HomeMy WebLinkAboutM002 - Mechanical SpecificationsMECHANICAL SPECIFICATIONSMECHANICAL GENERAL CONDITIONS (230010)A.GENERAL1.CONFORM TO ALL GENERAL AND SPECIAL CONDITIONS OF CONTRACT AS SPECIFIED BY ARCHITECT AND/OR OWNER.2.PRODUCTS AND INSTALLATION SHALL COMPLY WITH ALL APPLICABLE LAWS, CODES, GOVERNMENT REGULATIONS, UTILITY COMPANYREQUIREMENTS, ETC. OF ALL AUTHORITIES HAVING JURISDICTION. WORK SHALL COMPLY WITH THE FOLLOWING CODES, STANDARDS ANDORGANIZATIONS: INTERNATIONAL MECHANICAL CODE (IMC), INTERNATIONAL PLUMBING CODE (IPC), INTERNATIONAL ENERGY CODE, NATIONALELECTRIC CODE, NFPA, UNDERWRITERS LABORATORY (UL), IRI, FM, SMACNA “HVAC DUCT CONSTRUCTION STANDARDS” GUIDELINES, DETAILS,& MODEL SPECIFICATION, ASHRAE. WHERE CONFLICTS EXIST BETWEEN CODES, STANDARDS OR THIS SPECIFICATION THE HIGHERREQUIREMENT SHALL APPLY. DEVIATIONS FROM THE CONTRACT DOCUMENTS REQUIRED BY THE ABOVE AUTHORITIES SHALL BE SUBMITTED TOTHE ENGINEER FOR REVIEW. OBTAIN PERMITS AND PAY ALL FEES. ARRANGE FOR ALL REQUIRED INSPECTIONS AND APPROVALS. CONFIRMALL UTILITY COMPANY REQUIREMENTS AND CONNECTION POINTS IN FIELD, PRIOR TO STARTING WORK.3.ALL SPECIFICATIONS AND DRAWINGS, I.E., ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL ARE COMPLIMENTARY AND MUST BEUSED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.  ANY INFORMATION CONFLICTS WITHIN THE SPECIFICATIONS ANDDRAWINGS SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION. DRAWINGS ARE DIAGRAMMATIC.  CONFIRM ALL DIMENSIONS BY FIELDMEASUREMENT.  THE EXACT LOCATIONS FOR APPARATUS, FIXTURES, EQUIPMENT AND PIPING WHICH IS NOT COVERED BY DRAWINGS, SHALLBE OBTAINED FROM THE ARCHITECT OR HIS REPRESENTATIVE IN THE FIELD, AND THE WORK SHALL BE LAID OUT ACCORDINGLY.4.VISIT SITE, CHECK FACILITIES AND CONDITIONS MAKE ALL NECESSARY OBSERVATIONS, MEASUREMENTS, NOTE CONDITIONS UNDER WHICHWORK IS TO BE PERFORMED, AND TAKE ALL ITEMS INTO CONSIDERATION IN BID.5.EACH CONTRACTOR SHALL PROVIDE FOR HIS OWN CLEAN-UP, REMOVAL AND LEGAL DISPOSAL OF ALL RUBBISH DAILY. CONTRACTOR SHALLPROTECT THEIR WORK AND EXISTING OR ADJACENT PROPERTY AGAINST WEATHER, TO MAINTAIN THEIR WORK, MATERIALS, APPARATUS ANDFIXTURES FREE FROM INJURY OR DAMAGE. ANY WORK DAMAGED BY FAILURE TO PROVIDE PROTECTION REQUIRED, SHALL BE REMOVED ANDREPLACED WITH NEW WORK AT THE CONTRACTOR'S EXPENSE.6.THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, SEQUENCES OF CONSTRUCTION AND THE SAFETYOF WORKMEN.7.NO PIPING, DUCTWORK, CONTROLS, ETC., SHALL BE INSTALLED OR ROUTED ABOVE ELECTRICAL PANELS AND EQUIPMENT OR THROUGHELEVATOR ROOMS.8.THE CONTRACTOR SHALL COORDINATE AND OBTAIN A WRITTEN LISTING OF ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL EQUIPMENTFROM ELECTRICAL CONTRACTOR PRIOR TO ORDERING OF EQUIPMENT. NO ADDITIONAL PAYMENT WILL BE MADE FOR LACK OF CONTRACTORCOORDINATION OF ELECTRICAL CHARACTERISTICS.9.DURING THE BUILDING CONSTRUCTION SOME EXISTING INSTALLATION MAY BE EXPOSED THAT WILL HAVE TO BE CHANGED, ALTERED,REROUTED AND/OR ABANDONED. ANY SUCH WORK WHICH COMES UNDER THE JURISDICTION OF THIS CONTRACTOR SHALL BE DONE BY THISCONTRACTOR WITHOUT EXTRA COST TO THE OWNER, AS THOUGH FULLY DETAILED ON PLANS AND/OR DESCRIBED IN THE SPECIFICATIONS.10.WORK RELATED TO THE EXISTING BUILDING SHALL BE COORDINATED TO MINIMIZE INTERFERENCE OR INTERRUPTION OF NORMAL BUILDING USEBY OWNER. REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS.11.IN CASES OF DOUBT AS TO THE WORK INTENDED, OR IN THE EVENT OF NEED FOR EXPLANATION THEREOF, THE CONTRACTOR SHALL REQUESTSUPPLEMENTARY INSTRUCTIONS FROM THE ENGINEER.  NO CHANGES ARE TO BE MADE TO THE WORK OF THIS CONTRACT WITHOUT PRIORKNOWLEDGE AND APPROVAL OF THE ENGINEER.  THE CONTRACTOR SHALL HOLD THE OWNER AND ITS CONSULTANTS HARMLESS AGAINSTALL CLAIMS AND JUDGMENTS ARISING OUT OF THE CONTRACTORS PERFORMANCE OF THE WORK OF THIS CONTRACT.  THE CONTRACTORSHALL NOT PROCEED WITH ANY WORK, WHICH HE EXPECTS ADDITIONAL COMPENSATION BEYOND THE CONTRACT AMOUNT, WITHOUT WRITTENAUTHORIZATION FROM THE APPROPRIATE AUTHORITY.  FAILURE TO OBTAIN SUCH AUTHORIZATION SHALL INVALIDATE ANY CLAIM FOR EXTRACOMPENSATION.12.IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO INSTALL THE HEATING, VENTILATION AND AIR CONDITIONING SYSTEM SO AS TOINSURE QUIET OPERATION.  NO VIBRATION OR SOUND SHALL BE TRANSMITTED TO THE BUILDING, STRUCTURE OR OCCUPIED AREAS.  THEDECISION OF THE ENGINEER AS TO THE QUIETNESS OF THE SYSTEM AND EQUIPMENT SHALL BE FINAL.  IT SHALL BE THIS CONTRACTORSRESPONSIBILITY TO CORRECT OR REPLACE ANY NOISY SYSTEM OR EQUIPMENT AS REQUIRED.13.OBTAIN PERMITS AND PAY ALL FEES. ARRANGE FOR ALL REQUIRED INSPECTIONS AND APPROVALS.B.DEMOLITION1.DISCONNECT, DISASSEMBLE, CAP, PLUG AND REMOVE ALL MEP ELEMENTS (PIPING, DUCTS, ELECTRICAL DEVICES, WIRING, CONDUIT,EQUIPMENT, HANGERS, SUPPORTS, ETC) INDICATED ON THE DRAWINGS OR NOT OTHERWISE REQUIRED FOR COMPLETED PRODUCT. NO MEPELEMENTS ARE TO BE ABANDONED IN PLACE UNLESS SPECIFICALLY NOTED. NOT ALL ITEMS TO BE REMOVED ARE INDICATED ON DRAWING.2.ALL OPENINGS ON PIPING AND DUCTS THAT REMAIN SHALL BE CAPPED AND PROPERLY SECURED. WIRING SHALL BE DISCONNECTED ATCIRCUIT BREAKERS AND REMOVED AND BREAKERS MARKED "SPARE."  REMOVE AND RECLAIM ANY REFRIGERANT IN EXISTING SYSTEMS PRIORTO DEMOLITION OF ANY EQUIPMENT ACCORDING TO FEDERAL REQUIREMENT.3. ANY EQUIPMENT DESIGNATED BY OWNER TO BE SALVAGED SHALL BE PROTECTED AND DELIVERED TO AN OWNER DESIGNATED AREA ONSITE.4.ALL ASBESTOS REMOVAL (IF REQUIRED) WILL BE HANDLED BY THE OWNER AND IS NOT A PART OF THIS WORK.  IF MATERIALS SUSPECTED OFCONTAINING HAZARDOUS MATERIALS ARE ENCOUNTERED, DO NOT DISTURB; NOTIFY ARCHITECT AND OWNER IMMEDIATELY.C.BASIS OF DESIGN AND SUBSTITUTIONS1.MANUFACTURERS LISTED ARE BASIS OF DESIGN.  SUBSTITUTIONS ARE SUBJECT TO THE APPROVAL OF THE OWNER, ARCHITECT & ENGINEER.  IFSUBSTITUTION IS SUBMITTED, IT IS THE CONTRACTOR'S RESPONSIBILITY TO EVALUATE IT AND CERTIFY THAT THE SUBSTITUTION IS EQUIVALENTIN ALL RESPECTS TO THE BASIS OF DESIGN. WHERE SUBMITTALS VARY FROM THE CONTRACT REQUIREMENTS, THE CONTRACTOR SHALLCLEARLY INDICATE ON SUBMITTAL OR ACCOMPANYING DOCUMENTS THE NATURE AND REASON FOR VARIATIONS.  IF SUBSTITUTIONS AREAPPROVED, NOTIFY ALL OTHER CONTRACTORS, SUBCONTRACTORS OR TRADES AFFECTED BY SUBSTITUTION AND FULLY COORDINATE.  ANYCOSTS RESULTING FROM SUBSTITUTION, WHETHER BY CONTRACTOR OR OTHERS, SHALL BE RESPONSIBILITY OF AND PAID FOR BYSUBSTITUTING CONTRACTOR.  APPROVED SHOP DRAWINGS DOES NOT ABSOLVE THIS CONTRACTOR FROM THIS RESPONSIBILITY. APPROVALOF SUBSTITUTIONS IS AT THE DISCRETION OF THE ARCHITECT & ENGINEER AND IF SUBMITTED AFTER THE BID, AT THE RISK OF THECONTRACTOR.2.ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE OF DEFECTS AND U.L. LABELED.D.CUTTING, PATCHING AND DRILLING1.ALL CUTTING AND PATCHING OF THE BUILDING CONSTRUCTION REQUIRED FOR THIS WORK SHALL BE BY THIS CONTRACTOR UNLESS SHOWNON ARCHITECTURAL DRAWINGS AND CONFIRMED AS TO SIZE AND LOCATION PRIOR TO NEW CONSTRUCTION. CUTTING SHALL BE IN A NEATAND WORKMANLIKE MANNER. NEATLY SAW CUT ALL RECTANGULAR OPENINGS, SET SLEEVE THROUGH OPENING, AND FINISH PATCH ORPROVIDE TRIM FLANGE AROUND OPENING. CORE DRILL AND SLEEVE ALL ROUND OPENINGS. DO NOT CUT ANY STRUCTURAL COMPONENTSWITHOUT ARCHITECT'S APPROVAL.2.PATCH AND FINISH TO MATCH ADJACENT AREAS THAT HAVE BEEN CUT, DAMAGED OR MODIFIED AS A RESULT OF THE INSTALLATION OF THEMECHANICAL OR ELECTRICAL EQUIPMENT. FIRE STOP ALL PENETRATIONS OF FIRE RATED CONSTRUCTION IN A CODE APPROVED MANNER.3.ALL CONTRACTORS SHALL CONFIRM WITH OWNER, PRIOR TO BID, TIMES AVAILABLE FOR NOISE PRODUCING WORK SUCH AS CUTTING ANDCORE DRILLING OF FLOORS, WALLS, ETC., AS WELL AS TIMES FOR WORK WHICH REQUIRE ACCESS INTO ADJOINING TENANT SPACES. INCLUDEANY PREMIUM TIME IN BID.4.EXACT LOCATION OF ROOFTOP EQUIPMENT SHALL BE APPROVED BY OWNER'S STRUCTURAL ENGINEER.5.INFORMATION REGARDING REQUIRED PIPE OPENINGS IN WALLS, FLOORS, CHASES, ETC., AND CONCRETE EQUIPMENT PADS OR FOUNDATIONSSHALL BE GIVEN TO THE GENERAL CONTRACTOR BY THIS CONTRACTOR PRIOR TO THE CONSTRUCTION PERIOD. IF THIS CONTRACTOR FAILS TOCOMPLY WITH THIS REQUEST, OR IF INCORRECT INFORMATION IS GIVEN, THE NECESSARY CUTTING AND PATCHING WILL BE PERFORMED BY THEGENERAL CONTRACTOR, AT THIS CONTRACTOR'S EXPENSE.E.WARRANTY1.FULLY WARRANT ALL MATERIALS, EQUIPMENT AND WORKMANSHIP FOR ONE (1) YEAR FROM DATE OF ACCEPTANCE.EXTEND ALLMANUFACTURER'S WARRANTIES TO OWNER, INCLUDING ALL EXTENDED WARRANTIES ON HVAC EQUIPMENT.2.REPAIR OR REPLACE WITHOUT CHARGE TO THE OWNER ALL ITEMS FOUND DEFECTIVE DURING THE WARRANTY PERIOD. IN THE CASE OFREPLACEMENT OR REPAIR DUE TO FAILURE WITHIN THE WARRANTY PERIOD, THE WARRANTY ON THAT PORTION OF THE WORK SHALL BEEXTENDED FOR A MINIMUM PERIOD OF ONE (1) YEAR FROM THE DATE OF SUCH REPLACEMENT OR REPAIR.F.SHOP DRAWING SUBMITTALS1.SUBMIT SHOP DRAWINGS FOR MECHANICAL EQUIPMENT, FIRE PROTECTION SYSTEMS, DUCTWORK, AND PLUMBING FIXTURES AND EQUIPMENTWITH ADEQUATE DETAILS AND SCALES TO CLEARLY SHOW CONSTRUCTION. INDICATE THE OPERATING CHARACTERISTICS FOR EACH REQUIREDITEM. CLEARLY IDENTIFY EACH ITEM ON THE SUBMITTAL AS TO MARK, LOCATION AND USE, USING SAME IDENTIFICATION AS PROVIDED ONDESIGN DRAWINGS.2.DUCTWORK AND FIRE PROTECTION DRAWINGS SHALL BE FULLY DIMENSIONED BASED ON FIELD VERIFIED BUILDING CLEARANCES ANDARCHITECTURAL CEILING LAYOUTS, AND INDICATE STRUCTURAL, LIGHTING, DUCTWORK AND PIPING AT ALL CRITICAL LOCATIONS.3.CONTRACTOR SHALL REVIEW AND INDICATE HIS APPROVAL OF EACH SHOP DRAWING PRIOR TO SUBMITTAL FOR REVIEW. DO NOT STARTWORK OR FABRICATION UNTIL SHOP DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND RETURNED TO THE CONTRACTOR.4.SUBMITTALS WILL BE REVIEWED ONLY FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS AND NOT FOR DIMENSIONS ORQUANTITIES. THE SUBMITTAL REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR PURCHASE OF ANY ITEM IN FULLCOMPLIANCE WITH THE CONTRACT DOCUMENTS OR ITS COMPLETE AND PROPER INSTALLATION.5.WHERE SUBMITTALS VARY FROM THE CONTRACT REQUIREMENTS, THE CONTRACTOR SHALL CLEARLY INDICATE ON SUBMITTAL ORACCOMPANYING DOCUMENTS THE NATURE AND REASON FOR VARIATIONS.6.REFER TO VARIOUS SECTIONS FOR LISTING OF SHOP DRAWINGS REQUIRED ON THIS PROJECT.7.EACH MANUFACTURER OR HIS REPRESENTATIVE MUST CHECK THE APPLICATION OF HIS EQUIPMENT AND CERTIFY AT TIME OF SHOP DRAWINGSUBMITTAL THAT EQUIPMENT HAS BEEN PROPERLY APPLIED AND CAN BE INSTALLED, SERVICED AND MAINTAINED WHERE INDICATED ONDRAWINGS. ADVISE ENGINEER IN WRITING WITH SUBMITTAL DRAWINGS OF ANY POTENTIAL PROBLEMS. THE MANUFACTURER SHALL BERESPONSIBLE FOR ANY CHANGES THAT MIGHT BE NECESSARY BECAUSE OF PHYSICAL CHARACTERISTICS OF EQUIPMENT THAT HAVE NOTBEEN CALLED TO THE ENGINEER'S ATTENTION AT THE TIME OF SUBMITTAL.G.RECORD DRAWINGS1.EACH CONTRACTOR OR SUBCONTRACTOR SHALL KEEP ONE (1) COMPLETE SET OF THE CONTRACT WORKING DRAWINGS ON THE JOB SITE ONWHICH HE SHALL REGULARLY RECORD ANY DEVIATIONS OR CHANGES FROM SUCH CONTRACT DRAWINGS MADE DURING CONSTRUCTION.2.THESE DRAWINGS SHALL RECORD THE LOCATION OF ALL CONCEALED EQUIPMENT, PIPING, ELECTRIC SERVICE, SEWERS, WASTES, VENTS,DUCTS, CONDUIT AND OTHER PIPING, BY MEASURED DIMENSIONS TO EACH SUCH ITEM FROM READILY IDENTIFIABLE AND ACCESSIBLE WALLSOR CORNERS OF THE BUILDING. PLANS ALSO SHALL SHOW INVERT ELEVATION OF SEWERS AND TOP ELEVATION OF ALL OTHERBELOW-GRADE LINES.3.RECORD DRAWINGS SHALL BE KEPT CLEAN AND UNDAMAGED AND SHALL NOT BE USED FOR ANY PURPOSE OTHER THAN RECORDINGDEVIATIONS FROM WORKING DRAWINGS AND EXACT LOCATIONS OF CONCEALED WORK.4.AFTER THE PROJECT IS COMPLETED, THESE SETS OF DRAWINGS SHALL BE DELIVERED TO THE ARCHITECT IN GOOD CONDITION, AS APERMANENT RECORD OF THE INSTALLATION AS ACTUALLY CONSTRUCTED.H.FIRESTOPPING1.ALL SERVICES THAT PASS THRU FIRE OR SMOKE RATED PARTITIONS, WALLS, FLOORS, SHALL BE FIRESTOPPED. FIRE STOPPING RATING SHALLMATCH PARTITION RATING. ALL FIRE STOPPING SYSTEM SHALL MEET THE REQUIREMENTS OF ASTM E 814,UL 1479, AND BE FACTORY MUTUALAPPROVED.2.ALL FIRESTOPING AND/OR SMOKE STOPPING MATERIAL AND INSTALLATION SHALL BE AS MANUFACTURED BY HILTI OR APPROVED EQUAL.I.ACCESS DOORS & PANELS1.ACCESS DOORS SHALL BE PROVIDED IN WALLS AND CEILINGS WHERE REQUIRED TO PERMIT PROPER ACCESS TO VALVES AND ANY OTHERSUCH DEVICES WHICH REQUIRE MAINTENANCE OR SERVICE. DOORS PLACED IN WALLS, PARTITIONS OR OTHER FIRE-RATED CONSTRUCTIONSHALL HAVE A LABEL SIGNIFYING THAT THE DOOR HAS THE SAME FIRE RATING AS THE FIRE-RATED CONSTRUCTION.2.THIS CONTRACTOR SHALL FURNISH ACCESS PANELS TO THE GENERAL CONTRACTOR FOR INSTALLATION.3.ACCESS PANELS SHALL BE CONSTRUCTED OF 14 GAUGE STEEL, WITH 16 GAUGE STEEL FRAMES. DOORS SHALL FINISH FLUSH WITH THESURROUNDING SURFACE. FRAMES SHALL HAVE 3 INCH WIDE EXPANDED METAL FOR PLASTERED SURFACES AND PLAIN FLANGED TYPE FRAMEFOR TILE, MASONRY OR GYPSUM BOARD SURFACES. DOORS AND FRAMES SHALL BE FURNISHED PRIME COATED. DOORS INSTALLED INCERAMIC TILE OR OTHER NON-PAINTED SURFACES SHALL BE STAINLESS STEEL. HINGES SHALL BE CONCEALED SPRING TYPE, TO ALLOWDOORS TO BE OPENED 175 DEGREES. LOCKS SHALL BE FLUSH SCREWDRIVER TYPE WITH STEEL CAMS. ACCESS PANELS SHALL BE 16 INCHESBY 16 INCHES OR LARGER AS MAY BE REQUIRED FOR PROPER ACCESS TO THE DEVICE BEING SERVED.4.ACCESS PANELS ARE NOT REQUIRED IN COMPLETELY ACCESSIBLE LIFT OUT TILE CEILINGS. CONTRACTOR SHALL REVIEW THE ROOM FINISHSCHEDULE ON THE ARCHITECTURAL DRAWINGS IN ORDER TO VERIFY THE NEED FOR ACCESS PANELS.DUCTWORK (233113)1.FABRICATE AND ERECT ALL DUCTWORK TO ASHRAE AND SMACNA STANDARDS FROM NO. 1 GALVANIZED STEEL. COMPLY WITH NFPABULLETIN 90A REQUIREMENTS.2.SUPPLY DUCTWORK UPSTREAM OF TERMINAL UNITS AND WITHIN 15' OF ANY AHU FAN OUTLET SHALL HAVE A SMACNA 3" STATIC PRESSURERATING WITH SEAL CLASS A SEAMS AND JOINTS.3.GENERAL SUPPLY AND RETURN DUCTWORK HAVE A SMACNA 2" STATIC PRESSURE RATING WITH SEAL CLASS B SEAMS AND JOINTS.4.ALL EXPOSED ROUND AND OVAL DUCTWORK IN SHALL HAVE SPIRAL LOCKSEAM CONSTRUCTION.5.ALL RECTANGULAR TRANSFER DUCTWORK SHALL HAVE 1" THICK ACOUSTICAL LINER.6.GENERAL EXHAUST DUCTWORK UNDER 45' IN LENGTH SHALL HAVE A SMACNA 1" STATIC PRESSURE RATING WITH SEAL CLASS B SEAM ANDJOINTS. EXHAUST DUCTWORK OVER 45' IN LENGTH SHALL HAVE A SMACNA 2" STATIC PRESSURE RATING WITH SEAL CLASS A SEAM ANDJOINTS.7.ALL FLEXIBLE DUCTWORK SHALL BEAR THE UL 181 LABEL (CLASS 1 AIR DUCT) AND SHALL BE FACTORY INSULATED (1-1/2 “, 0.6 LB.,FIBERGLASS) ATCO UPC #076 I OR EQUAL.  FLEXIBLE DUCTWORK SHALL COMPLY W/ NFPA 90A, AND NFPA 90B.  ALL FLEXIBLE DUCTWORKCONNECTED TO DIFFUSERS SHALL NOT BE LESS THAN THE NECK SIZE OF THE DIFFUSER.  MINIMUM FLEXIBLE DUCT BEND RADIUS OFCURVATURE SHALL BE 3 DUCT DIAMETERS, MAXIMUM LENGTH SHALL BE 8-0", NO MORE THAN THE EQUIVALENT OF TWO (2) 90 DEGREE BENDSWILL BE ACCEPTABLE. FLEXIBLE DUCTS SHALL BE INDEPENDENTLY SUPPORTED FROM THE STRUCTURE AND CONNECTED WITH PLASTIC DRAWBANDS TIGHTENED WITH MANUFACTURER'S TOOL. FLEXIBLE DUCTS ARE NOT PERMITTED IN ROOMS WITHOUT CEILINGS.  8.INCLUDE ALL ACOUSTIC, DOUBLE RADIUS AIRFOIL SHAPED PERFORATED ALUMINUM TURNING VANES, MANUAL DAMPERS, FLEXIBLECONNECTORS, GRILLES AND DIFFUSERS, ACOUSTIC LINING, AND OTHER SHEET METAL ACCESSORIES FOR THE PROJECT. VOLUME DAMPERSTO BE OF OPPOSED BLADE TYPE CONSTRUCTED IN ACCORDANCE WITH "SMACNA" STANDARDS.9.ALL BRANCH CONNECTION FITTINGS IN RECTANGULAR DUCTWORK SHALL BE 45 DEGREE TRANSITION TYPE, CONICAL FITTINGS OR SPIN-INFITTINGS. BUTT FITTINGS ARE NOT ACCEPTABLE.HYDRONIC PIPING (232113)1.PIPE AND FITTINGS -- HYDRONIC PIPING 2" AND SMALLER SHALL BE TYPE "L" HARD COPPER TUBING ASTM B 88-832 WITH SWEATED JOINTSASTM B 16.22 USING 95_5 OR ANTIMONY SOLDER OR "PRESS-FIT" MECHANICAL JOINTING. FITTINGS SHALL BE CAST BRASS OR WROUGHTCOPPER. PROVIDE SCREWED UNIONS AT FINAL CONNECTIONS TO EQUIPMENT TO ALLOW DISCONNECTION FOR REPAIR OR SERVICING.2.BALL VALVES --- UP TO 2": BRONZE TWO PIECE BODY, STAINLESS STEEL BALL, TEFLON SEATS AND BLOW-OUT PROOF STUFFING BOX RING,LEVER HANDLE, AND BALANCING STOPS, UNION SOLDER ENDS. ACCEPTABLE MANUFACTURERS: CONBRACO (APOLLO), WATTS, INC., CRANE,INC., OR STOCKHAM, INC.3.BUTTERFLY VALVES -- BUTTERFLY VALVES SHALL BE DEZURIK 660 OR EQUAL WITH SEMI_STEEL LUG STYLE BODY, BRONZE DISC, 416STAINLESS STEEL SHAFT, BRONZE BEARINGS, "NORDEL" RUBBER SEAT, LEVER HANDLE OPERATORS AND SHALL BE RATED AT 175 POUNDSCWP. VALVES SHALL PROVIDE DEAD TIGHT SHUTOFF CAPABILITY IN EITHER DIRECTION UP TO 150 PSI WHEN THE DOWNSTREAM FLANGES AREREMOVED.4.VENT AND DRAIN VALVES -- ALL WATER PIPING SYSTEMS SHALL BE INSTALLED IN SUCH A MANNER THAT THEY CAN BE COMPLETELY VENTEDAND DRAINED. UNLESS OTHERWISE NOTED, PROVIDE AT ALL HIGH POINTS WHERE AIR CAN COLLECT 1/4" BRASS COMPRESSION VENT COCKS,AND AT ALL LOW POINTS ½" BALL VALVES WITH HOSE BIB ENDS AND CAPS.5.PRESSURE/TEMPERATURE PLUGS -- PROVIDE SISCO OR PETERSON 1/4_INCH NPT FITTING OF SOLID BRASS, FOR 1/8" O.D. PROBE. VALVE CORESHALL BE NEOPRENE FOR TEMPERATURE TO 200 F, AND RATED FOR ZERO LEAKAGE FROM VACUUM TO 1,000 PSIG. PROVIDE TEST KITCONSISTING OF TWO PRESSURE GAGES WITH PROBES AND 2 DIAL THERMOMETERS WITH CARRYING CASE.6.STRAINERS -- Y-PATTERN, BODY: ASTM A 126, CLASS B CAST IRON, WITH BOLTED OR SCREWED COVER AND BOTTOM DRAIN CONNECTION.END CONNECTIONS: THREADED ENDS FOR STRAINERS NPS 2 AND SMALLER; FLANGED ENDS FOR STRAINERS NPS 2-1/2 AND LARGER.STRAINER SCREEN: STAINLESS-STEEL, 20-MESH STRAINER, OR PERFORATED STAINLESS-STEEL BASKET. WITH TAPPED BLOWOFF PLUG.RATING: 150-PSIG WORKING PRESSURE.7. BALANCING VALVES -- PROVIDE BELL & GOSSETT "CIRCUIT SETTER PLUS" BALANCING VALVES WHERE SHOWN IN PIPING DETAILS ON THEDRAWINGS. VALVES SHALL BE OF BRONZE BODY/BRASS BALL CONSTRUCTION (½" TO 3" SIZES) WITH GLASS AND CARBON FILLED TFE SEATRINGS. VALVES SHALL HAVE DIFFERENTIAL PRESSURE READOUT PORTS, MEMORY STOP, CALIBRATED NAMEPLATE AND DRAIN PORT. EACHVALVE SHALL HAVE POSITIVE SHUTOFF AND SHALL BE CONSTRUCTED FOR 125 PSIG WORKING PRESSURE AT 250 DEGREES. PROVIDE TWO"CIRCUIT SETTER" CALCULATORS FOR THE OWNER'S USE.8.AUTOMATIC BALANCING VALVES -- PROVIDE HAYS FLUID CONTROLS "MEASURFLO" AUTOMATIC BALANCING VALVES, OR APPROVED EQUAL,WHERE SHOWN IN PIPING DETAILS ON DRAWINGS. VALVES SHALL HAVE BRASS BODIES AND CHANGEABLE FLOW CARTRIDGES.9.PROVIDE VALVES AND UNIONS WHERE NEEDED TO PERMIT DISCONNECTIONS OF EACH PIECE OF EQUIPMENT FOR REPAIRS. MAKECONNECTIONS TO EQUIPMENT WITH SHUT-OFF VALVES ON SUPPLY AND BALANCE VALVES ON RETURNS.  INSTALL UNIONS IN PIPES 2“ ANDSMALLER, ADJACENT TO EACH VALVE, AT FINAL CONNECTIONS EACH PIECE OF EQUIPMENT, AND ELSEWHERE AS INDICATED.  UNIONS ARE NOTREQUIRED ON FLANGED DEVICES.10.CONNECTIONS BETWEEN DISSIMILAR PIPING MATERIALS SHALL BE MADE WITH SUITABLE DIELECTRIC INSULATING UNIONS.  ISOLATE COPPERPIPING FROM DISSIMILAR METALS, SUCH AS METAL STUDS AND VENT PIPING.11.CLOSED SYSTEM WATER TREATMENT -- FILL SYSTEM WITH WATER AND LOW FOAM DETERGENT TO REMOVE DIRT AND SCALE, CIRCULATEUNTIL SYSTEM IS CLEAN AND FLUSH UNTIL WATER IS CLEAR AND REFILL WITH CLEAN WATER . ADD CORROSION AND RUST INHIBITORS.CHECK PH AND ADD CHEMICALS TO ADJUST PH PER MANUFACTURER'S INSTRUCTIONS. PROVIDE CHEMICAL POT FEEDER AND PIPE ACROSSSYSTEM. PROVIDE CHEMICAL TO TREAT SYSTEM FOR ONE YEAR. RECHECK AFTER ONE YEAR AND ADD CHEMICAL AS NEEDED FOR PROPERCHEMICAL TREATMENT.12.PROVIDE CONDENSATE DRAIN FOOR ALL COOLING COILS. ALL CONDENSATE DRAINS SHALL BE TRAPPED PER THE COOLING COIL TRAP DETAILOR MANUFACTURERS RECOMMENDATIONS, WHICH EVER IS MORE STRINGENT/DEEPER. PROVIDE CLEANOUT.13.CONDENSATE DRAIN PIPING IN RETURN AIR RATED PLENUMS SHALL BE TYPE L COPPER WITH 1/2" FIBERGLASS INSULATION (MIN. R-VAULE = 3).SCHEDULE 40 PVC WITHOUT INSULATION MAY BE USED IN ALL OTHER LOCATIONS.14.WHERE DAMAGE TO ANY BUILDING COMPONENT COULD OCCUR AS A RESULT OF OVERFLOW OR STOPPAGE OF THE PRIMARY CONDENSATEDRAIN SYSTEM, PROVIDE UL 508 WATER-LEVEL DETECTION DEVICE IN THE PRIMARY DRAIN PAN, OVERFLOW OUTLET OR IN A SECONDARYDRAIN PAN PER IMC REQUIREMENTS. COOLING SYSTEM SHALL DISABLE UPON DETECTION OF WATER AND GENERATE A BAS ALARM(IFAPPLICABLE.DUCTWORK & PIPE INSULATION (230713, 230719)1.INSULATE ALL ACCESSIBLE CONCEALED SUPPLY DUCTS WITH 1-1/2" THICK FOIL FACED REINFORCED KRAFT JACKET, FIBERGLASS DUCT WRAPFULLY SECURED TO DUCT. LAP AND TAPE SEAMS AND SECURE TIGHTLY TO THE DUCTS WITH WIRE OR STICK PINS. 2" THICK RIGID FIBERGLASSBOARD INSULATION SHALL BE USED FOR ALL INDOOR EXPOSED APPLICATIONS. INSULATION SHALL HAVE A MINIMUM R-VALUE OF 6.2.ALL DUCTWORK INSTALLED OUTSIDE OF THE BUILDING ENVELOPE SHALL BE INSULATED WITH 2" THICK FIBERGLASS BOARD INSULATIONHAVING A MINIMUM R-VALUE OF 8.3.DO NOT INSULATE:3.1.MAKE-UP AIR DUCTWORK OPERATING AT SURROUNDING AMBIENT CONDITIONS.3.2.RETURN AND EXHAUST AIR DUCTWORK LOCATED WITHIN THE BUILDING ENVELOPE. (DOES NOT INCLUDE BUILDING SHAFTS.)3.3.TRANSFER AIR DUCTWORK (ACOUSTICALLY LINE DUCT, CLEAR INSIDE DIMENSIONS SHOWN ON PLANS)3.4.EXPOSED SUPPLY DUCTWORK LOCATED IN CONDITIONED SPACE. (DOES NOT INCLUDE RETURN AIR PLENUM.)3.5.PHENOLIC DUCTWORK4.INTERNAL DUCT INSULATION -- DUCTWORK INDICATED TO HAVE INTERNAL NON-FIBEROUS INSULATION SHALL BE INTERNALLY COVERED WITH 1"THICK FLEXIBLE HYPOALLERGENIC POLYESTER FIBER INSULATION WITH FSK FACING. FOR DUCTWORK LOCATED OUTDOORS USE 2" THICKINTERNAL POLYESTER INSULATION. INSULATION SHALL HAVE AN "R" RATING OF 5 FOR 1" THICK INSULATION AND R-8 FOR 2" THICK INSULATION.INSULATION SHALL HAVE FLAME/SMOKE RATING OF 2.5/21. ONE INCH THICK INSULATION TO HAVE NRC COEFFICIENT OF 0.65. INSULATIONSHALL WITHSTAND DUCT VELOCITIES OF 4000 FPM. DUCT SIZES SHOWN IS CLEAR INSIDE. WHERE LINER IS USED INCREASE OUTSIDEDIMENSIONS OF SHEET METAL TO MAINTAIN INSIDE DUCT AREA. INSTALL PER MANUFACTURER'S INSTRUCTIONS.5.HYDRONIC PIPING TO BE INSULATED SHALL BE COVERED WITH 1-1/2" THICKNESS 4 POUND DENSITY [MAXIMUM CONDUCTIVITY = 0.27BTU/(HR·FT·°F)] SECTIONAL GLASS FIBER PIPE INSULATION HAVING FACTORY APPLIED WHITE "ALL SERVICE" JACKET. PIPING LOCATEDOUTDOORS SHALL BE INSULATED WITH 2" THICK INSULATION. LONGITUDINAL FLAPS SHALL BE SELF-SEALING TYPE ADDITIONALLY SECUREDWITH NONFERROUS FLARE DOOR STAPLES SPACED 6" ON CENTERS. END JOINTS SHALL BE CLOSED WITH 4" WIDE SELF-SEALING TAPESTAPLED IN PLACE. ALL FITTINGS TO BE FINISHED WITH PRE_MOLDED ONE-PIECE ZESTON TYPE PVC COVERS WITH FIBERGLASS INSULATIONINSIDE. SEAL ALL VISIBLE RAW FIBERGLASS WITH BENJAMIN FOSTER #3036 WHITE MASTIC.6.ALL INSULATION TO BE APPLIED IN FULL ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ALL INSULATION SHALL COMPLYWITH 25/50 FLAME AND SMOKE HAZARD RATINGS PER ASTM E-84, NFPA 255 AND UL 723.7.PROVIDE REMOVABLE INSULATION SECTIONS TO COVER PARTS OF EQUIPMENT WHICH MUST BE OPENED PERIODICALLY FOR MAINTENANCE;INCLUDE METAL VESSEL COVERS, FASTENERS, FLANGES, CHILLED WATER PUMPS, FRAMES AND ACCESSORIES.8.REPLACE DAMAGED INSULATION WHICH CANNOT BE REPAIRED SATISFACTORILY, INCLUDING UNITS WITH VAPOR BARRIER DAMAGE ANDMOISTURE SATURATED UNITS.EQUIPMENT (235000)1.MAKE ALL FINAL EQUIPMENT CONNECTIONS AND PROVIDE THE NECESSARY ADAPTORS, FITTINGS, VALVES, DEVICES, ETC. FOR A COMPLETEAND OPERABLE SYSTEM.  PROVIDE COMPLETE WITH BASES, ISOLATORS, SUPPORTS AND OTHER REQUIRED ACCESSORIES.2.EQUIPMENT SHALL BE INSTALLED IN FULL ACCORDANCE WITH THE MANUFACTURER'S DATA AND INSTALLATION INSTRUCTIONS, INCLUDINGCLEARANCES; LUBRICATE AND ADJUST AS REQUIRED.  IT IS THIS CONTRACTOR'S RESPONSIBILITY TO CHECK AND CONFORM TO THESEREQUIREMENTS PRIOR TO STARTING WORK.  FURNISH AND INSTALL CLEAN SET OF FILTERS PRIOR TO BALANCING.3.THE CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL EQUIPMENT PRIOR TO ORDERING OF EQUIPMENT.COORDINATE REQUIREMENT FOR PROVISION OF MOTOR STARTERS, DISCONNECTS, CONTACTORS, CONTROL WIRING, ETC. AS REQUIRED FORPROPER FUNCTIONING SYSTEM WITH ELECTRICAL CONTRACTOR. NO ADDITIONAL PAYMENT WILL BE MADE FOR LACK OF CONTRACTORCOORDINATION OF ELECTRICAL CHARACTERISTICS.4.ALL FLOOR MOUNTED EQUIPMENT SHALL BE INSTALLED ON CONCRETE HOUSEKEEPING PADS.  MINIMUM PAD THICKNESS SHALL BE NOMINAL4”.  PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4” ON EACH SIDE. CONCRETE PADS SHALL BE PROVIDED BY THISCONTRACTOR. IT SHALL BE THE RESPONSIBILITY OF THE THIS CONTRACTOR TO COORDINATE THE SIZE AND LOCATION OF THE CONCRETEHOUSEKEEPING PADS WITH THE GENERAL CONTRACTOR.5.ALL EQUIPMENT SHALL BE MOUNTED ON VIBRATION ISOLATORS TO PREVENT THE TRANSMISSION OF VIBRATION AND MECHANICALLYTRANSMITTED SOUND TO THE BUILDING STRUCTURE.6.ISOLATION EQUIPMENT SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER, AND SHALL BE DESIGNED SPECIFICALLY FOR THE APPLICATIONREQUIRED. THIS INCLUDES, BUT IS NOT LIMITED TO, PIPING DUCTWORK, PUMPS, COMPRESSORS. VIBRATION ISOLATORS SHALL BE RATED FORTHE WEIGHT AND SPACING REQUIRED FOR THE EQUIPMENT REQUIRING ISOLATION.7.PROVIDE CURBS FOR ALL ROOF OPENINGS FOR DUCTS, FLUES, PIPING AND EQUIPMENT.  CURBS SHALL BE FURNISHED AS ACCESSORIES TOTHE EQUIPMENT OR 8" HIGH PATE OR EQUAL EQUIPMENT SUPPORTS SPANNING STRUCTURE AND FLASHED INTO ROOFING. ALL CUTTING,FLASHING, AND PATCHING OF ROOF SHALL BE BY OWNER'S ROOFING CONTRACTOR AND PAID FOR BY MECHANICAL CONTRACTOR.CONTROLS (230910)1.PROVIDE COMPLETE TEMPERATURE CONTROLS FOR ALL HVAC SYSTEMS.  PROVIDE NEW CONTROL DEVICES INCLUDING DAMPER OPERATORS,TEMPERATURE SENSORS, STAGING RELAYS AND OTHER REQUIRED DEVICES TO PROVIDE A COMPLETE OPERATIONAL SYSTEM PER THEFOLLOWING OPERATING SEQUENCE.  MOUNT ALL CONTROLS FURNISHED AS ACCESSORIES TO EQUIPMENT AND PROVIDE ALL CONTROL WIRINGREQUIRED FOR PROPER OPERATION WHERE NOT SPECIFICALLY SHOWN ON ELECTRICAL PLANS.  ALL WIRING SHALL BE IN CONDUIT OR PERN.E.C. AND LOCAL CODE REQUIREMENTS.  STANDARD MOUNTING HEIGHT TO TOP OF THERMOSTAT IS 48" ABOVE FINISHED FLOOR OR ASINDICATED ON THE ARCHITECTURAL DRAWINGS.  DO NOT INSTALL THERMOSTATS NEAR DIMMER SWITCHES.  WIRING OF ALL MOTORIZEDOPERATORS AND THERMOSTATS (REGARDLESS OF VOLTAGE) ARE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR.2.THE CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE, WEB-BASED, NATIVE BACNET-INTEGRATED BUILDING AUTOMATION SYSTEM(BAS) INCLUDING ALL NECESSARY HARDWARE, ALL OPERATING AND APPLICATIONS SOFTWARE NECESSARY TO PERFORM THE HVAC CONTROLSEQUENCES OF OPERATION AS CALLED FOR IN THIS SPECIFICATION OR AS SHOWN ON THE DRAWINGS. BAS CONTRACTOR SHALL FURNISHAND INSTALL ALL RELATED SOFTWARE AND HVAC-DDC CONTROLS AS SPECIFIED WITHIN THIS SPECIFICATION. IT SHALL BE THERESPONSIBILITY OF THE BAS CONTRACTOR TO COORDINATE THIS WORK WITH THE GENERAL CONTRACTOR, MECHANICAL CONTRACTOR, ANDTHE ELECTRICAL CONTRACTOR AS IT RELATES TO THE INSTALLATION AND WIRING OF ALL RELATED HVAC SYSTEMS.3.IT SHALL BE THE RESPONSIBILITY OF THE BAS CONTRACTOR TO PROVIDE ALL THE REQUIRED LABOR AND PROGRAMMING TO SEAMLESSLYINTEGRATE THE NEW BAS BACNET SYSTEM AND ITS DDC POINTS, GRAPHICS, ALARMS, ETC. INTO AN EXISTING BAS IF PRESENT.4.THE CONTROLS CONTRACTOR SHALL WARRANT THE SYSTEM FOR 24 MONTHS AFTER SUBSTANTIAL COMPLETION. DURING THE WARRANTYPERIOD, THE BUILDING SYSTEM CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY REVISIONS TO THE SOFTWARE AS REQUIRED TOPROVIDE A COMPLETE AND WORKABLE SYSTEM CONSISTENT WITH THE LETTER AND INTENT OF THE SEQUENCE OF OPERATION SECTION OFTHE SPECIFICATION.5.THE FOLLOWING ARE THE APPROVED BAS MANUFACTURERS:·RELIABLE CONTROLS BY PITTSBURGH CONTROLS & CONSULTING·SCHNEIDER ELECTRIC ANDOVER CONTINUUM BY CS&E·JCI PITTSBURGH BRANCH OFFICE·SIEMENS PITTSBURGH·TRANE·AUTOMATED LOGIC, INC.2.CONTROL SEQUENCE SHALL BE AS FOLLOWS:HANGERS AND SUPPORTS (230529)1.SUPPORT ALL PIPING FROM STRUCTURE WITH UL LISTED HANGERS AND SUPPORTS SUITABLE FOR THE INTENDED INSTALLATION.  DESIGN,SELECTION, SPACING, AND APPLICATION OF HANGERS AND SUPPORTS SHALL COMPLY WITH ANSI B31.1 AND MSS SP-69. HANGERS SHALL BEMANUFACTURED BY PENTAIR., OR APPROVED EQUAL. BLACK OR GALVANIZED STEEL PIPE = MODEL NO. 100, CAST IRON PIPE = MODEL NO.400, COPPER TUBING = MODEL NO. 102-A.2.CONTRACTOR SHALL PROVIDE INSULATION HANGER WITH PROTECTIVE SHIELDS, SUCH AS PENTAIR, MODEL NO. 125, OR APPROVED EQUAL FORALL INSULATED PIPING.3.CONTRACTOR SHALL PROVIDE RISER CLAMPS FOR VERTICAL PIPING AT EACH LEVEL. RISER CLAPS SHALL BE PENTAIR MODEL NO. 510 FORSTEEL PIPING AND MODEL NO. 511 FOR COPPER TUBING OR APPROVED EQUAL. USE "SHORT-END" RISER CLAMPS WHERE SPACE IS LIMITED.4.CONTRACTOR SHALL PROVIDE SIDE BEAM CLAMPS FOR SUPPORTING PIPING FROM STRUCTURAL STEEL MEMBERS. BEAM CLAMPS SHALL BEMANUFACTURED BY PENTAIR, MODEL 300 OR APPROVED EQUAL.5.WHERE OTHER MEANS OF SUPPORT PIPING ARE REQUIRED OR DESIRED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING THEENGINEER'S APPROVAL PRIOR TO INSTALLING THOSE SUPPORTS.6.HANGERS AND SUPPORTS SHALL BE SPACED AT INTERVALS WHICH WILL PREVENT SAGGING AND REDUCE STRAIN ON VALVES ANDSPECIALTIES. HANGER SPACING SHALL BE NO GREATER AND ROD SIZE SHALL BE NO SMALLER THAN THAT SHOWN IN THE FOLLOWING TABLE.HANGERS SHALL ALLOW FOR EXPANSION AND CONTRACTION. HANGER SHALL BE PROVIDED AT EACH CHANGE OF DIRECTION.7.RISER CLAMPS SHALL BE INSTALLED ABOVE THE FLOOR AT EACH LEVEL. RISER CLAMPS MAY BE SUSPENDED BELOW FLOOR LEVEL, WITHHANGER RODS AND INSERTS, WHERE THE INSTALLATION OF ESCUTCHEON PLATES IS REQUIRED.PIPE WALL SEALS (230517)1.WALL PIPE SEALS WITH RUBBER LINKS SHALL BE THUNDERLINE LINK SEAL, OR APPROVED EQUAL. WALL PIPE SEALS WITH INORGANICMATERIAL LINKS THE PENETRATIONS OF FIRE RATED WALLS SHALL BE THUNDERLINE PYRO-PAC, OR APPROVED EQUAL.2.SEALS SHALL BE MODULAR MECHANICAL TYPE CONSISTING OF INTERLOCKING SYNTHETIC RUBBER OR INORGANIC MATERIAL LINKS SHAPED TOCONTINUOUSLY FILL THE ANNULAR SPACE BETWEEN THE PIPE AND WALL OPENING. LINKS SHALL BE LOOSELY ASSEMBLED WITH BOLTS TOFORM A CONTINUOUS BELT AROUND THE PIPE. A PRESSURE PLATE SHALL BE PROVIDED UNDER THE BOLT HEAD AND NUT OF EACH LINK.SEALS SHALL BE CONSTRUCTED TO PROVIDE ELECTRICAL INSULATION BETWEEN THE PIPE AND SLEEVE, THUS REDUCING CHANCES OFCATHODIC REACTION BETWEEN THESE TWO MEMBERS.3.AFTER THE SEAL ASSEMBLY IS POSITIONED IN THE SLEEVE, THE TIGHTENING OF THE BOLTS SHALL CAUSE THE SEALING ELEMENTS TO EXPANDAND PROVIDE AN ABSOLUTELY WATER-TIGHT SEAL BETWEEN THE PIPE AND SLEEVE.4.SLEEVES SHALL BE MANUFACTURED FROM HEAVY-WALL, WELDED OR SEAMLESS STEEL PIPE. A FULL CIRCLE CONTINUOUSLY WELDEDWATER STOP PLATE SHALL BE PROVIDED TO ASSURE POSITIVE WATER SEALING OF THE SLEEVE. SLEEVE SHALL BE PROTECTED BY ACOATING OF ENRICHED RED PRIMER.IDENTIFICATION (230593)1.CONTRACTOR SHALL PROVIDE IDENTIFICATION LABELS, TAGS, ETC. AS INDICATED ON THE DRAWINGS AND AS SPECIFIED HEREIN.THEIDENTIFICATION SHALL BE IN ACCORDANCE WITH ANSI STANDARD A13.1. PRESSURE SENSITIVE MARKERS SHALL BE MANUFACTURED BY THEBRADY CO., OR APPROVED EQUAL.  MARKERS SHALL BE MANUFACTURER'S STANDARD PRODUCT. PRESSURE SENSITIVE PIPE MARKERS SHALLBE MANUFACTURED BY THE BRADY CO., OR APPROVED EQUAL. PIPE MARKERS SHALL BE MANUFACTURER'S STANDARD PRODUCT.MOTOR CONTROLLERS (230513)1.UNLESS OTHERWISE INDICATED, EVERY MOTOR NOT SPECIFIED TO BE PROVIDED WITH A CONTROLLER AT THE FACTORY SHALL BE PROVIDEDWITH A CONTROLLER AS SPECIFIED HEREIN. CONTROLLERS SHALL BE FURNISHED BY THIS CONTRACTOR. INSTALLATION OF ALLCONTROLLERS SHALL BE BY THE ELECTRICAL CONTRACTOR.2.MOTOR CONTROLLERS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS OF NEMA STANDARD IC-1, INDUSTRIAL CONTROL AND BE HEAVYDUTY CONSTRUCTION. CONTROLLER SIZES SHALL BE VERIFIED TO BE COMPATIBLE WITH HORSEPOWER OF THE MOTOR. CONTROLLERS SHALLBE MANUFACTURED BY ALLEN-BRADLEY CO., GENERAL ELECTRIC, CUTLER-HAMMER OR APPROVED EQUAL.3.MANUAL MOTOR STARTERS:a.SWITCHES SHALL BE TUMBLER-SWITCH STYLE. THE MANUAL MOTOR STARTERS SHALL PROVIDE OVERLOAD PROTECTION WHICH CLOSELYFOLLOWS THE MOTOR LOAD. MANUAL MOTOR STARTERS FOR OUTDOOR USE SHALL BE NEMA TYPE 4X, INDOOR USE SHALL BE NEMATYPE 1, EXPLOSION PROOF USE SHALL BE NEMA TYPE 7.4.MAGNETIC MOTOR CONTROLLERS:a.MAGNETIC MOTOR CONTROLLERS SHALL BE PROVIDED AS INDICATED. THEY SHALL NOT BE SMALLER THAN NEMA SIZE 1.b.NON-REVERSING MAGNETIC CONTROLLER SHALL BE UTILIZED TO START FULL VOLTAGE, NON-REVERSING, AC SINGLE SPEED MOTORS.THE CONTROLLERS SHALL BE SIZED FOR THE LOAD UNLESS OTHERWISE INDICATED.c.REVERSING MAGNETIC CONTROLLER SHALL BE UTILIZED TO START FULL VOLTAGE REVERSING, AC SINGLE SPEED MOTORS. THECONTROLLER SHALL BE SIZED FOR THE LOAD UNLESS OTHERWISE INDICATED. LOCATION OF REVERSING MAGNETIC CONTROLLERS ISINDICATED ON THE DRAWINGS.d.WHERE MULTI-SPEED MOTORS ARE SCHEDULED ON THE DRAWINGS, THE MOTOR CONTROLS SHALL BE COMPATIBLE WITH THE TYPE MOTORSHOWN.e.OVERLOAD RELAYS SHALL BE SOLID STATE AND BE SUPPLIED IN EACH LEG. OVERLOAD RELAYS SHALL BE MATCHED TO LOAD ANDSHALL BE ADJUSTABLE FROM 90% TO 110%. A SINGLE RESET BUTTON SHALL BE MOUNTED ON THE STARTER DOOR TO PERMIT EXTERNALRESET. RELAYS SHALL BE CONVERTIBLE FROM MANUAL TO AUTOMATIC RESET BY A SIMPLE ADJUSTMENT.f.CONTROL TRANSFORMERS SHALL BE PROVIDED, WHERE REQUIRED. BOTH LEGS OF THE PRIMARY AND ONE LEG OF THE SECONDARY OFTHE CONTROL TRANSFORMER SHALL BE PROTECTED BY NEMA CLASS J FUSES. THE OTHER LEG OF THE SECONDARY SHALL BEGROUNDED. CONTROL TRANSFORMER CAPACITY SHALL BE ADEQUATE TO OPERATE ALL CONTROL DEVICES IN THE CIRCUIT. CONTROLVOLTAGE SHALL BE 120V AC UNLESS OTHERWISE SPECIFIED.g.UNLESS OTHERWISE INDICATED, ALL MOTOR STARTERS SHALL BE PROVIDED WITH HAND-OFF-AUTOMATIC (H.O.A.) SWITCH IN THE DOOR.ENCLOSURES FOR MAGNETIC STARTERS SHALL BE NEMA TYPE 1 FOR INDOOR USE NEMA TYPE 4X FOR OUTDOOR USE AND NEMA TYPE 7FOR EXPLOSION PROOF USE.h.MOTOR CONTROLLERS SHALL BE PROVIDED WITH ALL CONTROL DEVICES, INCLUDING AUXILIARY CONTACTS, REQUIRED FOR EQUIPMENT TOOPERATE AS SPECIFIED.5.COMBINATION MOTOR CONTROLLERS:a.COMBINATION MOTOR CONTROLLERS SHALL BE PROVIDED WITH MOLDED CASE MOTOR CIRCUIT PROTECTORS OR MOLDED CASE CIRCUITBREAKERS AS INDICATED. MOTOR CIRCUIT PROTECTIVE DEVICES SHALL HAVE SHORT CIRCUIT CAPACITY AS REQUIRED. UNIT CONTROLCIRCUIT FUSING SHALL BE PROVIDED. THE MOTOR CIRCUIT PROTECTIVE DEVICE SHALL BE MOUNTED IN THE SAME ENCLOSURE AS THEMAGNETIC CONTROLLER AND SHALL BE OPERABLE BY HAND FROM OUTSIDE THE ENCLOSURE. THE HANDLE SHALL BE SO INTERLOCKEDWITH THE DOOR THAT IT MUST BE RETURNED TO THE "OFF" POSITION BEFORE THE DOOR CAN BE OPENED, BUT A COIN-PROOF DEFEATMECHANISM SHALL BE PROVIDED TO ALLOW AUTHORIZED PERSONNEL TO OPEN THE ENCLOSURE DOOR WITHOUT OPENING THEDISCONNECTING DEVICE. PROVISIONS FOR PADLOCKING THE DISCONNECT HANDLE IN THE "OFF" POSITION SHALL BE MADE. THEENCLOSURE FOR COMBINATION STARTERS SHALL BE NEMA TYPE 1 FOR INDOOR USE AND NEMA TYPE 4X FOR OUTDOOR USE, AND NEMATYPE 7 FOR EXPLOSION PROOF USE.b.MOTOR CIRCUIT PROTECTORS SHALL BE THE CONTINUOUSLY ADJUSTABLE, INSTANTANEOUS MAGNETIC TRIP TYPE CIRCUIT BREAKER ANDSHALL BE SO CONSTRUCTED THAT ALL POLES OPEN, CLOSE AND TRIP SIMULTANEOUSLY.6.OVERLOAD AND SHORT CIRCUIT PROTECTION:a.HEATER ELEMENTS SHALL BE PROVIDED FOR OVERLOAD PROTECTION. MOTOR CIRCUIT PROTECTOR SHALL BE PROVIDED FOR MOTORSHORT CIRCUIT PROTECTION.DISCONNECT SWITCHES (230514)1.THIS CONTRACTOR SHALL FURNISH ALL SAFETY DISCONNECT SWITCHES (FUSED AND NON-FUSED) REQUIRED FOR EQUIPMENT FURNISHEDUNDER THIS CONTRACT. IN ADDITION, THIS CONTRACTOR SHALL FURNISH A SAFETY DISCONNECT SWITCH FOR ALL MOTORS AND EQUIPMENTWHICH DO NOT HAVE COMBINATION STARTERS OR INTEGRAL DISCONNECTING MEANS. FUSIBLE DISCONNECT SWITCHES SHALL BE PROVIDEDFOR ALL EQUIPMENT RATED FOR USE ONLY WITH FUSES (SUCH AS CONDENSING UNITS, COMPRESSORS, ETC.). SUCH SWITCHES SHALL BEONE, TWO OR THREE POLE TYPE, WITH SOLID NEUTRAL FOR 4 WIRE SERVICE, AND SHALL HAVE THE PROPER CURRENT AND VOLTAGE RATINGAS REQUIRED. INSTALLATION OF ALL DISCONNECT SWITCHES SHALL BE BY THE ELECTRICAL CONTRACTOR.2.ALL SAFETY SWITCHES SHALL BE NEMA HEAVY DUTY TYPE AND SHALL CARRY THE UNDERWRITERS' LABORATORIES LABEL. FUSIBLESWITCHES SHALL INCORPORATE CLASS "R" FUSE REJECTION FEATURE AND SHALL BE BRACED TO WITHSTAND 200,000 AMPERE RMSSYMMETRICAL FAULT CURRENT. SAFETY SWITCHES SHALL CONFORM TO FEDERAL SPECIFICATION W-S-865.3.PROVIDE HEAVY-DUTY TYPE, SHEET ENCLOSED, SAFETY SWITCHES. THE TYPE, SIZE, AND RATING SHALL BE AS INDICATED ON THE DRAWINGSOR AS REQUIRED BY THE MOTOR OR EQUIPMENT SERVED. THE ENCLOSURE FOR DISCONNECT SWITCHES SHALL BE NEMA TYPE 1 FOR INDOORUSE, NEMA TYPE 4X FOR OUTDOOR USE AND NEMA TYPE 7 FOR EXPLOSION PROOF USE. DISCONNECTS SHALL BE MANUFACTURED BYALLEN-BRADLEY, GENERAL ELECTRIC, CUTLER-HAMMER APPROVED EQUAL.4.SWITCHES SHALL INCORPORATE QUICK-MAKE, QUICK-BREAK OPERATING HANDLES. THE MECHANISM SHALL BE AN INTEGRAL PART OF THEBOX, NOT THE COVER, AND SWITCHES SHALL HAVE A COVER INTERLOCK TO PREVENT UNAUTHORIZED OPENING OF THE SWITCH DOOR IN THEON POSITION OR CLOSING OF THE SWITCH MECHANISM WITH THE DOOR OPEN. CURRENT CARRYING PARTS SHALL BE CONSTRUCTED OFHIGH-CONDUCTIVITY COPPER WITH SILVER-TUNGSTEN TYPE SWITCH CONTACT.5.FUSE CLIPS SHALL BE POSITIVE PRESSURE TYPE REINFORCED FUSE CLIPS.6.THE ELECTRICAL CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT ALL POWER WIRING TO ALL MECHANICAL CONTRACTOR FURNISHEDEQUIPMENT. THE MECHANICAL CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT ALL CONTROL WIRING TO ALL FURNISHED EQUIPMENT,INCLUDING CONTROL DEVICES, STARTERS AND INTEGRAL DISCONNECT SWITCHES OF CONTRACTOR FURNISHED EQUIPMENTCHECK, TEST, START, ADJUST, BALANCE AND INSTRUCTIONS (230593)1.AFTER INSTALLATION, CHECK ALL EQUIPMENT, AND PERFORM START UP IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.2.ALL PIPING SHALL BE TESTED AND FREE OF LEAKS.3.CONCEALED OR INSULATED WORK SHALL REMAIN UNCOVERED UNTIL REQUIRED TESTS HAVE BEEN COMPLETED, BUT IF CONSTRUCTIONSCHEDULE REQUIRES IT, ARRANGE FOR PRIOR TESTS ON PARTS OF SYSTEM AS APPROVED BY THE TENANT.123456781011121314151617BA91234567810111213141516179DrawnProject ManagerCheckedContract Drawing DateProject NumberQPNMLKJHGFEDCBA18191819QPNMLKJHGFEDCB202120212222TSRTSRRevit Template Versionv16: 2017.10.05This document is the product and property of Baxter Hodell Donnelly Preston, Inc. Neither the document nor the information itcontains may be copied or used for other than the specific project for which it was prepared without the written consent of BaxterHodell Donnelly Preston, Inc. CINCINNATI COLUMBUS RALEIGH PITTSBURGH ATLANTA LAWRENCE DIGENNARO, ARCHITECT 302 WEST THIRD STREET SUITE 500 CINCINNATI, OHIO 45202 PHONE 513.271.1634HIG02.21THE HARTFORD GROUP - 3RD FLOOR RENOVATION 501 PENNSYLVANIA PKWY #400 INDIANAPOLIS, IN 46280 No.Issue/Revision/Submission Date 1 ISSUED FOR BID AND PERMIT 12/14/20182016.05.27M002MECHANICAL SPECIFICATIONSAABJRHDCP