HomeMy WebLinkAboutF002 - Fire Protection Specifications123456781011121314151617BA91234567810111213141516179DrawnProject ManagerCheckedContract Drawing DateProject NumberQPNMLKJHGFEDCBA18191819QPNMLKJHGFEDCB202120212222TSRTSRRevit Template Versionv16: 2017.10.05This document is the product and property of Baxter Hodell Donnelly Preston, Inc. Neither the document nor the information itcontains may be copied or used for other than the specific project for which it was prepared without the written consent of BaxterHodell Donnelly Preston, Inc.
CINCINNATI
COLUMBUS
RALEIGH
PITTSBURGH
ATLANTA
LAWRENCE DIGENNARO, ARCHITECT
302 WEST THIRD STREET
SUITE 500
CINCINNATI, OHIO 45202
PHONE 513.271.1634HIG02.21THE HARTFORD GROUP - 3RD FLOOR RENOVATION
501 PENNSYLVANIA PKWY #400
INDIANAPOLIS, IN 46280
No.Issue/Revision/Submission Date
1 ISSUED FOR BID AND PERMIT 12/14/20182016.05.27F002FIRE PROTECTION SPECIFICATIONSZPKJRHDCP GENERAL INFORMATIONA.GENERAL1.CONFORM TO GENERAL AND SPECIAL CONDITIONS OF CONTRACT.2.CHECK OTHER PLANS AND SPECIFICATIONS AND FULLY COORDINATE WITH OTHER TRADES,OWNER AND ARCHITECT REQUIREMENTS.3.VISIT SITE, CHECK FACILITIES AND CONDITIONS MAKE NECESSARY OBSERVATIONS,MEASUREMENTS, NOTE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED, AND TAKEITEMS INTO CONSIDERATION IN BID.4.SYSTEMS SHALL BE COMPLETE AND WORKABLE IN RESPECTS, AND PLACED IN OPERATION.5.CONTRACTOR SHALL PROVIDE FOR HIS OWN CLEAN-UP, REMOVAL AND LEGAL DISPOSAL OFRUBBISH DAILY. CONTRACTOR SHALL PROTECT THEIR WORK AND EXISTING OR ADJACENTPROPERTY AGAINST WEATHER, TO MAINTAIN THEIR WORK, MATERIALS, APPARATUS ANDFIXTURES FREE FROM INJURY OR DAMAGE. ANY WORK DAMAGED BY FAILURE TO PROVIDEPROTECTION REQUIRED, SHALL BE REMOVED AND REPLACED WITH NEW WORK AT THECONTRACTOR'S EXPENSE.6.CONTRACTORS SHALL CONFIRM TO UTILITY COMPANY REQUIREMENTS. COORDINATECONNECTION POINTS IN FIELD.7.ARRANGE FOR AND OBTAIN OWNER'S AND INSURANCE REPRESENTATIVE'S PERMISSION FORANY SERVICE SHUTDOWNS.8.THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,SEQUENCES OF CONSTRUCTION AND THE SAFETY OF WORKMEN.9.PIPING, CONTROLS, ETC., SHALL NOT BE INSTALLED, OR ROUTED ABOVE, ELECTRICALPANELS AND EQUIPMENT OR THROUGH ELEVATOR MACHINE ROOMS.10.THE CONTRACTOR SHALL COORDINATE AND OBTAIN A WRITTEN LISTING OF ELECTRICALCHARACTERISTICS OF MECHANICAL EQUIPMENT FROM ELECTRICAL CONTRACTOR PRIOR TOORDERING OF EQUIPMENT. ADDITIONAL COMPENSATION WILL NOT BE MADE FOR LACK OFCONTRACTOR COORDINATION OF EQUIPMENT ELECTRICAL CHARACTERISTICS.11.DURING THE BUILDING CONSTRUCTION SOME EXISTING INSTALLATION MAY BE EXPOSEDTHAT WILL HAVE TO BE CHANGED, ALTERED, REROUTED AND/OR ABANDONED. ANY SUCHWORK WHICH COMES UNDER THE JURISDICTION OF THIS CONTRACTOR SHALL BE DONE BYTHIS CONTRACTOR WITHOUT ADDITIONAL COST TO THE OWNER.12.WORK RELATED TO THE EXISTING BUILDING SHALL BE COORDINATED TO MINIMIZEINTERFERENCE OR INTERRUPTION OF NORMAL BUILDING USE BY OWNER. REFER TOARCHITECTURAL PLANS AND SPECIFICATIONS FOR PHASING REQUIREMENTS.13.THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTINGCONDITIONS. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING CONDITIONS THAT MAYAFFECT THE BID. ADDITIONAL COMPENSATION WILL NOT BE PROVIDED FOR FAILURE TOREVIEW EXISTING CONDITIONS PRIOR TO BIDDING.B.CODES, PERMITS, STANDARDS AND REGULATIONS1.CONFORM TO APPLICABLE CODES (LOCAL, STATE, NATIONAL CODES, NFPA, OSHA, ETC.),GOVERNMENT REGULATIONS, UTILITY COMPANY REQUIREMENTS, AND APPLICABLESTANDARDS.2.OBTAIN PERMITS AND PAY FEES. ARRANGE FOR ALL REQUIRED TESTS, INSPECTIONS ANDAPPROVALS. PROVIDE COPIES OF INSPECTIONS AND APPROVALS TO THE A/E.C.RELATED WORK SPECIFIED ELSEWHERE1.OPENINGS AND CHASES, WHEN SHOWN ON ARCHITECTURAL DRAWINGS.2.TEMPORARY FIRE PROTECTION.3.POURED-IN-PLACE CONCRETE.4.FINISH PAINTING.5.ELECTRIC POWER WIRING.D.DRAWINGS1.THE SYSTEMS SHOWN ON THE DRAWINGS ARE DIAGRAMMATIC. CONFIRM DIMENSIONS BYFIELD MEASUREMENT.2.THE EXACT LOCATIONS FOR APPARATUS, FIXTURES, EQUIPMENT AND PIPING WHICH IS NOTCOVERED BY DRAWINGS, SHALL BE OBTAINED FROM THE ARCHITECT OR HISREPRESENTATIVE IN THE FIELD, AND THE WORK SHALL BE LAID OUT ACCORDINGLY.3.DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT ONE ANOTHER. ANYMATERIALS OR LABOR CALLED FOR IN ONE BUT NOT THE OTHER SHALL BE PROVIDED.E.DEMOLITION AND REMOVAL1.DISCONNECT, DISASSEMBLE, CAP, PLUG AND REMOVE PIPING, DUCTS AND EQUIPMENTINDICATED ON THE DRAWINGS, AND AS REQUIRED FOR THE PROJECT.2.ANY EQUIPMENT DESIGNATED BY OWNER TO BE SALVAGED SHALL BE PROTECTED ANDDELIVERED TO THE OWNER'S STORAGE.3.DEMOLITION TO BE DONE IN A MANNER NOT TO DAMAGE ADJACENT WORK AND NOTAFFECT THE OPERATION OF SYSTEMS TO REMAIN IN USE. ANY ITEM TO REMAIN THAT ISDAMAGED BY THE CONTRACTOR OR THAT REQUIRES DAMAGE DUE TO THE ABSOLUTENECESSITY FOR DEMOLITION REQUIREMENTS SHALL BE REPLACED AND/OR REPAIRED AT HISEXPENSE.4.OPENINGS ON PIPING AND DUCTS THAT REMAIN SHALL BE CAPPED AND PROPERLYSECURED.5.ASBESTOS REMOVAL WILL BE HANDLED BY THE OWNER AND IS NOT A PART OF THIS WORK.6.EXAMINE AREAS AND CONDITIONS UNDER WHICH DEMOLITION WORK SHALL BE PERFORMED.CONTRACTOR SHALL COORDINATE WORK WITH OTHER DEMOLITION WORK.7.REMOVE SUPPORTS, HANGERS, AND ACCESSORIES FROM EQUIPMENT AND MATERIALINDICATED TO BE REMOVED.F.BASE EQUIPMENT, MATERIALS AND SUBSTITUTIONS1.EQUIPMENT AND MATERIALS SHALL BE NEW, FREE OF DEFECTS AND U.L. LISTED AND F.M.APPROVED IF APPROPRIATE.2.BASE BID MANUFACTURERS ARE INCLUDED IN SPECIFICATIONS OR LISTED IN SCHEDULE ONDRAWINGS. ANY OTHER MANUFACTURER'S ARE CONSIDERED A SUBSTITUTION.3.THE NAME, OR MAKE OF ANY ARTICLE, DEVICE, MATERIAL, FORM OF CONSTRUCTION,FIXTURE, ETC., STATED IN THIS SPECIFICATION, SHALL BE KNOWN AS A "STANDARD".4.PROPOSALS SHALL BE BASED ON "STANDARDS" SPECIFIED.5.THE EQUIPMENT SCHEDULES ON DRAWINGS INDICATE MANUFACTURERS EQUIPMENT MODELNUMBERS UPON WHICH DESIGN HAS BEEN BASED. THE USE OF OTHER MANUFACTURERSEQUIPMENT THAT IS LISTED AS ACCEPTABLE ALTERNATES THAT REQUIRES STRUCTURALCHANGES, CHANGES IN ROOF OPENINGS, CHANGE OF PIPE SIZES & BUILDINGCONFIGURATION, ARCHITECTURAL CHANGES, ETC., SHALL BE THE CONTRACTOR'SRESPONSIBILITY. ADDITIONAL COSTS OF SUCH CHANGES SHALL BE PAID BY THECONTRACTOR SUBMITTING THE ALTERNATES.6.SUBSTITUTIONS ARE SUBJECT TO THE APPROVAL OF THE OWNER. IT SHALL BE THECONTRACTOR'S RESPONSIBILITY TO EVALUATE AND CERTIFY WITH DOCUMENTATION THATTHE SUBSTITUTION IS EQUIVALENT IN ALL RESPECTS TO THE BASE SPECIFICATIONS.7.IF SUBSTITUTIONS ARE APPROVED, NOTIFY ALL OTHER CONTRACTORS, SUBCONTRACTORSOR TRADES AFFECTED BY SUBSTITUTION AND FULLY COORDINATE. ANY COSTS RESULTINGFROM SUBSTITUTION, WHETHER BY CONTRACTOR OR OTHERS, SHALL BE RESPONSIBILITY OF,AND PAID FOR BY SUBSTITUTING CONTRACTOR. APPROVED SHOP DRAWINGS DOES NOTABSOLVE THIS CONTRACTOR FROM THIS RESPONSIBILITY.8.EQUIPMENT SHALL BE INSTALLED IN FULL ACCORDANCE WITH THE MANUFACTURER'S DATAAND INSTALLATION INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TOCHECK AND CONFORM TO THESE REQUIREMENTS.G.CHECK, TEST, START, ADJUST, BALANCE AND INSTRUCTIONS1.AFTER INSTALLATION, CHECK ALL EQUIPMENT, AND PERFORM START UP IN ACCORDANCEWITH THE MANUFACTURER'S INSTRUCTIONS, AND REQUIREMENTS OF THE SPECIFICATIONS.2.PIPING SHALL BE TESTED AND FREE OF LEAKS. MAKE REPAIRS NEEDED FOR A LEAK FREESYSTEM.3.CONCEALED OR INSULATED WORK SHALL REMAIN UNCOVERED UNTIL REQUIREDINSPECTIONS, AND TESTS HAVE BEEN COMPLETED. IF CONSTRUCTION SCHEDULEREQUIRES IT, ARRANGE FOR TESTS ON PARTS OF SYSTEM AS REQUIRED.4.INSTRUCT OWNER IN OPERATION OF SYSTEMS AND SUBMIT OPERATING AND MAINTENANCEMANUAL ON EQUIPMENT AND SYSTEMS AS REQUIRED BY THE SPECIFICATIONS. PROVIDE AMINIMUM OF 16 HOURS OF INSTRUCTION TO OWNER'S REPRESENTATIVE.H.CUTTING, PATCHING AND DRILLING1.CUTTING AND PATCHING OF THE BUILDING CONSTRUCTION REQUIRED FOR THIS WORK SHALLBE BY THIS CONTRACTOR. CUTTING SHALL BE IN A NEAT AND WORKMANLIKE MANNER.2.NEATLY SAW CUT RECTANGULAR OPENINGS, SET SLEEVE THROUGH OPENING, AND FINISHPATCH OR PROVIDE TRIM FLANGE AROUND OPENING.3.CORE DRILL AND SLEEVE ROUND OPENINGS.4.DO NOT CUT ANY STRUCTURAL COMPONENTS WITHOUT ARCHITECT'S/ENGINEER'SAPPROVAL.5.PATCH AND FINISH TO MATCH ADJACENT AREAS THAT HAVE BEEN CUT, DAMAGED ORMODIFIED AS A RESULT OF THE INSTALLATION OF THE MECHANICAL OR ELECTRICALEQUIPMENT. FIRE STOP PENETRATIONS OF FIRE RATED CONSTRUCTION IN A CODEAPPROVED MANNER, AND MAINTAIN FIRE RATING OF ASSEMBLY.6.CONTRACTORS SHALL CONFIRM WITH OWNER/ARCHITECT, PRIOR TO BID, TIMES AVAILABLEFOR NOISE PRODUCING WORK SUCH AS CUTTING AND CORE DRILLING OF FLOORS, WALLS,ETC., AS WELL AS TIMES FOR WORK WHICH REQUIRE ACCESS INTO ADJOINING TENANTSPACES. INCLUDE PREMIUM TIME IN BID.7.INFORMATION REGARDING REQUIRED PIPE OPENINGS IN WALLS, FLOORS, CHASES, ETC.,AND CONCRETE EQUIPMENT PADS OR FOUNDATIONS SHALL BE GIVEN TO THE GENERALCONTRACTOR BY THIS CONTRACTOR PRIOR TO THE CONSTRUCTION PERIOD. IF THISCONTRACTOR FAILS TO COMPLY WITH THIS REQUEST, OR IF INCORRECT INFORMATION ISGIVEN, THE NECESSARY CUTTING AND PATCHING WILL BE PERFORMED BY THE GENERALCONTRACTOR, AT THIS CONTRACTOR'S EXPENSE.I.WARRANTY1.FULLY WARRANT MATERIALS, EQUIPMENT AND WORKMANSHIP FOR ONE (1) YEAR FROMDATE OF ACCEPTANCE.2.PROVIDE MANUFACTURER'S WARRANTIES TO OWNER, INCLUDING EXTENDED WARRANTIES.3.REPAIR OR REPLACE WITHOUT CHARGE TO THE OWNER ITEMS FOUND DEFECTIVE DURINGTHE WARRANTY PERIOD. IN THE CASE OF REPLACEMENT OR REPAIR DUE TO FAILURE WITHINTHE WARRANTY PERIOD, THE WARRANTY ON THAT PORTION OF THE WORK SHALL BEEXTENDED FOR A MINIMUM PERIOD OF ONE (1) YEAR FROM THE DATE OF SUCHREPLACEMENT OR REPAIR.J.SHOP DRAWING SUBMITTALS1.SUBMIT SHOP DRAWINGS FOR MECHANICAL EQUIPMENT, FIRE PROTECTION SYSTEMS,DUCTWORK, AND PLUMBING FIXTURES AND EQUIPMENT WITH ADEQUATE DETAILS ANDSCALES TO CLEARLY SHOW CONSTRUCTION. INDICATE THE OPERATING CHARACTERISTICSFOR EACH REQUIRED ITEM. CLEARLY IDENTIFY EACH ITEM ON THE SUBMITTAL AS TO MARK,LOCATION AND USE, USING SAME IDENTIFICATION AS PROVIDED ON DESIGN DRAWINGS.SUBMITTALS WITH MULTIPLE ITEMS MUST BE MARKED FOR PROPOSED ITEM OR SUBMITTALWILL BE REJECTED.2.FIRE PROTECTION DRAWINGS SHALL BE FULLY DIMENSIONED BASED ON FIELD VERIFIEDBUILDING CLEARANCES AND ARCHITECTURAL CEILING LAYOUTS. INDICATE STRUCTURAL,LIGHTING, DUCTWORK AND PIPING AT ALL CRITICAL LOCATIONS.3.CONTRACTOR SHALL REVIEW AND INDICATE HIS APPROVAL OF EACH SHOP DRAWING PRIORTO SUBMITTAL FOR REVIEW. DO NOT START WORK OR FABRICATION UNTIL SHOP DRAWINGSHAVE BEEN REVIEWED AND APPROVED BY THE ENGINEER AND RETURNED TO THECONTRACTOR.4.SUBMITTALS SHALL BE REVIEWED ONLY FOR GENERAL COMPLIANCE WITH THE CONTRACTDOCUMENTS AND NOT FOR DIMENSIONS OR QUANTITIES. THE SUBMITTAL REVIEW SHALLNOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR PURCHASE OF ANY ITEM IN FULLCOMPLIANCE WITH THE CONTRACT DOCUMENTS OR ITS COMPLETE AND PROPERINSTALLATION.5.WHERE SUBMITTALS VARY FROM THE CONTRACT REQUIREMENTS, THE CONTRACTOR SHALLCLEARLY INDICATE ON SUBMITTAL OR ACCOMPANYING DOCUMENTS THE NATURE ANDREASON FOR VARIATIONS.6.REFER TO VARIOUS SECTIONS FOR LISTING OF SHOP DRAWINGS REQUIRED ON THISPROJECT.7.EACH MANUFACTURER OR HIS REPRESENTATIVE SHALL CHECK THE APPLICATION OF HISEQUIPMENT AND CERTIFY AT TIME OF SHOP DRAWING SUBMITTAL THAT EQUIPMENT HASBEEN PROPERLY SELECTED AND CAN BE INSTALLED, SERVICED AND MAINTAINED WHEREINDICATED ON DRAWINGS. ADVISE ENGINEER IN WRITING WITH SUBMITTAL DRAWINGS OFANY POTENTIAL PROBLEMS. THE MANUFACTURER SHALL BE RESPONSIBLE FOR ANYCHANGES THAT MIGHT BE NECESSARY BECAUSE OF PHYSICAL CHARACTERISTICS OFEQUIPMENT THAT HAVE NOT BEEN CALLED TO THE ENGINEER'S ATTENTION AT THE TIME OFSUBMITTAL.8.FIRE PROTECTION SUBMITTAL SHALL BE SUBMITTED AS A COMPLETE PACKAGE CONSISTINGOF PRODUCT CUT SHEETS, DRAWING AND CALCULATIONS. INCOMPLETE PACKAGE WILL BEREJECTED.K.RECORD DRAWINGS1.EACH CONTRACTOR OR SUBCONTRACTOR SHALL KEEP ONE (1) COMPLETE SET OF THECONTRACT WORKING DRAWINGS ON THE JOB SITE, THE CONTRACTOR SHALL REGULARLYRECORD ANY DEVIATIONS, AND/OR CHANGES FROM CONTRACT DRAWINGS MADE DURINGCONSTRUCTION.2.THESE DRAWINGS SHALL RECORD THE LOCATION OF EQUIPMENT, PIPING, ELECTRIC SERVICE,SEWERS, WASTES, VENTS, DUCTS, CONDUIT AND OTHER PIPING, BY MEASUREDDIMENSIONS TO EACH SUCH ITEM FROM READILY IDENTIFIABLE AND ACCESSIBLE WALLS ORCORNERS OF THE BUILDING. PLANS ALSO SHALL SHOW INVERT ELEVATION OF SANITARY,AND/OR STORM SEWERS AND TOP ELEVATION OF OTHER BELOW-GRADE LINES.3.RECORD DRAWINGS SHALL BE KEPT CLEAN AND UNDAMAGED AND SHALL NOT BE USEDFOR ANY PURPOSE OTHER THAN RECORDING DEVIATIONS FROM WORKING DRAWINGS ANDEXACT LOCATIONS OF CONCEALED WORK.4.AFTER THE PROJECT IS COMPLETED, THESE SETS OF DRAWINGS SHALL BE DELIVERED TOTHE ARCHITECT IN GOOD CONDITION, AS A PERMANENT RECORD OF THE INSTALLATION.FIRE PROTECTION SPRINKLER SYSTEMA.SCOPE1.FURNISH LABOR, MATERIALS AND EQUIPMENT AS REQUIRED TO INSTALL COMPLETE FIREPROTECTION SYSTEMS FOR PROJECT. SPRINKLER SYSTEM DESIGN AND HYDRAULICCALCULATIONS SHALL BE PROVIDED WITH THIRD PARTY PROFESSIONAL ENGINEERS STAMP.2.SPRINKLER WORK FOR PROJECT ESSENTIALLY CONSISTS OF, BUT NOT LIMITED TO, THEFOLLOWING:a.FIRE PROTECTION SERVICE MAIN EXTENDED FROM STREET MAIN INTO BUILDING,INCLUDING TAP TO MAIN, VAULT WITH DOUBLE DETECTOR CHECK VALVE, BACKFLOWPREVENTER AND VALVES, FIRE DEPARTMENT CONNECTION, SITE OR WALL POSTINDICATOR VALVE, AND ALARM CHECK VALVE INSIDE BUILDING WITH WATER MOTORALARM.a.COMBINATION DOMESTIC/FIRE PROTECTION SERVICE MAIN EXTENDED FROM STREETMAIN INTO BUILDING, INCLUDING TAP TO MAIN, METER VAULT, FIRE DEPARTMENTCONNECTION, WALL POST INDICATOR VALVE, BACKFLOW PREVENTER, AND ALARMCHECK VALVE INSIDE BUILDING WITH WATER MOTOR ALARM.a.FIRE PROTECTION SERVICE EXTENDED FROM FLANGED CONNECTION ABOVE FINISHEDFLOOR TO SYSTEM, INCLUDING FIRE DEPARTMENT CONNECTION, WALL POSTINDICATOR VALVE, DOUBLE DETECTOR CHECK VALVE BACKFLOW PREVENTER, ANDALARM CHECK VALVE WITH WATER MOTOR ALARM.a.MODIFY EXISTING WET PIPE SPRINKLER SYSTEM AS REQUIRED TO CONFORM TO NEWCEILING AND/OR WALL LAYOUT, AND NEW SYSTEMS.a.LIMITED AREA SPRINKLER SYSTEM EXTENDED FROM THE DOMESTIC WATER SYSTEM,AS REQUIRED TO CONFORM TO NFPA AND LOCAL AUTHORITY HAVING JURISDICTION.a.EXTEND WET SPRINKLER SYSTEM FOR NEW OR REMODELED AREAS FROM EXISTINGSYSTEM IN BUILDING.a.WET SPRINKLER SYSTEM FOR NEW BUILDING.b.PREPARE SUBMITTAL DRAWINGS AND HYDRAULIC CALCULATIONS AS REQUIRED FORAPPROVAL BY OWNER'S INSURANCE COMPANY, BUILDING DEPARTMENT, LOCALAUTHORITY HAVING JURISDICTION AND NFPA REQUIREMENTS. COMPLY WITH NFPA-13REQUIREMENTS FOR PREPARATION OF DRAWINGS AND CALCULATIONS.c.FLUSH AND CONDUCT PRESSURE TEST OF COMPLETED SYSTEM IN ACCORDANCEWITH NFPA AND AUTHORITIES HAVING JURISDICTION. DELIVER ALL CERTIFICATES TOOWNER.d.OTHER ITEMS INDICATED ON DRAWINGS OR REQUIRED FOR COMPLETE INSTALLATIONAND TO SATISFY ALL CODE REQUIREMENTS.g.PIPING SHALL NOT BE INSTALLED AT LOCATIONS SUBJECT TO FREEZING, UNLESSPROVIDED AS DRY PIPE SYSTEM, OR ANTI-FREEZE SYSTEM. PROVIDE FIRE WATCH.B.DESIGN BASIS1.DESIGN BASIS FOR SYSTEM SHALL BE PER NFPA 13, LIFE SAFETY CODE 101 IN ACCORDANCEWITH CODE AND LOCAL AUTHORITY HAVING JURISDICTION. SYSTEM SHALL BE AHYDRAULICALLY DESIGNED.2.PIPE SIZES INDICATED ON DRAWING ARE APPROXIMATE AND SHALL BE VERIFIED BYCONTRACTORS HYDRAULIC DESIGN.3.STANDARD-PRESSURE PIPING SYSTEM COMPONENT: LISTED FOR 175-PSIG MAXIMUMWORKING PRESSURE.4.SPRINKLER SYSTEM DESIGN SHALL BE APPROVED BY AUTHORITIES HAVING JURISDICTION,AND OWNER'S INSURANCE UNDERWRITER. PRIOR TO START OF CONSTRUCTION.5.PROVIDE MARGIN OF SAFETY FOR AVAILABLE WATER FLOW AND PRESSURE AND 10PERCENT.6.SPRINKLER OCCUPANCY HAZARD CLASSIFICATIONS:a.ELECTRICAL EQUIPMENT ROOMS: ORDINARY HAZARD, GROUP 1.b.GENERAL STORAGE AREAS: ORDINARY HAZARD, GROUP 1.c.MECHANICAL EQUIPMENT ROOMS: ORDINARY HAZARD, GROUP 1.d.OFFICE AND PUBLIC AREAS: LIGHT HAZARD.7.MINIMUM DENSITY FOR AUTOMATIC-SPRINKLER PIPING DESIGN:a.LIGHT-HAZARD OCCUPANCY: 0.10 GPM OVER 1500-SQ. FT. AREA.b.ORDINARY-HAZARD, GROUP 1 OCCUPANCY: 0.15 GPM OVER 1500-SQ. FT. AREA.c.SPECIAL OCCUPANCY HAZARD: AS DETERMINED BY AUTHORITIES HAVINGJURISDICTION.8.MAXIMUM PROTECTION AREA PER SPRINKLER:a.OFFICE AND PUBLIC SPACES: 225 SQ. FT. (20.9 SQ. M)b.STORAGE AREAS: 130 SQ. FT.c.MECHANICAL EQUIPMENT ROOMS: 130 SQ. FT.d.ELECTRICAL EQUIPMENT ROOMS: 130 SQ. FT.e.OTHER AREAS: ACCORDING TO NFPA 13 RECOMMENDATIONS UNLESS OTHERWISEINDICATED.9.TOTAL COMBINED HOSE-STREAM DEMAND REQUIREMENT: ACCORDING TO NFPA 13 UNLESSOTHERWISE INDICATED:a.LIGHT-HAZARD OCCUPANCIES: 100 GPM (6.3 L/S) FOR 30 MINUTES.b.ORDINARY-HAZARD OCCUPANCIES: 250 GPM (15.75 L/S) FOR 60 TO 90 MINUTES.C.DRAWINGS AND CALCULATIONS1.CONTRACTOR SHALL PREPARE SUBMITTAL DRAWING AND HYDRAULIC CALCULATIONS FORSPACE IN ACCORDANCE WITH OWNER'S INSURANCE COMPANY AND BUILDING DEPARTMENTREQUIREMENTS. DRAWINGS AND CALCULATIONS SHALL BE PERFORMED BY A REGISTEREDPROFESSIONAL ENGINEER. PROVIDE PROFESSIONAL ENGINEERS STAMP AND SIGNATUREON DRAWINGS AND HYDRAULIC CALCULATIONS.2.CONTRACTOR SHALL OBTAIN FLOW TEST DATA ON CITY WATER MAIN AND SUBMIT DATAWITH CALCULATIONS. PERFORM FLOW TEST IF DATA IS OLDER THAN ONE YEAR.3.PROVIDE WET STANDPIPE SYSTEM FOR PROJECT IN ACCORDANCE WITH NFPA 14REQUIREMENTS, AND AUTHORITY HAVING JURISDICTION.4.CONTRACTOR AND DESIGNER SHALL BE STATE AND LOCAL CERTIFIED. DESIGNER SHALL BEMINIMUM LEVEL 3 NICET CERTIFIED. CONTRACTOR DRAWINGS AND CALCULATIONS SHALL BEREVIEWED AND STAMPED BY REGISTERED ENGINEER.D.PIPING4.PIPING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 13 REQUIREMENTS.5.FIRE PROTECTION PIPING SHALL BE AS FOLLOWS:c.INSIDE BUILDING:- 2 INCH AND SMALLER: THREADED-END, SCHEDULE 40 STEEL PIPE; CAST- ORMALLEABLE-IRON THREADED FITTINGS; AND THREADED JOINTS.- 2 1/2 INCH AND LARGER: GROOVED-END, SCHEDULE 10 STEEL PIPE;GROOVED-END FITTINGS; GROOVED-END-PIPE COUPLINGS; AND GROOVEDJOINTS.d.INSTALL STANDPIPES WHERE INDICATED ON DRAWINGS, INCLUDING SUPERVISEDISOLATION VALVE, AND WATERFLOW SWITCH AT BASE OF RISER. PROVIDE FIREDEPARTMENT VALVE WITH CAP AND CHAIN AT EACH FLOOR.e.PROVIDE GALVANIZED PIPING AND FITTINGS FOR DRY FIRE PROTECTION SYSTEM.f.CONTRACTOR SHALL ARRANGE FOR SHUTDOWN OF EXISTING SYSTEM WITHLANDLORD, OWNER MAINTENANCE AND FIRE ALARM PERSONNEL, AND INSURANCEUNDERWRITER. PROVIDE FIRE WATCH WHILE SYSTEM IS SHUT DOWN.g.FLUSH PIPING UPON COMPLETION OF PROJECT AND TEST PER NFPA 13.h.INSTALL INSPECTOR'S TEST CONNECTION WITH DRAIN VALVE AND TERMINATE DRAINTHROUGH EXTERIOR WALL WITH GALVANIZED PIPE, TEST FITTING AND SPLASH BLOCK.i.SYSTEMS REQUIRING GALVANIZED PIPING SHALL BE PROVIDED WITH SCREWEDFITTINGS, AND UNIONS.F.SPRINKLERS1.SPRINKLERS SHALL BE AS SCHEDULED ON DRAWINGS.2.SPRINKLERS SHALL MATCH EXISTING BASE BUILDING STANDARDS.3.BASIS-OF-DESIGN PRODUCT: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE THEPRODUCT INDICATED IN SPECIFICATION OR A COMPARABLE PRODUCT BY ONE OF THEFOLLOWING MANUFACTURERS:a.VIKING CORPORATIONb.VICTAULIC CO.c.TYCO4.INSTALL HIGHER TEMPERATURE SPRINKLER HEADS AS REQUIRED BY CODE OR APPLICATION.5.SUBMIT SAMPLES OF SPRINKLERS TO ARCHITECT PRIOR TO FABRICATION OF ANY PIPING.G.PRESSURE GAUGES1.PRESSURE GAUGES SHALL BE UL LISTED, 3-1/2- TO 4-1/2-INCH DIAMETER, DIAL PRESSUREGAGE WITH RANGE OF 0 TO 250 PSIG MINIMUM.a.WATER SYSTEM PIPING: INCLUDE CAPTION "WATER" OR "AIR/WATER" ON DIAL FACE.b.AIR SYSTEM PIPING: INCLUDE CAPTION "AIR" OR "AIR/WATER" ON DIAL FACE.I.HANGERS AND SUPPORTS1.HANGERS FOR BLACK OR GALVANIZED STEEL PIPE SHALL BE MANUFACTURED BY MICHIGANHANGER CO., MODEL NO. 100, OR APPROVED EQUAL.2.HANGERS FOR COPPER TUBING SHALL BE MANUFACTURED BY MICHIGAN HANGER CO.,MODEL NO. 102-A, OR APPROVED EQUAL.3.TRAPEZE HANGERS OF A TYPE APPROVED BY THE ENGINEER MAY BE USED WHERE PIPESARE DESIGNED TO RUN PARALLEL AND AT THE SAME ELEVATION.4.STRAP HANGERS SHALL NOT BE PERMITTED.5.CONTRACTOR SHALL PROVIDE RISER CLAMPS FOR VERTICAL PIPING AT EACH LEVEL. RISERCLAPS SHALL BE MICHIGAN HANGER CO., MODEL NO. 510 FOR STEEL PIPING AND MODELNO. 511 FOR COPPER TUBING OR APPROVED EQUAL. USE “SHORT-END“ RISER CLAMPSWHERE SPACE IS LIMITED.6.IN CONCRETE, MICHIGAN HANGER CO., MODEL NO. 355 INSERTS, OR APPROVED EQUAL.INSERTS SHALL PERMIT ADJUSTMENT FROM 3/4 INCH THROUGH 1-1/4 INCH. IN METAL DECKS,CONTRACTOR SHALL PROVIDE REDHEAD SDI INSERTS, OR APPROVED EQUAL. POWDERPROPELLED INSERTS WILL BE PERMITTED IN NEW CONSTRUCTION WHERE TYPE ANDLOCATION ARE APPROVED BY THE ENGINEER PRIOR TO INSTALLATION.7.CONTRACTOR SHALL PROVIDE SIDE BEAM CLAMPS FOR SUPPORTING PIPING FROMSTRUCTURAL STEEL MEMBERS. BEAM CLAMPS SHALL BE MANUFACTURED BY MICHIGANHANGER CO., MODEL 300 OR APPROVED EQUAL.8.WHERE OTHER MEANS OF SUPPORT PIPING ARE REQUIRED OR DESIRED, THE CONTRACTORSHALL BE RESPONSIBLE FOR OBTAINING THE ENGINEER'S APPROVAL PRIOR TO INSTALLINGTHOSE SUPPORTS.9.HANGER SHALL BE PROVIDED AT EACH CHANGE OF DIRECTION.10.HANGERS AND SUPPORTS SHALL BE SPACED AT INTERVALS WHICH WILL PREVENTSAGGING AND REDUCE STRAIN ON VALVES AND SPECIALTIES. HANGER SPACING SHALL BENO GREATER AND ROD SIZE SHALL BE NO SMALLER THAN THAT SHOWN IN THE FOLLOWINGTABLE. HANGERS SHALL ALLOW FOR EXPANSION AND CONTRACTION. HANGERS ANDSUPPORTS MUST COMPLY WITH NFPA-13 REQUIREMENTS.FERROUS PIPING AND COPPER TUBING:DIAMETER OF PIPE MAXIMUM SPACINGROD SIZEUP TO 1"8 FT.3/8"1-1/4" T0 1-1/2"10 FT3/8"2" THRU 3"12 FT3/8"4" AND 5"15 FT1/2"6" AND LARGER15 FT5/8"J.VALVES1.BASIS-OF-DESIGN PRODUCT: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE THEPRODUCT INDICATED IN SPECIFICATION OR A COMPARABLE PRODUCT BY ONE OF THEFOLLOWING MANUFACTURERS:a.VIKING CORPORATIONb.VICTAULIC CO.c.NIBCOd.APOLLO2.INSTALL VALVES AND TRIM AS REQUIRED BY NFPA 13, "UL" LISTED AND "FM" APPROVED.3.SHUT-OFF VALVES SHALL BE FITTED WITH TAMPER SWITCHES BY FIRE PROTECTIONCONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR. COORDINATE LOCATIONS WITHELECTRICAL CONTRACTOR.4.PROVIDE FLOW SWITCH IN RISER COORDINATE WITH ELECTRICAL CONTRACTOR.5.INSTALL WALL/SITE POST INDICATOR VALVE, AS INDICATED ON DRAWINGS AND REQUIREDBY LOCAL AUTHORITY HAVING JURISDICTION.6.BALL VALVES:a. 2-INCHES AND SMALLER: SHALL BE RATED FOR A MINIMUM OF 400 PSI WOG, VALVEBODY CONSTRUCTED OF BRONZE, 2-PIECE BODY, STANDARD PORT, WITH TEFLONSEATS AND SEALS, AND BLOW-OUT PROOF STEMS. VALVES SHALL HAVE LOCKABLEHANDLES AND SHALL BE UL LISTED AND FM APPROVED. THEY SHALL HAVETHREADED ENDS FOR USE IN STEEL PIPING. BALL VALVES SHALL BE VICTAULICSERIES 722. VALVES SHALL BE PROVIDED WITH TAMPERPROOF SWITCHES.7.BUTTERFLY VALVES:a.2-INCHES TO 8-INCHES: SHALL BE RATED FOR A MINIMUM OF 300 PSI FIREPROTECTION SERVICE, FACTORY COATED DUCTILE IRON BODY WITH GROOVED ENDSAND NICKEL COATED DUCTILE IRON DISC WITH NITRILE SEATS. VALVES SHALL BE ULLISTED AND FM APPROVED. PROVIDE VALVE WITH FACTORY MOUNTED ACTUATORWITH INDICATOR FLAGS AND SUPERVISORY SWITCH. VALVES SHALL BE VICTAULICSERIES 705W. VALVES SHALL BE PROVIDED WITH TAMPERPROOF SWITCHES.8.OS&Y GATE VALVES WITH TAMPER SWITCH:a.2 1/2-INCHES TO 12-INCHES: SHALL BE RATED FOR A MINIMUM OF 250 PSI FIREPROTECTION SERVICE, FACTORY COATED DUCTILE IRON BODY WITH GROOVED ENDSAND EPDM COATED CAST IRON DISC. VALVES SHALL SEAL IN OPEN POSITION.VALVES SHALL BE UL LISTED AND FM APPROVED. PROVIDE VALVE WITH STEMMOUNTED SUPERVISORY SWITCH FROM POTTER ROEMER MODEL 6220. VALVESSHALL BE VICTAULIC SERIES 771H.9.CHECK VALVES:a.2-INCHES AND LARGER: SHALL BE RATED FOR A MINIMUM OF 250 PSI FIREPROTECTION SERVICE, FACTORY COATED DUCTILE IRON BODY WITH GROOVED ENDSAND ELASTOMER-COATED DUCTILE IRON DISC. VALVES SHALL BE INSTALLEDHORIZONTAL AND VERTICAL POSITIONS. VALVES SHALL BE UL LISTED AND FMAPPROVED. VALVES SHALL BE VICTAULIC VALVE SERIES 717.10.PROVIDE VALVE TAGS AND VALVE CHART PER ASME A13.1 SCHEME FOR THE IDENTIFICATIONOF PIPING SYSTEMS. PROVIDE BUILDING PLAN SHOWING LOCATIONS OF VALVES.L.PIPE IDENTIFICATION1.CONTRACTOR SHALL PROVIDE IDENTIFICATION LABELS, TAGS, ETC., FOR FIRE PROTECTIONPIPING AS INDICATED ON THE DRAWINGS AND AS SPECIFIED HEREIN.2.THE IDENTIFICATION OF PLUMBING PIPING SHALL BE IN ACCORDANCE WITH ANSI STANDARDA13.1.3.PRESSURE SENSITIVE PIPE MARKERS SHALL BE MANUFACTURED BY THE BRADY CO., ORAPPROVED EQUAL. PIPE MARKERS SHALL BE MANUFACTURER'S STANDARD PRODUCT.M.ACCESS DOORS1.ACCESS DOORS SHALL BE PROVIDED IN WALLS AND CEILINGS WHERE REQUIRED TO PERMITPROPER ACCESS TO VALVES AND ANY OTHER SUCH DEVICES WHICH REQUIREMAINTENANCE OR SERVICE. DOORS PLACED IN WALLS, PARTITIONS OR OTHER FIRE-RATEDCONSTRUCTION SHALL HAVE A LABEL SIGNIFYING THAT THE DOOR HAS THE SAME FIRERATING AS THE FIRE-RATED CONSTRUCTION.2.THIS CONTRACTOR SHALL FURNISH ACCESS PANELS TO THE GENERAL CONTRACTOR FORINSTALLATION.3.ACCESS PANELS SHALL BE CONSTRUCTED OF 14 GAUGE STEEL, WITH 16 GAUGE STEELFRAMES. DOORS SHALL FINISH FLUSH WITH THE SURROUNDING SURFACE. FRAMES SHALLHAVE 3 INCH WIDE EXPANDED METAL FOR PLASTERED SURFACES AND PLAIN FLANGEDTYPE FRAME FOR TILE, MASONRY OR GYPSUM BOARD SURFACES. DOORS AND FRAMESSHALL BE FURNISHED PRIME COATED. DOORS INSTALLED IN CERAMIC TILE OR OTHERNON-PAINTED SURFACES SHALL BE STAINLESS STEEL.4.HINGES SHALL BE CONCEALED SPRING TYPE, TO ALLOW DOORS TO BE OPENED 175DEGREES. LOCKS SHALL BE FLUSH SCREWDRIVER TYPE WITH STEEL CAMS.5.ACCESS PANELS SHALL BE 16 INCHES BY 16 INCHES OR LARGER AS MAY BE REQUIRED FORPROPER ACCESS TO THE DEVICE BEING SERVED.6.ACCESS PANELS ARE NOT REQUIRED IN COMPLETELY ACCESSIBLE LIFT OUT TILE CEILINGS.CONTRACTOR SHALL REVIEW THE ROOM FINISH SCHEDULE ON THE ARCHITECTURALDRAWINGS TO VERIFY THE NEED FOR ACCESS PANELS.N.FIRESTOPPING1.SERVICES THAT PASS THRU FIRE OR SMOKE RATED PARTITIONS, WALLS, FLOORS, SHALL BEFIRESTOPPED. FIRE STOPPING SYSTEM RATING SHALL MATCH PARTITION RATING. FIRESTOPPING SYSTEM SHALL MEET THE REQUIREMENTS OF BUILDING CODE.2.FIRESTOPING AND/OR SMOKE STOPPING MATERIAL AND INSTALLATION SHALL BE ASMANUFACTURED BY HILTI OR APPROVED EQUAL.END OF FIRE PROTECTION SPECIFICATIONS