HomeMy WebLinkAboutM-401 MECHANICAL DETAILSDIFFUSER, GRILLE, & REGISTER
SCHEDULE
TAG
CFM
DIMENSIONAL DATA
THROW DATA
MOUNTING
PRESS.
DROP
MAX NC
SOUND
LEVEL
MANUFACTURE
/ MODEL #
MODULE
SIZE
SLOT DIFF INFO
INSLOT WIDTH
INLET
SIZE
DIRECTION
DISTANCES
100FPM
A
0-119
24X24
6
4-WAY
3
LAY -IN
0.02
20
TINS #OMNI
B
120-249
24X24
8
4-WAY
5
LAY -IN
0.06
20
TINS #OMNI
C
250-349
24X24
10
4-WAY
7
LAY -IN
0.07
20
TINS #OMNI
D
350-WO
24X24
12
4-WAY
9
LAY -IN
0.11
20
TINS #OMNI
E
550-750
24X24
14
4-WAY
16
LAY -IN
0.15
20
TINS #OMNI
F
0-225
SXB
8)3
LAY -IN
0.05
11
TINS #50F
G
225-550
12X12
12X12
LAY -IN
0.05
13
TINS #50F
H
550-2250
24X24
24X24
LAY -IN
0.05
14
TITUS #50F
1
150a50
4'
(4) 1-1/2"
10
2-WAY
18
LAY -IN
0.09
19
TITUS #TBD410
J
1 350-450
1 4'
(4) 1-1/2"
12
2-WAY
26
LAY -IN
0.09
26
Trrus #TBD80
K
OA40
12x12
1-WAY
LAY -IN
1 0.05
1 20
ITITUS #35ORL
L
1440-19001
1
1 24x24
1 1-WAY
I
I LAY -IN
1 0.05
1 20
TRUS #35ORL
NOTES:
TITUS OMNI-AA = ALUMINUM
TITUS OMNI d STEEL
TITUS 50F = ALUMINUM BOARDER AND GRILLE
TITUS SLOTTED-BO= UNINSULATED BOOT
TITUS SLOT TBDIEO = INSULATED BOOT
ENERGY RECOVERY UNIT SCHEDULE
SUPPLY/ EXHAUST MOTOR DATA
UNIT ELECTRICAL DATA
I HEAT EXCHANGER DATA
UNIT
MARK
RENEWAIRE
NO
MODEL NO
EXHAUST SUPPLY TYPE HP VOLTSI ESP
I
FLA MCA MOCP
I
TYPE SUMMER WINTER SENSIBLE
I I
WEIGHT
NOTES
CFM CFM PHASE
HX % EFF HX % EFF HX %EFF
LBS.
ERVA
EV45ORT
435
435
Pay
0.5
120/1
0.34
8.1
10.1
15
PLATE
58
63
73
250
1-6
NOTES:
1.) Supply and exhaust shall have 2" MEIN 8 fillers. Unit mFg. to provide two complete sets.
2.) Manufacturer shall provide single point electrical connection with unit mounted disconnect and motor starters With control contacts.
3.) Provide unit complete with exterior cabinet construciton, insulated 14" high roof curb, and RTR rooftop adapter for side discharge of supply air.
4.) Controls will be provided by PSI. Provide 24VAC transformer/relay package.
5.) Unit to be insulated double wall minimum 1" insulation.
S.) Drain pan 4o be stainless steel, insulated.
Single Duct Terminal Unit Schedule
Tag
AHU
Room
Model
Size
Unit Outlet
CFM
Max
Min
Static Pressure
Inlet Down Min
NC Levels
Red. Dlseh.
Electric Heat Coil
CFM KW VOIfsIPh. SEa pa EAT LAT
Electrical
MCA MOP
Unitlnformation
Hand
VAV-01
RTII-4
Ogmand Office
DESV
08
1200
160
0
0.5
0.25
0.01
-
13
160
2
120/1
S
55
95.2
20.8
25
LH
VAV-02
RTLI-4
HR CONF.
DESV
08
12x10
175
0
0.5
0.25
0.01
-
13
175
2
120/1
S
55
91.7
20.0
25
LH
VAV-03
RTU-.3
Scott M
DESV
06
12x8
100
0
0.5
0.25
0.01
-
-
100
1
120/1
S
55
87.1
10.4
15
RH
VAV-04
RTUI
Accounting Office
DESV
08
12x10
150
0
0.5
0.25
0.01
-
13
150
2
120/1
S
55
97.8
20.8
25
RH
VAV-05
RTLLi
Scott M
DESV
08
12x10
205
0
0.5
0.25
0.01
-
14
M5
2.5
120/1
S
55
94.2
26.0
30
RH
NOTES:
1.) Selections are based on Titus as Manufacturer.
2.) All performance based on tests conducted in accordance with ASHRAE 130-2DO8 and AHRI 8862008.
3.) All NC le\e1s determined using AHRI 8852008 Appendix E.
4.) All aimow, pressure losses and heating performance values haze been connected for altitude.
5.) Units of measure: tlimensions (in), airfiow (ofm), air pressure (in wg), and temperatures (degF).
6.) In the "Steps" column, code "S" denotes a modulating SCR heater.
7.) The minimum supply circuit ampacity (MCA) and maximum aercurrent protection (MOP) ratings were calculated in accordance with UL standards based on motor and electric coil full load current ratings.
8.) Check submittal drawings for exact dimensions.
9.) Blanks (-) indicate a sound power level or INC under 20.
10.) Provide units with 22 gauge casing, muflipoint flow sensor on inlet. Disconnect With fusing, control transformer and speed controller.
11.) Provide units with fiber free, 1" insulation and bottom access panel.
12.) Pmvide units with mounting of all TCC's control components.
13.) Provide units tail cannection and control panel on same side of terminal.
75 11
T
19-1/4"
28it
a
r
1
EV450RT WITH RTF/RTR ADAPTER
(45RTRF) AND CURB (45CURB)
IN RTR CONFIGURATION
RELEASED FOR CONSTRUCTION
CONTROL
MAINTAIN
SUPPLY AIR
FROM MAIN
SUPPORT TERMINAL UNIT -
NTH DUCT STRAP AT ALL
FOUR CORNERS
ro1,
FASTEN WITH TWO
SCREWS MINIMUM
TRANSITION
TO INLET SIZE
TYPICAL VAV
INSULATED LOW PRESSURE TERMINAL UNIT
FLEXIBLE DUCT (12' MAX)
LOW
S.A.
COL
REHEAT
VAV TERMINAL UNIT W/ REHEAT COIL DETAIL
NO SCALE
FLEXFLOW ELBOW BY
THERMAFLEX
www.flexflowelbow.com
h_._ ..._..._ . _...__ ___..._.... __.. _..._
AT ALL ROUND NECK WTLETSANLETS UNLESS
OTHERWISE NOTED ON DRAWINGS.
FLEXIBLE DUCT CONNECT TO AIR OUTLET /
INLET DETAIL
NO SCALE
BIRD SCREEN
FLEXIBLE DUCT
nexFlow Elbow by-
Thennaflex
www.flexflowelbow.com
COUNG
STRUCTURE
SUSPEND ELBOW
FROM STRUCTURE
NOTE: INSTALL FLEXIBLE
DUCTWORK SUPPORTS AT
ALL ROUND NECK
OUTLETS/NLETS UNLESS
OTHERWISE NOTED ON
DRAWINGS.
DRAW BANDS SNUG,
WTHOUT CRUSHING
FLEXIBLE DUCT
TRIM STRAPS AFTER
TIGHTENING
FLEXIBLE DUCT CONNECT TO AIR OUTLET /
INLET DETAIL
NO SCALE
FLEX DUCT, MAX. ALLOWABLE
LENGTH = 5 FT.�
TYPICAL SUPF
AIR DIFFUSER
VOLUME DAMPERS /
TRUNK DUCT)
AT CONTRACTOR'S OPTION, IN
LIEU OF RIGID ELBOW, USE NON
COLLAPSIBLE FRAME EQUAL TO
*FUEX-FLOW ELBOW.
LAY -IN CENNG
HIGH EFFICIENCY 45' RECTANGULAR
ENTRY BRANCH RTRNG TAKEOFF
SUPPLY AIR DIFFUSER CONNECTION DETAIL
NO SCALE
COUNTER FLASHING REMOVE EXISTING I
SEAL WATER TIGHT FAN
--- FLASHING I I -
- - SLOPE (APPROI(IMATELY
ROOF r------------------ t FOR WATER RUN-OFF
PROVIDEE 20 GAUGE I I PROMDROMDE 1' RIGID
ALUMINUM CAP INSULATION
_l _l
FASTEN
CURB
AND SEALOWAATER
RGHT
EXISTING GURB�
FASTEN TO
DECK
ROOF OPENING
6" EXHAUST
DUCTWORK
CPVC FLUETHRU ROOF DETAIL
5 NO SCALE
EXISTING ROOFING
EXISTING ROOF DECK
n ROOF CAP ENCLOSURE DETAIL
U NO SCALE
il3•Ik1CiI&
NO. Description & Date
NO. Description & Date
NO. Description & Date
JOB NO.: IDB-119-2607
DATE: 1-18-19
DRAWN BY: TPT
CHECKED BY: KLB
10100828
STATE OF
Fes/-/r,`/,'v-.�w J }?ffna.•'.
SIGNATURE
'ILIw drawly wd as o®r®ta me Wa
aps�mtr a Fmraawmweha msd
sm\ a rwpraaue a..ear. m m
eue M w=r ram=•• mmeww=n m
wtmwm=, .nao=t mrp..m wrluw
enrol.+==.
U
Z
LJ
U_Z
Q
0
/
ClI
LJ
Z
0
I
v �
0
0 0
U
IL rq
Or!
Z
Q
Q
Q
3,.,7
Z
/
tall
0
ILL
LJ
C�
O
L `n
Ou
i>
G�
.ate
SHEET
MA01
Subject to compliance with all regulations
of State and Local Codes
City off Commit
lj rt"113300�
DATE: 04/12/19
PROPRIETARY AND CONFIDENTIAL
MECHANICAL
DETAILS