HomeMy WebLinkAboutE-002 ELECTRICAL SPECIFICATIONS1600.00 ELECTRICAL SPECIFICATIONS
GENERAL ELECTRICAL REQUIREMENTS
APPLICABLE CODES: CONTRACTOR'S INSTALLATION SHALL COMPLY PATH CURRENT NEC CODE ADOPTED BY STATE/AREA WHERE WORK
IS PERFORMED. VERIFY ADOPTED CODE AND STATE'S/AREAS AMENDMENTS TO CODE IF ANY. LOCAL AHJ (AUTHORITY HAVING
JURISDICTION) SHALL BE USED AS A RESOURCE DURING CONSTRUCTION WHERE APPLICABLE. ALL REFERENCES TO NEC WITHIN
THESE SPECIFICATIONS ARE IN REFERENCE CODE DESCRIBED ABOVE.
1.0 BASIC ELECTRICAL REQUIREMENTS
1.1 MATERIAL SUBSTITUTIONS: MATERIALS, EQUIPMENT AND SPECIALTY ITEMS SHOWN IN THESE DRAWINGS AND SPECIFICATIONS ARE
SPECIFIED AROUND A UST OF BRAND NAMES KNOWN FOR AND PERFORMANCE PROVEN TO THE ENGINEER. ONLY THOSE
MANUFACTURERS NAMED IN THESE DRAWINGS AND SPECIFICATIONS OR IN A WRITTEN ADDENDUM WILL BE APPROVED FOR THE
PROJECT. THE TERMS "OR EQUAL" AND "APPROVED EQUAL' ARE MEANT TO APPLY ONLY TO THOSE MANUFACTURERS AND BRAND
NAMES LISTED HEREIN AND DOES NOT IMPLY "OR EQUAL" OUTSIDE THE LIMITS OF THE NAMED MANUFACTURERS. THE ENGINEER
RESERVES THE SOLE RIGHT FOR THE APPROVAL OF PROPOSED ADDITIONAL MANUFACTURERS, MATERIAL, AND/OR EQUIPMENT.
1.2 SUBMITTALS SUBMIT ONE (1) ELECTRONIC COPY OF BROCHURES, CATALOG OUT SHEETS, TECHNICAL DATA OR DRAWINGS OF ALL
EQUIPMENT AND/OR MATERIALS SUBMITTALS DRAWINGS SHALL STATE CAPACITIES PHYSICAL DIMENSIONS AND WEIGHTS, AS WELL AS
FULLY DESCRIBE ALL OPTIONS AND APPURTENANCES NECESSARY TO DEMONSTRATE THAT THE EQUIPMENT MEETS THE INTENT OF
THESE DRAWINGS AND SPECIFICATIONS. THE REVIEW OF SHOP DRAWINGS BY THE ENGINEER DOES NOT RELIEVE THE CONTRACTOR OF
1.3 PERMITS AND INSPECTIONS: THE CONTRACTOR SHALL OBTAIN AND FURNISH ALL NECESSARY PERMITS AND INSPECTION CERTIFICATES
FOR ALL MATERIAL AND LABOR FURNISHED BY HIM. THE COST OF PERMITS, CERTIFICATES, AND ALL INSPECTION FEES REQUIRED IN
CONNECTION WITH THE INSTALLATION OF THE ELECTRICAL SYSTEMS SHALL BE BORNE BY THE CONTRACTOR.
1.4
1.4.1
1.5
PROVIDE TEMPORARY UGHTING TO OTHER TRADES FOR WORK DURING ELECTRICAL OR UGHTING SYSTEM DOWNTIME FOR THE
DURATION OF THE PROJECT. ALL TEMPORARY LIGHTING SHALL BE REMOVED AT END OF PROJECT.
1.6 STANDARDS OF MATERIALS AND WORKMANSHIP: ALL WORK SHALL CONFORM TO OR EXCEED THE MINIMUM REQUIREMENTS OF THE
NATIONAL ELECTRIC CODE (NEC), THE CURRENTLY ENFORCED EDITION, AND ALL FEDERAL, STATE, LOCAL, AND MUNICIPAL
ORDINANCES. ALL MATERIALS SHALL BE NEW, COMPLETE WITH UNDERWRITERS LABORATORIES (UL), INC., AND CARRY THE UL LABEL,
IF A STANDARD HAS BEEN ESTABUSHED FOR THAT TYPE OF MATERIAL. ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER
AND SHALL PRESENT A NEAT MECHANICAL APPEARANCE WHEN COMPLETED.
1.7 EXISTING CONDITIONS THIS CONTRACTOR SHALL EXAMINE THE EXISTING PROJECT SITE AND FAMILIARIZE HIMSELF WITH THE
CONDITIONS AS THEY EXIST, OR THAT WILL IN ANY MANNER AFFECT HIS WORK UNDER THIS CONTRACT. ALL CONDITIONS SHALL BE
CONSIDERED IN THE PREPARATIONS OF BIDS.
1.7.1 NOT ALL EXISTING ELECTRICAL EQUIPMENT, DEVICES, LIGHT FIXTURES, ETC. ARE SHOWN ON THE DRAWINGS. THE ELECTRICAL
SUBCONTRACTOR IS RESPONSIBLE FOR CONDUCTING A SURVEY OF THE JOB SITE TO DETERMINE THE EXTENT OF THE EXISTING
EQUIPMENT DEVICES LIGHT FIXTURES ETC. AND HIS WORK.
1.8 DAMAGES: THIS CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE TO THE WORK OF OTHER TRADES OR TO THE FACILITY AND ITS
CONTENTS CAUSED BY EQUIPMENT INSTALLED BY HIM.
1.8.1 REMOVE AND REPLACE CEILINGS AS REQUIRED TO PERFORM ALL WORK ASSOCIATED WITH THIS PROJECT. ANY GRID AND/OR TILES
DAMAGED AS PART OF THE REMOVAL OR REINSTALLATION PROCESS SHALL BE REPLACE BY THE ELECTRICAL CONTRACTOR AT HIS
COST.
1.9 CLEANUP: THIS CONTRACTOR SHALL KEEP THE PREMISES CLEAN OF ALL DEBRIS CAUSED BY HIS WORK. AT THE CONCLUSION OF
CONSTRUCTION, THE SITE SHALL BE THOROUGHLY CLEANED OF ALL RUBBLE, DEBRIS AND UNUSED MATERIALS.
1.10 CLOSE-OUT: THIS CONTRACTOR SHALL PROVIDE ALL DOCUMENTS, AFFIDAVITS, GUARANTEES AND TRAINING REQUIRED FOR PROJECT
CLOSE-OUT INCLUDING THE FOLLOWING:
OPERATING AND MAINTENANCE MANUALS (5 BOUND COPIES)
RECORD "AS -BUILT' DOCUMENTS (CD)
GUARANTEES AND WARRANTIES
1.11 SITE WORK:
1.11.1 THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE ALL SITE WORK, TRENCHING BACK FILL, DRIVE/WALK REPAIR, AND ALL OTHER
WORK ASSOCIATED WTH THE INSTALLATION OF NEW SERVICES OR CIRCUITS AS PART OF THIS PROJECT.
1.11.2 PROTECT LAWN AREAS, TREES, SHRUBS, SIDEWALKS, DRIVES, MONUMENTS, ETC. FROM DAMAGE DURING CONSTRUCTION. RE -GRADE,
RESEED, AND RE -PAVE ANY AREAS THAT ARE DISTURBED.
1.11.3 THE ELECTRICAL SUBCONTRACTOR IS RESPONSIBLE FOR LOCATING ALL EXISTING SITE UTILITIES AS REQUIRED TO PERFORM
DESIGNATED WORK AS PART OF THIS PROJECT. REROUTING SERVICES IN CONFLICT OR REROUTE NEW WORK AS REQUIRED TO
COMPLETE PROJECT.
1.11.4 EACH TRADE SHALL REPAIR ALL DAMAGE CAUSED BY WORK PROMPTLY AND COMPLETELY TO THE SATISFACTION OF THE OWNER AND
PERFORMANCE SERVICES INC.
1.11.5 COORDINATE ALL SITE WORK WTH THE OWNER AND PERFORMANCE SERVICES INC. PRIOR TO EXECUTION.
1.11.6 COORDINATE ALL UTILITY WORK WITH LOCAL UTILITIES. ANY MODIFICATIONS DIRECTED BY UTILITY THAT ARE DIFFERENT THAN THAT
SHOWN ON DRAWINGS SHALL BE COORDINATED WITH ENGINEER PRIOR TO EXECUTION.
1.12 CUTTING, PATCHING. AND PAINTING:
1.12.1 THE SUBCONTRACTOR SHALL PATCH, REPAIR, MATCH TEXTURE, AND PAINT ALL EXISTING SURFACES WHERE ELECTRICAL EQUIPMENT,
DEVICES, ETC. ARE BEING REMOVED OR SURFACES THAT ARE DAMAGED DURING INSTALLATION OF NEW EQUIPMENT AND DEVICES.
1.12.2 THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE ALL FLOOR, WALL, AND CEILING PENETRATIONS TO COMPLETE HIS WORK. PROVIDE
PROPER FIRE STOPPING FOR ALL PENETRATIONS MADE THROUGH RATED WALLS AND ASSEMBLIES.
1.12.3 PAINT ALL NEW CONDUIT. JUNCTION BOXES, AND HANGERS TO MATCH ADJACENT SURFACES WHERE INSTALLED IN EXPOSED
LOCATIONS.
2,0 BASIC ELECTRICAL MATERIALS AND METHODS
2.1 SUPPORTS THIS CONTRACTOR SHALL PROVIDE MISCELLANEOUS LUMBER AND METAL FRAMING FOR THE SUPPORT OF ELECTRICAL
MATERIALS AND EQUIPMENT. PROVIDE WOOD OR METAL GROUNDS, NAILERS BLOCKING, FASTENERS AND ANCHORAGE AS REQUIRED.
MATERIALS SHALL BE OF COMPARABLE QUALITY AND TYPE USED FOR THE GENERAL CONSTRUCTION IN THE ARE WHERE INSTALLED.
2.2 JOINT SEALERS: PROVIDE JOINT SEALERS FOR SEALING AROUND ELECTRICAL MATERIALS AND EQUIPMENT. PROVIDE FIRE RESISTANT
SEALERS WHERE CONDUIT AND/OR WIRING EXTENDS THROUGH FIRE AND/OR SMOKE RATED WALLS AND FLOORS SEAL ALL CONDUIT
PENETRATIONS OF THE BUILDING WALLS AND FOUNDATIONS BELOW GRADE.
2.2.0 FIRE STOPPING:
221 PROVIDE APPROPRIATE SEALANT (I.E. FIRE STOPPING) OR BARRIERS TO MAINTAIN CONSTRUCTION INTEGRITY FOR ANY PENETRATIONS
THROUGH FLOORS, STRUCTURAL CEILINGS, AND FIRE WALLS.
222 FIRE STOPPING METHOD SHALL BE UL LISTED AND RATED FOR PENETRATIONS APPLIED.
2.2.3 HILT TYPE FS-ONE FOR MECHANICAL/ELECTRICAL ROOM PENETRATIONS.
3.0 RACEWAYS:
3.1 GENERAL: ALL POWER WIRING, ALL WRING FOR OVER 24 VOLTS, AND DESIGNATED SYSTEMS WIRING SHALL BE ROUTED IN EMT
RACEWAY UNLESS NOTED OTHERWISE. ALL WIRING AND CONDUIT SHALL BE INSTALLED CONCEALED IN FINISHED SPACES EXCEPT
WHERE SURFACE WIRE WAYS ARE NOTED. CONDUIT MAY BE ROUTED EXPOSED IN MECHANICAL AND ELECTRICAL ROOMS, ATTIC SPACE
AND IN AREAS WHICH HAVE NO CEILINGS.
3.2 OUTDOORS: PVC CONDUIT (SCHEDULE 40) - BELOW GRADE AND IN CONCRETE.
3.3 INDOORS USE THE FOLLOWING WRING METHODS - ABOVE FLOOR
RICH) METAL CONDUIT (CRC) (WHERE INDICATED OR REQUIRED)
ELECTRICAL METALLIC TUBING (EMT) (NOT IN EARTH OR CONCRETE)
METAL SURFACE RACEWAY (ONLY WHERE SPECIFICALLY NOTED ON PLANS OR APPROVED BY ARCHITECT) PAINT TO MATCH WALL.
USE THE FOLLOWING WIRING METHODS - BELOW FLOOR
PVC CONDUIT (SCHEDULE 40)
3.4 =. THE MINIMUM CONDUIT SIZE SHALL BE 3/4" UNLESS NOTED OTHERWISE. DEDICATED SWITCH LEGS MAY BE RUN IN 1/2'
CONDUIT.
3.5 FIBS; PROVIDE CONDUIT BODIES OF THE TYPES, SHAPES AND SIZES AS REQUIRED BY THE INSTALLATION AND THE NEC. USE
METALLIC BODIES WITH STEEL CONDUIT AND PLASTIC WITH PLASTIC CONDUIT. RIGID CONDUITS (GRC AND INC) SHALL BE FOUND WITH
THREADED TYPE CONNECTIONS AND COUPLINGS. EMT SHALL BE JOINED WITH CONNECTORS OF STEEL OR MALLEABLE IRON AND
SHALL BE OF THE COMPRESSION OR SET SCREW TYPE. INDENTOR, FRICTION AND DIE-CAST METAL CONNECTORS WILL NOT BE
PERMITTED. PROVIDE INSULATED BUSHINGS AT ALL ENTRANCES TO PANEL BOARDS, STARTERS, PULL BOXES, ETC.
3.6 VIBRATING EQUIPMENT: CONNECT TO VIBRATING EQUIPMENT AND HYDRAULIC PNEUMATIC OR ELECTRIC SOLENOID OR MOTOR -DRIVEN
EQUIPMENT WITH UQUID TIGHT FIEABLL METAL CONDUIT.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camnel �
4.0 WIRE AND CABLES:
4.1 GENERAL: PROVIDE COPPER WIRE AND CABLE WITH 600 VOLT INSULATION SUITABLE FOR THE TEMPERATURE, CONDITIONS, AND
LOCATIONS WHERE INSTALLED. MINIMUM SIZE BRANCH CONDUCTORS $HALL BE $12 MINIMUM AND TEMPERATURE RATING SHALL BE
75'C. ALUMINUM CONDUCTORS SHALL BE ALLOWED WITH WRITTEN APPROVAL FROM PERFORMANCE SERMCES INC.
4.2 CONDUCTORS: PROVIDE STRANDED CONDUCTORS FOR SIZES /8 AWG AND LARGER. SOLD FOR #10 AND AND SMALLER. (THE
INTENTION OF THE SOLD WIRE IS FOR TERMINATION AT RECEPTACLES. STRANDED /10 AWG AND SMALLER MAY BE USED IN
CONDUITS UP TO DEVICE, BUT TERMINATE WITH SOLID)
4.3 INSULATION: PROVIDE THHN OR THWN FOR ALL CONDUCTOR INSULATION. (NOTE THAT CONDUIT SIZE SHOWN ON THESE DRAWINGS IS
BASED ON THHN INSULATION. LARGER CONDUIT MAY BE REQUIRED FOR OTHER INSULATIONS.)
4A FLEXIBLE CONDUIT (OR NO CABLEI: THE USE OF SHALL BE UNITED TO SERVE NEW RECEPTACLES AND SWITCHES IN EXISTING WALLS
OR ON UGHTING FIXTURES WHERE NOT PROVIDED OR BEING RELOCATED. A JUNCTION BOX MUST BE UTIUZED NEAR THE WALL WTH
THE NEW DEVICE. FLEXIBLE CONDUIT MUST BE PLENUM RATED AND HAVE AN APPROPRIATE SIZE NEUTRAL ADDITIONAL MC CABLE
USE SHALL BE ALLOWED WITH WRITTEN APPROVAL FROM PERFORMANCE SERVICES INC., PRIOR TO INSTALLATION. MC CABLE SHALL
BE SIMILAR TO SOUTHWRE ARMORUTE.
5"0 CABINETS, BOXES, AND FITTINGS:
5.1 GONER PROVIDE OUTLET AND DEVICE BOXES, PULL AND JUNCTION BOXES, CABINETS, HINGED DOOR ENCLOSURES AND BOXES AND
FITTINGS FOR HAZARDOUS LOCATIONS AS INDICATED ON THESE DRAWINGS, AS REQUIRED BY NEC OR BY THE INSTALLATION.
5.2 OUTLET, DEVICE AND SMALL PARING BOXES: PROVIDE METAL BOXES ON METAL RACEWAYS AND NON-METAWC BOXES ON
NON-METAWC RACEWAYS. BOXES SHALL BE OF THE TYPE, SHAPE, SIZE AND DEPTH TO SUIT EACH LOCATION AND APPLICATION.
BOXES SHALL INCLUDE STAMPED KNOCKOUTS, THREADED SCREW HOLES, AND APPROPRIATE ACCESSORIES SUCH AS MOUNTING
BRACKETS AND STRAPS, CABLE CLAMPS. GROUNDING TERMINALS, EXTERIOR RINGS AND FIXTURE STUDS. BOXES SHALL HAVE FIRE
RATINGS MATCHING WALL INSTALLATION.
5.3 PULL AND JUNCTION BOXES: PULL AND JUNCTION BOXES SHALL HAVE SCREWED COVERS AND SHALL BE OF THE SIZE AND SHAPE
TO SUIT THE APPLICATION.
5.4 CABINETS CABINETS SHALL CONSIST OF A BOX AND A FRONT WTH A ONE PIECE FRAME AND A LOCKING, HINGED DOOR. PROVIDE A
FRONT WITH APPROXIMATELY 3/4' OVERLAP ON ALL EDGES FOR FLUSH CABINETS AND THE SAME SIZE AS THE BOX FOR SURFACE
CABINETS, UNLESS NOTED OTHERWSE.
5.5 NEMA 1 CONSTRUCTION: PROVIDE THE FOLLOWING:
STEEL BOXES - PAINTED - GRAY ENAMEL
HOT -DIPPED GALVANIZED STEEL BOXES
5.6 NEMA 3 AND 3R CONSTRUCTION: PROVIDE THE FOLLOWING:
STEEL BOXES - PAINTED - GRAY ENAMEL
HOT -DIPPED GALVANIZED STEEL BOXES
STAINLESS SCREWS
5.7 ACCESSORIEc: PROVIDE DOOR HANDLES, LATCHES, KEY LOCKS, DRIP GUARDS, MOUNTING PANELS, DOOR STOPS, PADLOCK HASPS,
GASKETS/SEALS AND OTHER ACCESSORIES AD REQUIRED. ALL BOXES, CABINETS, AND ENCLOSURES WHICH ARE NOT SECURED BY
SCREWS OR BOLTS SHALL HAVE PROVISIONS FOR LOCKING THE DOOR OR COVER.
6.0 ELECTRICAL CONNECTIONS FOR EQUIPMENT:
6.1 N RAL THIS CONTRACTOR SHALL EXTEND THE ELECTRICAL POWER WIRING TO EACH PIECE OF EQUIPMENT INDICATED ON THESE
��
DRAWINGS AND SCHEDULES. THIS SHALL INCLUDE WIRING AND RACEWAY TO THE TERMINALS OF THE EQUIPMENT OR PLUG
RECEPTACLE AS REQUIRED.
6.2 EQUIPMENT: MOTOR STARTERS, DISCONNECT SWITCHES, JUNCTION BOXES, WHICH ARE NOT AN INTEGRAL PART OF THE EQUIPMENT,
FURNISHED BY OTHER TRADES, THE OWNER OR PERFORMANCE SERVICES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR AS
PART OF THIS PROJECT.
6.3 MOTOR/HVAC EQUIPMENT CONNECTIONS: CONTRACTOR SHALL CONNECT MOTORS WITH WEATHER TIGHT FLEXIBLE
CONDUIT/CONNECTIONS PROPERLY SIZE FOR THE WIRE INDICATED ON DRAWINGS. MINIMUM SIZE SHALL BE 3/4". CONTRACTOR
SHALL PROVIDE 90' CONNECTION AT MOTOR WHERE A STRAIGHT CONNECTION WOULD PUT A LARGE LOOP IN CONDUIT. MAXIMUM
LENGTH FOR MOTOR CONNECTION SHALL BE A MAXIMUM OF 3'-0' UNLESS WRITTEN APPROVAL FROM PERFORMANCE SERVICES INC.
CONTRACTOR SHALL HARD WIRE TO A POINT NO FARTHER THAN 3' FROM MOTOR, SECURELY MOUNTING CONDUIT AS REQUIRED THEN
EXTENDING TO MOTOR MA FLEXIBLE CONDUIT DESCRIBED ABOVE.
7,0 WIRING DEVICES:
7.1 GAL PROVIDE WIRING DEVICES OF THE TYPE, CHARACTERISTICS, GRADES, COLORS AND ELECTRICAL RATINGS FOR EACH
APPLICATIONS INDICATED ON THESE DRAWINGS.
7.2 MANUFACTURERS
EATON/COOPER WIRING DEVICES
HUBBELL. INC.
LEVITON
LEGRAND/PASS AND SEYMOUR. INC.
7.3 DNADP. SWITCHES AND RECEPTACLES SHALL BE CONSTRUCTED FROM THERMOPLASTIC NYLON.
CaaR: GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE IVORY COLOR. SPECIAL PURPOSE OUTLETS (DEVICES OTHER
THAN 15A OR 20A RATED) SHALL BE BLACK IN COLOR.
7.4 RECEPTACLES: ALL RECEPTACLES SHALL BE HEAVY DUTY GRADE, GROUNDING TYPE DUPLEX RECEPTACLES SHALL BE RATED AT 20
AMPERES.
7.5 USE RECEPTACLES: TWO 3.1A USB CHARGING PORTS AND TWO 20A RECEPTACLES, EQUAL TO EATON IIIR7756
7.5 COVER PLATES: COVER PLATES SHALL BE OF THE APPROPRIATE TYPE AND SIZE TO ACCOMMODATE THE DEVICES. COVER PLATES
SHALL BE STAINLESS STEEL WEATHERPROOF COVER PLATES SHALL BE PROVIDED FOR ALL EXTERIOR RECEPTACLES AND SNITCHES
WHERE INDICATED ON THESE DRAWINGS. WET LOCATION COVER PLATES SHALL DIE CAST METAL, GRAY, BE LISTED AS 'WET LOCATION
WITH COVER CLOSED', IDENTIFIED AS 'EXTRA DUTY AND SHALL HAVE A COVER WHICH CLOSES WITH A CORD SET PLUGGED INTO
THE RECEPTACLE.(TAYMAC MX4380S) ISOLATED GROUND AND HOSPITAL GRADE RECEPTACLES (WHERE REQUIRED) SHALL BE
LABELED/USTED AS SUCH,
8"0 CIRCUIT AND MOTOR DISCONNECTS:
8.1 GENERAL. PROVIDE CIRCUIT AND MOTOR DISCONNECT SWITCHES IN TYPES, SIZES, DUTIES, FEATURE, RATINGS AND ENCLOSURES AS
INDICATED OR AS REQUIRED BY THE NEC OR THE APPLICATION. PROVIDE NEMA 1 ENCLOSURES FOR INDOOR SWITCHES AND NEMA 3R
ENCLOSURES WITH RAINTIGHT HUBS FOR EXTERIOR SWITCHES. FOR MOTORS AND STARTER DISCONNECTS, PROVIDE UNITS WITH
HORSEPOWER RATINGS SUITABLE FOR THE LOAD.
8.2 MANUFACTURERS:
ALLEN-BRADELY COMPANY
APPLETON
CROUSE-HINDS COMPANY
CUTER -HAMMER
GENERAL ELECTRIC
ITE/GOULD, INC.
SIEMENS ENERGY AND AUTOMATION, INC.
SQUARE D COMPANY
8.3 FUSIBLE SWITCHES: PROVIDE HEAVY DUTY SWITCHES WTH FUSES OF THE CLASSES AND CURRENT RATINGS INDICATED OR REQUIRED.
PROVIDE UL SERMCE ENTRANCE LABEL WHERE USED AS MAIN SERVICE DISCONNECT. PROVIDE TYPE "RKT FUSES FOR MOTOR LOADS
AND TYPE "L" FOR SERVICE ENTRANCE SWITCHES..
8.4 GROUNDING: PROVIDE EQUIPMENT GROUNDING CONNECTIONS FOR DISCONNECT SWITCH ENCLOSURES AND GROUND IN ACCORDANCE
WITH NEC AND AS STATED HEREIN.
9"0 ELECTRICAL IDENTIFICATION:
9.1 GENERA PROVIDE IDENTIFICATION OF ELECTRICAL MATERIALS, EQUIPMENT AND INSTALLATIONS. PROVIDE EQUIPMENT LABELS,
WARNING AND CAUTION SIGNS, OPERATING INSTRUCTION SIGNS AND IDENTIFYING LABELS FOR THE FOLLOWING:
DISCONNECTS, MOTOR STARTERS, AND VARIABLE FREQUENCY DRIVES
CONTACTORS AND RELAYS
CABINETS AND ENCLOSURES
CONTROL AND ALARM PANELS
SWITCHBOARDS, UGII AND POWER PANELS
9.2 WIRE ABLE MARKERS: PROVIDE VINYL OR VINYL -CLOTH, SELF-ADHESIVE, WRAP -AROUND, CABLE/CONDUCTOR MARKERS WITH
PREPRINTED NUMBERS AND LETTERS.
9.3 ENGRAVED PLASTIC LAMINATE: PROVIDE ENGRAVED PLASTIC LAMINATED LABELS, SIGNS AND INSTRUCTION PLATES OF STOCK
MELAMINE PLASTIC. ENGRAVED LEGENDS SHALL BE WHITE LETTERS ON BLACK FACE. PROVIDE 1/16 INCH THICK FOR SIGNS UP TO 20
SQUARE INCHES OR 8 INCHES IN LENGTH AND 1/8 INCH THICK FOR LARGER SIGNS TAGS FOR EMERGENCY POWER SYSTEMS SHALL
BE RED BACKGROUND WITH WHITE ENGRAVED LETTERS. PROVIDE EQUIPMENT LABEL IN 1/2" TALL LETTERS AND POWER SOURCE
(PANEL NAME AND CIRCUIT) IN 1/4' LETTERS
9.4 CONDUCTOR COLOR CODES: PROVIDE COLOR CODING FOR SECONDARY SERVICE, FEEDER AND BRANCH CIRCUIT CONDUCTORS
THROUGHOUT THE PROJECT. SECONDARY ELECTRICAL SYSTEM AS FOLLOWS: (IDENTIFY THE HIGH -LEG ON ALL OPEN DELTA
CONNECTIONS PER NEC 110.15)
PHASE 120/240 VOLT PHASE 2081 VOLT PHASE 277/480 VOLTS
A BLACK A BLACK A BROWN
B RED B RED B ORANGE
C BLUE C YELLOW
NEUTRAL WHITE NEUTRAL WHITE NEUTRAL WHITE/GRAY
GROUND GREEN GROUND GREEN GROUND GREEN
IG GREEN I.G. GREEN I.G. GREEN
9.5 JUNCTION BOXES PROVIDE WRITTEN LABEL TO ALL JUNCTION BOXES. LABEL JUNCTION BOX COVERS WITH CIRCUIT NUMBERS
LOCATED WITHIN JUNCTION BOXES WITH BLACK SHARPIE.
9.6 COVERPLATES7 PROVIDE LABEL TO BACK OF ALL COVERPLATES. LABEL BACK OF COVERPLATES OF SWITCHES AND RECEPTACLES
WITH CIRCUIT NUMBER FEEDING DEVICE WTH BLACK SHARPIE.
10.0 GROUNDING:
10.1 GENERA THIS CONTRACTOR SHALL EXTEND THE ELECTRICAL POWER WIRING TO EACH PIECE OF EQUIPMENT INDICATED ON THESE
DRAWINGS AND SCHEDULES THIS SHALL INCLUDE WIRING AND RACEWAY TO THE TERMINALS OF THE EQUIPMENT OR PLUG
RECEPTACLE AS REQUIRED.
10.2 EQUIPMENT GROUNDING SYSTEM: THE EQUIPMENT GROUNDING SYSTEM SHALL GROUND ALL ELECTRICAL EQUIPMENT, METAWC
RACEWAYS, ENCLOSURES AND ALL NON CURRENT -CARRYING PARTS OF ELECTRICAL EQUIPMENT, SOUND EQUIPMENT, ALARM SYSTEM
EQUIPMENT, MECHANICAL EQUIPMENT AND OTHER BUILDING SYSTEM EQUIPMENT WHICH USES ELECTRICITY OR WHICH COULD BECOME
ENERGIZED UNDER FAULT CONDITIONS. AN EQUIPMENT GROUNDING CONDUCTOR, SIZED IN ACCORDANCE WITH NEC TABLE 250-95,
SHALL BE PROVIDED IN ALL CONDUIT, RACEWAY CABLE TRAY, ETC. ALL EQUIPMENT SHALL BE GROUNDED PATH AN EQUIPMENT
GROUNDING CONDUCTOR CABLE (GREEN OR GREEN WITH YELLOW TRACER).
10.3 EQUIPMENT GROUNDING CONDUCTOR: CONDUCTOR SHALL BE RUN IN THE SAME CONDUIT AND RACEWAY AS THE CURRENT CARRYING
CONDUCTORS, WITHOUT EXCEPTION.
10.4 STEEL(MAGNETIC) CONDUIT: USED FOR MECHANICAL PROTECTION OF A GROUNDING CONDUCTOR SHALL BE SECURELY BONDED TO
THAT CONDUCTOR AT EACH END.
11.0 PANELBOARDS:
11.1 CENERe1. ELECTRICAL CONTRACTOR TO PROVIDE 120/208 VOLT 30 DISTRIBUTION PANELS AND MAIN SERVICE EQUIPMENT AS SHOWN
AND SCHEDULED ON THE DRAWINGS.
11.2 REGULATIONS: CONFORM TO REQUIREMENTS OF NFPA 70. FURNISH PRODUCTS LISTED AND CLASSIFIED BY UNDERWRITERS
LABORATORIES INC. AS SUITABLE FOR THE PURPOSE SPECIFIED AND SHOWN. INSTALL PANELBOARDS IN ACCORDANCE WITH NEMA PB
1.1.
11.3 MANUFACTURES:
EATON/CUTLER-HAMMER
GENERAL ELECTRIC COMPANY
SQUARE D COMPANY
SIEMENS
11.4 EXECUTION:
11.4.1 UGHTING AND APPLIANCE BRANCH CIRCUIT PANELBOARDS: NEMA PB7, CIRCUIT BREAKER TYPE.
11.4.2 PANELBOARD BUS: COPPER, RATINGS AS INDICATED. PROVIDE COPPER GROUND BUS IN EACH PANELBOARD.
11.4.3 MINIMUM INTEGRATED SHORT CIRCUIT RATING: 10,000 AMPERES EMS SYMMETRICAL FOR 240V PANELBOARDS: 14,000 AMPERES EMS
SYMMETRICAL FOR 480V PANELBOARDS OR AS NOTED.
11.4.4 MOLDED CASE CIRCUIT BREAKERS: NEMA AB 1, BOLT ON TYPE THERMAL MAGNETIC TRIP CIRCUIT BREAKERS WITH COMMON TRIP
HANDLE FOR ALL POLES. PROVIDE CIRCUIT BREAKERS UL LISTED AS TYPE SWD FOR LIGHTING CIRCUITS. PROVIDE UL A GROUND
FAULT INTERRUPTER CIRCUIT BREAKERS WERE SCHEDULED. DO NOT USE TANDEM CIRCUIT BREAKERS.
11.4.5 ENCLOSURE: NEMA PIT 1, TYPE 1.
11.4.6 CABINET BOX: 6 INCH DEPTH, 20 INCH WIDTH FOR 240 VOLT AND LESS PANELBOARDS, 20 INCH WIDTH FOR 480 VOLT
PANELBOARDS.
11.4.7 CABINET FRONT. RUSH AND SURFACE AS SCHEDULED CABINET FRONT WITH DOORAN-DOOR CONSTRUCTION AND FLUSH LOCK ALL
KEYED ALIKE. FINISH IN MANUFACTURER'S GRAY ENAMEL.
11.4.8 EC TO PROVIDE ENGRAVED IDENTIFICATION TAGS FOR EACH PANEL TAGS SHALL HAVE BLACK BACKGROUND WITH k HIGH WHITE
ENGRAVED LETTERS.
12.0 FUSES:
12.1 DENERAL PROVIDE FUSES OF THE TYPES, CLASSES AND CURRENT RATINGS AS INDICATED. VOLTAGE RATINGS SHALL BE CONSISTENT
WITH THE CIRCUITS ON WHICH THEY ARE USED.
12.2 MANUFACTURERS:
EATON BUSSMANN
UTTELFUSE
FERRAZ SHAWMUT
12.3 CARTRIDGE FUSES PROVIDE NON-RENEWABLE CARTRIDGE TYPE FUSES WHICH COMPLY WITH ANSI/IEEE STANDARD A.M.
CLASS RK1 DUAL ELEMENT TIME DELAY FUSES
12.4 CONTROL TRANSFORMERS AND BALLAST: PROVIDE NON-RENEWABLE CARTRIDGE TYPE FUSES CLASS KTK-R, CURRENT LIMITING,
COMPLYING WITH UL 198C, CLASS EQUAL. FUSE HOLDERS FOR ALL CLASS KTK-R FUSES PROVIDE EATON BUSSMANN TYPE HEB
SERIES TRON (1 POLE) OR TYPE HEY SERIES TRON (2 POLE) FUSE HOLDERS WHERE APPLICABLE.
12.5 APPLICATION: APPLY FUSES AS INDICATED ON THE DRAWINGS, OR AS FOLLOWS:
FUSES RATED 600 AMPERES OR LESS SHALL BE UL CLASS R
13,0 MOTOR CONTROLLERS:
13.1 GENERAL: PROVIDE A MOTOR CONTROLLER FOR EVERY MOTOR EXCEPT THOSE MOTORS 'WHICH ARE FURNISHED WITH CONTROL PANELS
WHICH INCLUDE CONTROLLERS. CONTROLLERS SHALL HAVE OVERLOAD PROTECTION FOR EACH PHASE AND SHALL INCLUDE A
DISCONNECT DEVICE.
13.2 MANUFACTURERS:
ALLEN-BRADELY COMPANY
EATON/CUTER HAMMER
GENERAL ELECTRIC
SQUARE D COMPANY
SIEMENS
13.3 PROVIDE COMBINATION CONTROLLERS CONSISTING OF A CONTROLLER AND A DISCONNECT SWITCH MOUNTED IN A COMMON
ENCLOSURE OF THE TYPES, SIZES, RATING AND NEMA RATINGS AS INDICATED. EACH UNIT SHALL HAVE AN OPERATING HANDLE FOR
THE DISCONNECT AND A DOOR INTERLOCK TO PREVENT THE DOOR FROM OPENING WHEN THE CONTROLLER IS ENERGIZED.
13.3.1 CONTROL POWER TRANSFORMER: PROVIDE A CONTROL POWER TRANSFORMER FOR 120 VOLT CONTROL POWER. TRANSFORMER SHALL
HAVE TWO (2) PRIMARY AND ONE (1) SECONDARY FUSES. A GROUNDED SECONDARY NEUTRAL AND SHALL BE SIZED AS REWIRED
TO POWER THE STARTER AND ANY EXTERNAL CONTROL DEVICES (MINIMUM SIZE 75 VA)
13.3.2 FUSIBLE SWITCH: PROVIDE FUSIBLE SWITCH ASSEMBLIES UNLESS OTHERWISE INDICATED ON THE DRAWINGS. SNITCH SHALL BE
QUICK -MAKE, QUICK -BREAK TYPE WITH EXTERNAL HANDLE WHICH CAN BE PADLOCKED IN THE "ON" AND "OFT POSITIONS FUSES
SHALL BE CLASS R UNLESS OTHERNSE NOTED.
13.4 MANUAL MOTOR STARTER: PROVIDE SINGLE-PHASE MANUAL MOTOR STARTERS WHERE INDICATED, OF THE SIZES AND RATINGS AS
PADLOCKED "OFF. IN FINISHED SPACES PROVIDE A FLUSH UNIT WITH A STAINLESS STEEL COVER PLATE, PILOT LIGHT AND WITHOUT
THE PADLOCK OPTION.
14.0 RELAYS. CONTACTORS AND CONTROLS:
14.1 DFNERe1. PROVIDE RELAYS, CONTRACTORS, TIME CLOCKS, PHOTOCELLS, PUSH BUTTONS, SELECTOR SWITCHES AND PILOT UGHTS AS
INDICATED ON THE DRAWINGS. AS REQUIRED IN THESE SPECIFICATIONS OR AS REQUIRED BY THE INSTALLATION.
14.2 MANUFACTURERS:
ALLEN-BRADLEY COMPANY
EATON/CUTLER HAMMER
GENERAL ELECTRIC
SQUARE D COMPANY
SIEMENS
15.0 PUSH BUTTONS. SELECTOR SWITCHES AND PILOT LIGHTS:
15.1 GENERAL
15.2 MANUFACTURERS:
EATON/CUTLER HAMMER
GENERAL ELECTRIC
SQUARE D COMPANY
SIEMENS
16.0 RELAYS:
16.1 GENERAL PROVIDE RELAYS AND CONTROL RELAYS AS SHOWN OR SCHEDULED ON THESE DRAWINGS OR AS REQUIRED BY THE
INSTALLATION. PROVIDE THE NUMBER AND TYPE OF CONTACTS WITH PROPER VOLTAGE/AMPERAGE RATINGS REQUIRED FOR A
COMPLETE AND OPERATING SYSTEM. TIMING RELAYS SHALL BE PLUG-IN, SOLID-STATE, ADJUSTABLE DELAY UNIT COMPLETE WITH
SOCKET AND RESTRAINING STRAP.
MECHANICAL SHEETS HAVE ADDITIONAL
ELECTRICAL WORK TO BE PERFORMED BY
ELECTRICAL CONTRACTOR
CONTRACTOR SHALL REFER TO MECHANICAL
SHEETS FOR ADDITIONAL WORK.
17.0 CONTACTORS:
17.1 GENERAL; PROVIDE CONTACTORS AS SHOWN OR SCHEDULED ON THESE DRAWINGS. PROVIDE THE NUMBER AND TYPES OF CONTACTS
WITH THE VOLTAGE AND AMPERAGE REQUIRED TO CONTROL THE LOAD. CONTACTORS SHALL BE RATED FOR FULL AMPERAGE TO THE
TYPE OF LOAD INDICATED (LIGHTING, HEAT, MOTOR, ETC.).
18,0 MANUAL CONTROLS:
18.1 GENERAL PUSH BUTTONS, SELECTOR SWITCHES AND PILOT LIGHTS SHALL BE HEAVY DUTY, INDUSTRIAL QUALITY DEVICES. THEY
SHALL MOUNT IN 30.5 MM HOLES. PROVIDE CONTACT BLOCKS AND CONFIGURATIONS AS INDICATED. PUSH BUTTONS SHALL BE
19.0 LIGHTING:
19.1 IN MOST CASES THE LIGHTING FIXTURES AND LAMPS FOR BOTH INDOOR AND OUTDOOR APPLICATIONS WILL BE PROVIDED BY
PERFORMANCE SERVICES, INC. THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE FOR HANDLING AND INSTALLATION OF ALL LIGHT
FIXTURES FOR THE PROJECT.
19.2 ALL FIXTURES SHALL BE AS SCHEDULED ON THE PLANS. ALL FIXTURES SHALL BE LAMPED AS SCHEDULED ON THE PLANS. LAMPS
SHALL BE TRANSPORTED AND HANDLED TO MINIMIZE BREAKAGE.
19.3 FIXTURES SCHEDULED ON THE PLANS TO BE CLEANED AND RELAMPED, SHALL BE DISASSEMBLED AND COMPLETELY CLEANED. ALL
SURFACES SHALL HAVE ALL ACCUMULATED DIRT REMOVED AND LENSES POLISHED. ANY MISSING FASTENERS SHALL BE REPLACED.
ANY FIXTURE FOUND NOT TO BE IN REUSABLE CONDITION SHALL BE REPORTED TO PERFORMANCE SERVICE, INC. IMMEDIATELY.
19.4 ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL HANDLING OF FIXTURES ON SITE. HE SHALL COORDINATE STORAGE
LOCATIONS OF FIXTURES ON SITE WITH GENERAL CONTRACTOR. ALL FIXTURES SHALL BE KEPT IN THE SHIPPING PACKAGING UNTIL
INSTALLED. ALL INDIRECT/DIRECT LENSED FIXTURES SHALL HAVE PROTECTIVE PLASTIC IN PLACE UNTIL FINAL CLEANING IS
COMPLETED.
19.5 ALL WIRING RUNS IN FIXTURES SHALL BE RATED AT 90'C. ALL CONNECTIONS SHALL BE APPROVED BY THE FIXTURE MANUFACTURER.
EACH FIXTURE SHALL BE CONNECTED WITH A FLEXIBLE CONDUIT AND WRING (WHIP) WTH A LENGTH NOT TO EXCEED 6'-0" IN
LENGTH.
19.6 ALL FIXTURES SUPPORTED FROM STEEL STRUCTURE SHALL BE SECURELY ATTACHED TO STRUCTURE WITH STEEL FASTENERS.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE INSTALLATION OF BOTH BALLAST AND LENS SAFETY CABLES/CHAINS. HE
SHALL ALSO PROVIDE ADDITIONAL SUPPORT STEEL FOR INSTALLATION OF FIXTURES IN LOCATION/PATTERN SHOWN ON PLANS.
"UNISTRUY IS APPROVED FOR ADDITIONAL SUPPORT STEEL
19.7 FIXTURES INSTALLED IN FIRE RATED CENNGS SHALL HAVE FIXTURE CUPS ATTACHED TO CEILING GRID SYSTEM. INSTALL RECESSED
LUMINARIES USING ACCESSORIES AND FIRE STOPPING MATERIALS TO MEET AND MAINTAIN CEILING FIRE RATING.
19.8 ELECTRICAL CONTRACTOR SHALL INSTALL ALL ACCESSORIES FURNISHED WITH EACH LUMINARIES. ALL FIXTURES SHALL BE INSTALLED
COMPLETE. ANY BROKEN FIXTURES SHALL BE REPORTED TO PERFORMANCE SERVICES, INC. IMMEDIATELY.
19.9 ALL FIXTURES SHALL BE GROUNDED AND BOND ALL INTERIOR FIXTURES PER NEC AND LOCAL REQUIREMENTS
19.10 ALL EXTERIOR FIXTURES SHALL BE GROUNDED TO BUILDING ELECTRICAL DISTRIBUTION SYSTEM. FIXTURE, SUPPORT AND BASE SHALL
ALL BE BONDED TOGETHER AND ATTACHED TO THE GROUNDING SYSTEM.
19.11 ALL LED FIXTURES SHALL FILTERED.
20.0 VARIABLE FREQUENCY DRIVES:
20.1 UNLESS SCHEDULED OTHERWISE ON THE PLANS, ALL VARIABLE FREQUENCY DRIVES WILL BE PROVIDED BY PERFORMANCE SERVICES,
INC. THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE FOR HANDLING AND INSTALLATION OF ALL VARIABLE FREQUENCY DRIVES
FOR THE PROJECT.
20.2 VARIABLE FREQUENCY DRIVES WILL BE PROVIDED WTH INTEGRAL DISCONNECT.
20.3 VARIABLE FREQUENCY DRIVES SHALL BE LOCATED AS SHOWN ON THE PLANS. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL
BLOCKING AND SUPPORTS FOR THE INSTALLATION OF DRIVES.
20.4 LINE SIDE AND LOAD SIDE POWER WIRING FROM THE VARIABLE FREQUENCY DRIVES SHALL BE INSTALLED IN SEPARATE CONDUITS.
20.5 WHERE DRIVE IS NOT WITHIN SIGHT DISTANCE OF THE MOTOR SERVED, THE ELECTRICAL CONTRACTOR SHALL PROVIDE A DISCONNECT
SWITCH AT THE MOTOR SERVED. PROVIDE INTERLOCK SAFETY WIRING FROM DISCONNECT SWITCH TO DRIVE. DRIVE SHALL TURN 'OFF"
IF REMOTE DISCONNECT SWITCH IS TURNED OFF.
20.6 VARIABLE FREQUENCY DRIVES SHALL BE INSTALLED PER THE MANUFACTURERS WRITTEN INSTALLATION INSTRUCTIONS.
20.7 ELECTRICAL CONTRACTOR SHALL PROVIDE A NEMA 3R ENCLOSURE FOR DRIVES MOUNTED OUTDOORS ENCLOSURE SHALL BE
VENTILATED AND HEATED PER THE MANUFACTURERS WRITTEN INSTALLATION INSTRUCTIONS.
20.8 ELECTRICAL CONTRACTOR SHALL PROVIDE ENGRAVED PLASTIC IDENTIFICATION PLATE FOR EACH VARIABLE FREQUENCY DRIVE.
21.0 SURGE -PROTECTIVE DEVICE (SPD
21.1 RATED AND TESTED FOR CATEGORY C3 (20KV, 10KA, 8 BY 20 MICROSECOND WAVEFORM) AS DEFINED BY ANSI/IEEE C62.41
21.2 WTH SYSTEM VOLTAGE RATING: 480Y/277, 3 PHASE, 4 WIRE GROUNDED, 6OHZ.
21.3 PROTECTION MODES: EACH LINE TO NEUTRAL, EACH UNE TO GROUND, NEUTRAL TO GROUND.
21.4 MAXIMUM SURGE CURRENT CAPACITY (8 X 20 MICROSECONDS) FOR MULTIPLE OCCURRENCES WITH MINIMUM CAPACITY ALLOWED IS
240,000 AMPS L-L, 120,000 AMPS L-N, 120,000 AMPS L-G, AND 120,000 N-G.
21.5 UL-1449 (2ND EDITION) CLAMPING VOLTAGE SUPPRESSION RATING L-N = 800, L-G = 800, AND N-G = 800.
21.6 SURVIVAL UFE RATING OF A MINIMUM OF 1000 ANSI/IEEE C62.41 SURGES WITH LESS THAN 10% DEGRADATION OF UL 1449 SURGE
RATING.
21.7 SHORT CIRCUIT INTERRUPTING RATING EQUAL TO OR GREATER THAN EXISTING EQUIPMENT AT POINT OF CONNECTION (PER NEC
ARTICLE 285) THE SPD SHALL NOT REQUIRE THE USE OF ANY UPSTREAM OVERCURRIENT PROTECTION TO MEET THIS RATING.
21.8 ACCESSORIES: PROVIDE WITH INTEGRAL FUSED DISCONNECT, MODULE STATUS INDICATOR LIGHTS, UNIT STATUS INDICATOR LIGHTS,
AUDIBLE ALARM AND SILENCE SWITCH, AND TRANSIENT COUNTER.
21.9 ACCEPTABLE MANUFACTURERS ADVANCE PROTECTION TECHNOLOGIES, INNOVATIVE TECHNOLOGIES, UEBERT CORPORATION AND
CUTLER HAMMER.
21.10 SUBMIT MANUFACTURER'S DATA & PERFORMANCE SHEET FOR APPROVAL WITH BID PACKAGE.
21.11 PROVIDE AND INSTALL A NEW SURGE -PROTECTIVE DEMCE (SPD) INSIDE OR NEXT TO THE NEW MAIN SWITCHBOARD.
21.12 IF UNIT IS MOUNTED EXTERNAL TO THE NEW MAIN SWITCHBOARD, PROVIDE OVER CURRENT DEMCE TO CONNECT TO THE
SWITCHBOARD. PROVIDE FUSING PER THE SPD MANUFACTURER'S INSTALLATION INSTRUCTIONS. LOCATE THE NEW SPD AS CLOSE AS
POSSIBLE TO THE MAIN DISTRIBUTION PANE AND WITHIN LIMITS OF THE SPD MANUFACTURES RECOMMENDED INSTALLATION
INSTRUCTIONS.
21.13 VERIFY EXISTING GROUNDING SYSTEM PERFORMANCE IS WITHIN THE UNITS OF THE NEW SPD MANUFACTURER'S INSTALLATION
INSTRUCTIONS AND THE ELECTRIC CODE REQUIREMENTS PROVIDE ADDITIONAL GROUNDING AND BONDING AS REQUIRED TO MEET
CURRENT REQUIREMENTS.
22.0 OCCUPANCY SENSORS
22.1 ALL OCCUPANCY SENSORS WILL BE FURNISHED BY PSI AND INSTALLED BY THE CONTRACTOR.
22.2 A SINGLE WALL OR COUNG MOUNTED SENSOR SERVING A SPACE SHALL BE EQUAL TO LLVTTON 80DC20-MDW (COILING) OR LEVITON
#ODW12-MDW (WALL).
22.3 A WALL SWITCH SENSOR SHALL BE EQUAL TO LEMTON {OSSMT-GD.
22.4 SENSORS SERVING THE FOLLOWING LOCATION OR INSTALLATION TYPES SHALL BE LEVITON IOSC20-MOW (CEILING) OR IEVTON
/OSW12-MOW (WALL) WITH AN /OSP20-RDH POWER PACK AND RELAY:
LOCATIONS WHERE THE SENSOR ALSO INTERFACES HVAC EQUIPMENT CONTROL.
LOCATIONS WHERE MULTIPLE SENSORS CONTROL THE SAME GROUP OF LIGHT FIXTURES.
LOCATIONS WHERE MULTIPLE CIRCUITS ARE CONTROLLED BY THE SAME SENSOR (ADD ON RELAY REQUIRED).
23.1 INDOOR, VENTILATED, PAD MOUNTED, DRY TYPE WITH COPPER OR ALUMINUM COIL.
23.2 220 DEGREE C INSULATION CLASS WITH A MAXIMUM OF 150 DEGREE C RISE ABOVE 40 DEGREE C AMBIENT.
23.3 TAPS - TWO 2.5% ABOVE AND TWO 2.5% BELOW NORMAL FULL CAPACITY.
23.4 GROUND BAR INSIDE TRANSFORMER ENCLOSURE.
REVISIONS
NO.
DescnPcion & Dace
NO.
Description & Dace
NO.
Description & Dace
JOB NO.:
MINEEN
IDB-119.2607
DATE:
1-I849
DRAWN BY:
MH
CHECKED BY: XXX
Qf
10100828
3` STATE OF ' c
. /ADIAVP.'
OF
SIGNATURE
T'W. a.w.ma .m a+ a®baY w w
proyvt� et Messvanw wa,Nw av4
,EW mt b e.Dt^avaM In whol. m N
.aewme, wnhew .m.....rnrm
gym.
U
Z
v
LU
UQ
NNNNNNN
Z
O
N
11IL1)
•
Z
C
O
N
N 0�
°
LU
UQ
o
d
ZQ
Q
z:
Z
CII
0
LL
aL
LU
CL
SHEET
E-002
DATE: 04/12/19
PROPRIETARY AND CONFIDENTIAL
ELECTRICAL
SPECIFICATIONS