HomeMy WebLinkAboutE-203 FIRST FLOOR POWER AND SYSTEMS PLANGENERAL NOTES
RELEASED FOR CONSTRUCTION
0 4' 8' 16'
NORTH SCALE: 1 /8" = V-0"
1. ALL MATERIAL/EQUIPMENT REMOVED BY SUBCONTRACTORS SHALL BE DISPOSED OF OFF
SITE. OWNER HAS FIRST RIGHT OF REFUSAL FOR ANY EQUIPMENT/MATERIAL/PARTS
REMOVED FROM PROJECT.
2. FIRE ALARM VISUAL DEVICES SHALL BE SET AT 15 CANDELA WHERE NO VALUE SHOWN.
3. CIRCUIT NUMBERS SHOWN FROM EXISTING PANELS ARE FOR REFERENCE ONLY. USE
ACTUAL BREAKERS AVAILABLE AFTER DEMOLITION WORK IS COMPLETE.
4. COLOR OF WIRING DEVICES AND COVERPLATES SHALL MATCH EXISTING.
PLAN NOTES
1. PROVIDE POWER CONNECTION TO ELECTRIC DUCT HEATER. PROVDIE 30A DISCONNECT
SWITCH.
2. PROVIDE FLUSH JUNCTION BOX FOR FURNITURE FEED CONNECTION TO PARTI110NS.
BRANCH CIRCUIT(S) AS INDICATED.
3. PROVIDE FLOOR BOX FOR FURNITURE FEED CONNECTION TO PARTITIONS. BRANCH
CIRCUIT(S) AS INDICATED. SAW CUT SLAB AND ROUTE CONDUIT UP IN NEARBY NEW
WALL PROVIDE SIMILAR BOX FOR DATA CABLING WITH 1.25" CONDUIT TO ABOVE
ACCESSIBLE CEILING.
4. FOR ELEVATOR RECALL
5. CONNECT NEW RECEPTACLES IN THIS ROOM TO BRANCH CIRCUIT LISTED, UNLESS
OTHERWISE NOTED.
S. EXISTING RECEPTACLES SHALL REMAIN IN THIS ROOM, UNLESS OTHERWISE NOTED.
7. CONNECT TO EXISTING FACE BRANCH CIRCUIT.
B. PROVIDE NEW SWITCH FOR CONTROL OF EXISTING BREAK AREA EXHAUST FAN. WIRE
INTO EXISTING EF CIRCUIT AS REQUIRED. PROVIDE "EXHAUST FAN" NAMEPLATE ON
SWITCH COVERPLATE
9. CONNECT TO EXISTING RECEPTACLE BRANCH CIRCUIT SERVING THIS AREA.
10. INSTALL BEHIND TV MONITOR. COORDINATE MOUNTING WITH TV SUPPORT BRACKET.
11. STUB CONDUIT THROUGH WALL FOR OUTDOOR WAR INSTALL AS HIGH AS POSSIBLE
ABOVE FIRST FLOOR CEILING.
12. INSTALL RECEPTACLES ABOVE COUNTER EXCEPT FOR RECEPTACLE SERVING UNDER
COUNTER REFRIGERATOR.
13. INSTALL AT CEILING PROJECTOR.
14. INSTALL ABOVE COUNTER BACKSPLASH.
15. SAW CUT FLOOR TO INSTALL CONDUITS FOR POWER AND DATA (1.25")TO RECEPTION
DESK. ROUTE FROM ABOVE ACCESSIBLE CEILING DOWN IN WALL, TURN UP INTO
FRAMED WALL OF CASEWORK AND TO DEVICE LOCATIONS.
16. REMOVE THREE 1P-20A CIRCUIT BREAKERS SERVING VENDING MACHINES REMOVED
DURING THE DEMOLITION PHASE. INSTALL A NEW 3P-100A CIRCUIT BREAKER IN
SPACE CREATED. NEW BREAKER SHALL BE SAME MANUFACTURER, TYPE, AND AIC
RATING AS EXISTING. USE NEW 100A BREAKER TO FEED NEW PANEL RES.
17. INSTALL ALL GFCI RECEPTACLES SHOWN AT CASEWORK ABOVE COUNTER
BACKSPLASH.
18. INSTALL ONE RECEPTACLE AT EACH MICROWAVE SHELF. SEE CASEWORK ELEVATION
FOR CONFIGURATION.
19. RELOCATE RECEPTACLE TO NEW WALL FACE.
20. INSTALL 6" BELOW TOP OF COUNTERTOP.
21. RELOCATED MOTORIZED PROJECTION SCREEN FROM CONTROLS AREA. REINSTALL
ORIGINAL CONTROL SWITCH IN NEARBY WALL AND CONNECT TO SCREEN. CONNECT
SCREEN TO RECEPTACLE CIRCUIT SERVING THE AREA.
REVISIONS
NO. Description & Dare
NO. Description & Dace
NO. Description & Dare
JOB NO.: IDB-119-2607
DATE: 1-1"9
DRAWN BY: FWH
10100828
STATE OF
0
SIGNATURE
Insist drawls( W Lb am4Yb was the
=a eaLwm.m. Larrbaa r
to rae aw ft wbla r as
WtroWby a w118auL rtpta� eyLe4
pamlw Mwl
U
Z
vi
LEI
U_Q
�
z
a
0
p[
Z
LU
-
c
0
o
UCIL
0 0
Z
z
Q
a
o
z
O
IL
LU
11.
G�
C�
O
Cz
E co
0)
Ov
i�
aC/-)
SHEET
Emw203
Subject to compliance with all regulations
of State and Local Codes
City of Cannel
DATE: 04/12/19
FIRST FLOOR POWER AND SYSTEMS PLAN
SCALE: 1/8"=l90"
PROPRIETARY AND CONFIDENTIAL
FIRST FLOOR
POWER AND
SYSTEMS PLAN