPROOF
POWER LEGEND
SUBSCRIPTS ASSOCIATED WTH RE
(GFI) GROUND FAULT RECEPTACLE
(H) HORIZONTALLY MOUNTED C ABOVE COUNTER
OR ABOVE COUNTER BACKSPLASH TO BOTTOM,
UNLESS NOTED OTHERWSE
(WP) WEATHERPROOF COVER WITH GROUND FAULT
RECEPTACLE.
® SPECIAL RECEPTACLE
SINGLE RECEPTACLE WALL OUTLET WITH 2OA, 125V
SINGLE RECEPTACLE MOUNTED 18' A.F.F. TO
BOTTOM, UNLESS NOTED OTHERWISE.
DUPLEX RECEPTACLE WALL OUTLET WITH 2OA, 125V
DUPLEX RECEPTACLE MOUNTED 18' A.F.F. TO
BOTTOM, UNLESS NOTED OTHERWISE
DOUBLE DUPLEX WITH (2) 20A, 125V DUPLEX
RECEPTACLES. MOUNT 18' A.FY TO BOTTOM,
UNLESS NOTED OTHERWISE.
DUPLEX RECEPTACLE WITH 2OA, 125V DUPLEX
MOUNTED 4' ABOVE COUNTER OR ABOVE COUNTER
BACKSPLASH TO BOTTOM, UNLESS NOTED
OTHERWISE
O FLOOR OUTLET AS NOTED.
n G) JUNCTION BOXES
SURFACE RACEWAY WITH RECEPTACLES AS
>� SPECIFIED ON DRAWING. PLANS SHALL INDICATE
LOCATION OF DEVICE BRACKET AND RECEPTACLE
Sp SWITCH WITH PILOT LAMP
Sap WEATHERPROOF SWITCH
MANUAL MOTOR CONTROLLER WITH THERMAL
Si OVERLOAD TO SUIT MOTOR, P=PILOT, MOUNT W
AST UNLESS NOTED OTHERWISE.
PUSH BUTTON STATION AS SPECIFIED. MOUNT 44"
A.F.F. TO TOP, UNLESS NOTED OTHERWISE.
MUSHROOM HEAD OPERATOR. MOUNT 44' A.F.F. TO
CENTER, UNLESS NOTED OTHERWISE.
10/y NON —FUSED DISCONNECT SWITCH MOUNTED AT
19 4'-6' TO TOP, UNLESS NOTED OTHERWISE,
SUBSCRIPT INDICATES SWITCH RATING.
"I F20 FUSED DISCONNECT, MOUNT 4'-6' A.F.F. TO TOP,
SUBSCRIPT INDICATES SWITCH RATING & VISE SIZE,
FAR=FUSE AS REQUIRED. FIELD VERIFY FUSE SIZE.
COMBINATION MAGNETIC MOTOR CONTROLLER SUIT
F20 TO MOTOR, MOUNT AT 4'-6" A.F.F. TO TOP,
UNLESS INDICATED OTHERWISE. SUBSCRIPT
INDICATES SWITCH RATING & FUSE SIZE, FAR=FUSE
AS REWIRED. FIELD VERIFY FUSE SIZE.
VARIABLE FREQUENCY CONTROLLER WITH
DISCONNECT, MOUNT AT 4'-6' A.F.F. TO TOP,
UNLESS INDICATED OTHERWISE.
30/3 MAGNETIC MOTOR CONTROLLER SUIT TO MOTOR,
® MOUNT AT d-C A.F.F. TO TOP, UNLESS INDICATED
OTHERWISE. SUBSCRIPT INDICATES SWITCH RATING.
MOTOR AS SCHEDULED.
s ELECTRICAL POWER PANEL (RECESSED MOUNTED)
MEN ELECTRICAL POWER PANEL (SURFACE MOUNTED)
1 GROUND
RP1-14,16118
3P-100A
4#22#6G-1.2511C.
POWER RISER DIAGRAM
LIGHTING LEGEND
S SINGLE POLE SWITCH
Ss THREE WAY SYATCH
SA FOUR WAY SWITCH
So AUTOMATIC DOOR SWITCH
So SWITCH WITH PILOT LAMP
Ss KEY OPERATED SWITCH
Sop WEATHER PROOF SWITCH
DIMMER (CONNECTED TO OS OR VS WHERE
0% APPUCABLE) (X = VS INTEGRAL VACANCY SENSOR)
IN OCCUPANCY SENSOR MOUNTED AT SWITCH HEIGHT
I] VACANCY SENSOR MOUNTED AT SWITCH HEIGHT
'O,M,c' LOWER CASE LETTERS AT LUMINAIRES INDICATE
SWITCHING ARRANGEMENT.
Ll CEDING MOUNTED LUMINARIES AS SCHEDULED.
'X' INDICATES FIXTURE TYPE.
ilid CEILING MOUNTED LUMINARIES WITH EMERGENCY
BATTERY BACKUP. 'X' INDICATES FIXTURE TYPE.
O CEILING MOUNTED FIXTURE AS SCHEDULED.
U WALL MOUNTED WMINAIRE AS SCHEDULED.
M. SYMBOL INDICATES NIGHT LIGHT WHEN SHOWN ON
LIGHTING PLAN ADJACENT TO LUMINARIES
+20'-0' SYMBOL INDICATED MOUNTING HEIGHT OF WALL
MOUNTED LUMINARIES FROM A.F.F. TO BOTTOM
I CEILING MOUNTED SINGLE FACED EXIT LIGHT FIXTURE
e AS SCHEDULED WITH DIRECTIONAL ARROW AS
SHOWN ON DRAWINGS.
CEILING MOUNTED DOUBLE FACED EXIT LIGHT
m FIXTURE AS SCHEDULED WITH DIRECTIONAL ARROWS
AS SHOWN ON DRAWINGS.
WALL MOUNTED SINGLE FACED EXIT LIGHT FIXTURE
I AS SCHEDULED WITH DIRECTIONAL ARROWS AS
SHOWN ON DRAWINGS, MOUNT 7'-4' A.F.F UNLESS
NOTED OTHERWISE.
WALL MOUNTED DOUBLE FACED EXIT UGHT FIXTURE
FQ AS SCHEDULED WITH DIRECTIONAL ARROWS AS
SHOWN ON DRAWINGS, MOUNT 7'-4' AFT UNLESS
NOTED OTHERWISE.
® CEILING MOUNTED OCCUPANCY SENSOR
® CEILING MOUNTED VACANCY SENSOR
® CEILING MOUNTED DAYUGHT HARVESTING SENSOR
FIRE ALARM LEGEND
® FIRE ALARM MANUAL PULL STATION, MOUNT 487
TO THE CENTER, UNLESS OTHERWISE NOTED.
COMBINATION FIRE ALARM HORN / VISUAL
0 ANNUNCIATION DEVICE. MOUNT 80' A.F.F. TO
BOTTOM OR 6' BELOW CEILING, WHICHEVER IS
LOWER. 15 CANDELA IF NOT NOTED HIGHER.
FIRE ALARM HORN, MOUNT 80' A.F.F. TO BOTTOM
OR 6' BELOW CENNG TO BOTTOM, WHICHEVER IS
LOWER.
FIRE ALARM VISUAL ANNUNCIATION DEVICE, MOUNT
0/ 80' A.F.F. TO BOTTOM OR 6' BELOW CEILING TO
BOTTOM, WHICHEVER IS LOWER. 15 CANDELA IF NOT
NOTE HIGHER.
DUCT —TYPE SMOKE DETECTOR. INTERLOCK WITH
FIRE ALARM SYSTEM FOR AUTOMATIC FAN
SHUTDOWN. LOCATE IN DUCT AS NOTED ON PLAN.
OF H CEIUNG MOUNTED RATE OF RISE HEAT DETECTOR.
FO CEIUNG MOUNTED SMOKE DETECTOR.
® TAMPER SWITCH, PROVIDE ADDRESS MODULE AND
MAKE REQUIRED CONNECTION TO SUPERVISE FIRE
PROTECTION SYSTEM.
®ROW SWITCH, PROVIDE ADDRESS MODULE AND
MAKE REQUIRED CONNECTIONS TO SUPERVISE FIRE
PROTECTION SYSTEM.
® FIRE ALARM CONTROL PANEL
®A FIRE ALARM REMOTE ANNUNCIATOR PANEL
INAC NOTIFICATION APPUANCE CIRCUIT POWER PANEL.
�s WATER/GAS SOLENOID AS SPECIFIED. PROVIDE
C� ELECTRICAL CONNECTION AS REQUIRED.
® WALL MOUNTED MAGNETIC DOOR HOLDER. F=FLOOR
MOUNTED.
ADDRESSABLE RELAY
TECHNOLOGY LEGEND
❑V INTERCOM SPEAKER VOLUME CONTROL
cs INTERCOM CALL SWITCH AS SPECIFIED. MOUNT 44"
A.F.F. TO TOP, UNLESS NOTED OTHERWISE.
VOICE/DATA OUTLET IN WALL. STUB 1' CONDUIT
FROM OUTLET INTO NEAREST ACCESSIBLE CENNG
(X) AND BUSH END. MOUNT 18' AF.F TO BOTTOM,
UNLESS NOTED OTHERWISE. (X=CABLE QUANTITY)
DATA OUTLET IN WALL STUB 1' CONDUIT FROM
OUTLET INTO NEAREST ACCESSIBLE CEILING AND
N BUSH END. MOUNT le A.FY TO BOTTOM, UNLESS
NOTED OTHERWISE. (X=CABLE QUANTITY)
VOICE OUTLET IN WALL STUB 1' CONDUIT FROM
OUTLET INTO NEAREST ACCESSIBLE CEILING AND
M BUSH END. MOUNT 18' A.F.F TO BOTTOM, UNLESS
NOTED OTHERWISE. (X=CABLE QUANTITY)
b EMPTY OUTLET FOR WALL MOUNTED SPEAKER BY
OTHERS FOR PA/INTERCOM SYSTEM AS SPECIFIED.
SQ EMPTY OUTLET FOR CEILING MOUNTED SPEAKER BY
OTHERS FOR PA/INTERCOM SYSTEM AS SPECIFIED.
E=M CLOSED CIRCUIT TV CAMERA
® CARD READER AS SPECIFIED. MOUNT 44' A.F.F. TO
TOP, UNLESS NOTED OTHERWISE.
® TV OUTLET IN WALL. STUB 1- CONDUIT FROM
OUTLET INTO NEAREST ACCESSIBLE CBUNG AND
BUSH END. COORDINATE MOUNTING HEIGHT WITH
TELEVISION MOUNT.
12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE
SUPPORT CONNECTED TO STRUCTURE ABOVE
BOX
E CONDUIT J.`
WIRE /
LAY —IN. CEILING
LAY IN LIGHT FIXTURE DETAIL
NOT TO SCALE
REVISIONS
NO. Descnpvion & Dace
NO. Description & Dace
NO. Description & Dace
JOB NO.: IDB-119.2607
DATE: 1-18-19
DRAWN BY: FWH
CHECKED BY: XXX
,�N � 11111/1'�0�.
��GVSTEgd; 9%'G
o'
10100828
3 STATE OF '
SIGNATURE
TOM 4nwMa W W memt= �n lb
proyvt� m etteto�w 0.s.1w .m
aEW mt b e.Dt^avaM In whoM m N
p.pA hx .ns m..a.. m.on.mw o
.wwme, wmsem .m.....rntwc
pemren
U
Z
LI J
UQ
Z
0
LU
Z
-
C
O
N
VI 0'%
0
UC
C:)
CL
C
Inc!
Z
Q
Q
37
Z
oo
L.L
LL
Lyo
.L
LI J
CL
SHEET
MO I
DATE: 04/12/19
NOT TO SCALE
PROPRIETARY AND CONFIDENTIAL
ELECTRICAL
SYMBOLS,
ABBREVIATIONS,
AND SCHEDULES