HomeMy WebLinkAboutE003 - Electrical Specifications3.1INSTALLATIONA.COORDINATE LAYOUT AND INSTALLATION OF PANELBOARDS ANDCOMPONENTS WITH OTHER CONSTRUCTION THAT PENETRATESWALLS OR IS SUPPORTED BY THEM, INCLUDING ELECTRICAL ANDOTHER TYPES OF EQUIPMENT, RACEWAYS, PIPING, ENCUMBRANCESTO WORKSPACE CLEARANCE REQUIREMENTS, AND ADJACENTSURFACES. MAINTAIN REQUIRED WORKSPACE CLEARANCES ANDREQUIRED CLEARANCES FOR EQUIPMENT ACCESS DOORS ANDPANELS.B.COMPLY WITH NECA 1. INSTALL PANELBOARDS AND ACCESSORIESACCORDING TO NECA 407 AND NEMA PB 1.1.C.MOUNT TOP OF TRIM 90 INCHES ABOVE FINISHED FLOOR UNLESSOTHERWISE INDICATED.SECTION 262726 - WIRING DEVICESPART 1 - GENERAL1.1SUBMITTALSA.PRODUCT DATA: FOR EACH TYPE OF PRODUCT.PART 2 - PRODUCTS2.1GENERAL WIRING-DEVICE REQUIREMENTSA.WIRING DEVICES, COMPONENTS, AND ACCESSORIES: LISTED ANDLABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY,AND MARKED FOR INTENDED LOCATION AND APPLICATION.B.DEVICES THAT ARE MANUFACTURED FOR USE WITH MODULARPLUG-IN CONNECTORS MAY BE SUBSTITUTED UNDER THEFOLLOWING CONDITIONS:A.CONNECTORS SHALL COMPLY WITH UL 2459 AND SHALL BE MADEWITH STRANDING BUILDING WIRE.B.DEVICES SHALL COMPLY WITH THE REQUIREMENTS IN THIS SECTION.C.DEVICES FOR OWNER-FURNISHED EQUIPMENT: RECEPTACLES: MATCHPLUG CONFIGURATIONS. CORD AND PLUG SETS: MATCH EQUIPMENTREQUIREMENTS.D.SOURCE LIMITATIONS: OBTAIN EACH TYPE OF WIRING DEVICE ANDASSOCIATED WALL PLATE FROM SINGLE SOURCE FROM SINGLEMANUFACTURER. ACCEPTABLE MANUFACTURERS ARE EATON,HUBBELL, PASS & SEYMOUR, AND LEVITON, UNLESS OTHERWISENOTED.2.2STRAIGHT-BLADE RECEPTACLESA.DUPLEX CONVENIENCE RECEPTACLES: 125 V, 20 A; COMPLY WITHNEMA WD 1, NEMA WD 6 CONFIGURATION 5-20R, UL 498, ANDFS W-C-596.B.ISOLATED-GROUND, DUPLEX CONVENIENCE RECEPTACLES: 125 V,20 A; COMPLY WITH NEMA WD 1, NEMA WD 6 CONFIGURATION 5-20R,UL 498, AND FS W-C-596.1.DESCRIPTION: STRAIGHT BLADE; EQUIPMENT GROUNDINGCONTACTS SHALL BE CONNECTED ONLY TO THE GREENGROUNDING SCREW TERMINAL OF THE DEVICE AND WITHINHERENT ELECTRICAL ISOLATION FROM MOUNTING STRAP.ISOLATION SHALL BE INTEGRAL TO RECEPTACLECONSTRUCTION AND NOT DEPENDENT ON REMOVABLE PARTS.2.3USB CHARGER DEVICESA.TAMPER-RESISTANT, USB CHARGER RECEPTACLES: 12 V DC, 2.0 A,USB DUAL TYPE A; COMPLY WITH NEMA WD 1, NEMA WD 6CONFIGURATION 5-20R, UL 498, UL 1310, AND FS W-C-596.1.DESCRIPTION: SINGLE-PIECE, RIVETLESS, NICKEL-PLATED,ALL-BRASS GROUNDING SYSTEM. NICKEL-PLATED, BRASSMOUNTING STRAP.2.4GFCI RECEPTACLESA.DUPLEX RECEPTACLE, 125 V, 20 A, STRAIGHT BLADE,NON-FEED-THROUGH TYPE.COMPLY WITH NEMA WD 1, NEMA WD 6 CONFIGURATION 5-20R,UL 498, UL 943 CLASS A, AND FS W-C-596.INCLUDE INDICATOR LIGHT THAT SHOWS WHEN THE GFCI HASMALFUNCTIONED AND NO LONGER PROVIDES PROPER GFCIPROTECTION.2.5TWIST-LOCKING RECEPTACLESA.TWIST-LOCK, SINGLE CONVENIENCE RECEPTACLES: 125 V, 20 A;COMPLY WITH NEMA WD 1, NEMA WD 6 CONFIGURATION L5-20R, ANDUL 498.2.6PENDANT CORD-CONNECTOR DEVICESA.DESCRIPTION:1.MATCHING, LOCKING-TYPE PLUG AND RECEPTACLE BODYCONNECTOR.2.NEMA WD 6 CONFIGURATIONS L5-20P AND L5-20R,HEAVY-DUTY GRADE, AND FS W-C-596.3.BODY: NYLON, WITH SCREW-OPEN, CABLE-GRIPPING JAWSAND PROVISION FOR ATTACHING EXTERNAL CABLE GRIP.4.EXTERNAL CABLE GRIP: WOVEN WIRE-MESH TYPE MADE OFHIGH-STRENGTH, GALVANIZED-STEEL WIRE STRAND, MATCHEDTO CABLE DIAMETER, AND WITH ATTACHMENT PROVISIONDESIGNED FOR CORRESPONDING CONNECTOR.2.7CORD AND PLUG SETSA.DESCRIPTION:1.MATCH VOLTAGE AND CURRENT RATINGS AND NUMBER OFCONDUCTORS TO REQUIREMENTS OF EQUIPMENT BEINGCONNECTED.2.CORD: RUBBER-INSULATED, STRANDED-COPPER CONDUCTORS,WITH TYPE SOW-A JACKET; WITH GREEN-INSULATEDGROUNDING CONDUCTOR AND AMPACITY OF AT LEAST 130PERCENT OF THE EQUIPMENT RATING.3.PLUG: NYLON BODY AND INTEGRAL CABLE-CLAMPING JAWS.MATCH CORD AND RECEPTACLE TYPE FOR CONNECTION.2.8TOGGLE SWITCHESA.COMPLY WITH NEMA WD 1, UL 20, AND FS W-S-896.B.SWITCHES, 120/277 V, 20 A:C.PILOT-LIGHT SWITCHES: 120/277 V, 20 A.1.DESCRIPTION: SINGLE POLE, WITH LED-LIGHTED HANDLE,ILLUMINATED WHEN SWITCH IS OFF.2.KEY-OPERATED SWITCHES: 120/277 V, 20 A.3.`DESCRIPTION: SINGLE POLE, WITH FACTORY-SUPPLIED KEY INLIEU OF SWITCH HANDLE.2.9WALL SWITCH SENSOR LIGHT SWITCH, DUAL TECHNOLOGYA.DESCRIPTION: SWITCHBOX-MOUNTED, COMBINATIONLIGHTING-CONTROL SENSOR AND CONVENTIONAL SWITCHLIGHTING-CONTROL UNIT USING DUAL TECHNOLOGY. ADJUSTABLETIME DELAY OF 20 MINUTES. ABLE TO BE LOCKED TO AUTOMATIC-ONOR MANUAL-ON MODE. COMPLY WITH NEMA WD 1, UL 20, ANDFS W-S-896.2.10WALL PLATESA.SINGLE AND COMBINATION TYPES SHALL MATCH CORRESPONDINGWIRING DEVICES.B.PLATE-SECURING SCREWS: METAL WITH HEAD COLOR TO MATCHPLATE FINISH.C.MATERIAL FOR FINISHED SPACES: SMOOTH, HIGH-IMPACTTHERMOPLASTIC.D.MATERIAL FOR UNFINISHED SPACES: SMOOTH, HIGH-IMPACTTHERMOPLASTIC.E.MATERIAL FOR DAMP LOCATIONS: THERMOPLASTIC WITHSPRING-LOADED LIFT COVER, AND LISTED AND LABELED FOR USE INWET AND DAMP LOCATIONS.F.WET-LOCATION, WEATHERPROOF COVER PLATES: NEMA 250,COMPLYING WITH TYPE 3R, WEATHER-RESISTANT THERMOPLASTICWITH LOCKABLE COVER.2.11FLOOR SERVICE FITTINGSA.TYPE: MODULAR, DUAL-SERVICE UNITS SUITABLE FOR WIRINGMETHOD USED. TYPE AS INDICATED ON DRAWINGS.B.COMPARTMENTS: BARRIER SEPARATES POWER FROM VOICE ANDDATA COMMUNICATION CABLING.C.SERVICE PLATE: AS INDICATED BY ARCHITECT WITH SATIN FINISH.D.POWER RECEPTACLE: NEMA WD 6 CONFIGURATION 5-20R, GRAYFINISH, UNLESS OTHERWISE INDICATED.E.DATA COMMUNICATION OUTLET: AS DIRECTED BY THE OWNER.2.12POKE-THROUGH ASSEMBLIESA.DESCRIPTION:1.FACTORY-FABRICATED AND -WIRED ASSEMBLY OFBELOW-FLOOR JUNCTION BOX WITH MULTICHANNELED,THROUGH-FLOOR RACEWAY/FIRESTOP UNIT AND DETACHABLEMATCHING FLOOR SERVICE-OUTLET ASSEMBLY.2.COMPLY WITH UL 514 SCRUB WATER EXCLUSIONREQUIREMENTS.3.SERVICE-OUTLET ASSEMBLY: TYPE AS INDICATED ONDRAWINGS.4.SIZE: SELECTED TO FIT NOMINAL CORED HOLES IN FLOOR ANDMATCHED TO FLOOR THICKNESS.5.FIRE RATING: UNIT IS LISTED AND LABELED FOR FIRE RATING OFFLOOR-CEILING ASSEMBLY.6.CLOSURE PLUG: ARRANGED TO CLOSE UNUSED COREDOPENINGS AND REESTABLISH FIRE RATING OF FLOOR.2.13FINISHESA.DEVICE COLOR:1.WIRING DEVICES CONNECTED TO NORMAL POWER SYSTEM: ASSELECTED BY ARCHITECT UNLESS OTHERWISE INDICATED ORREQUIRED BY NFPA 70 OR DEVICE LISTING.2.WIRING DEVICES CONNECTED TO EMERGENCY POWER SYSTEM:RED3.ISOLATED-GROUND RECEPTACLES: AS SPECIFIED ABOVE, WITHORANGE TRIANGLE ON FACE.A.WALL PLATE COLOR: FOR PLASTIC COVERS, MATCH DEVICE COLOR.PART 3 - EXECUTION3.1INSTALLATIONA.COMPLY WITH NECA 1, INCLUDING MOUNTING HEIGHTS LISTED INTHAT STANDARD, UNLESS OTHERWISE INDICATED.B.COORDINATION WITH OTHER TRADES:1.PROTECT INSTALLED DEVICES AND THEIR BOXES. DO NOTPLACE WALL FINISH MATERIALS OVER DEVICE BOXES AND DONOT CUT HOLES FOR BOXES WITH ROUTERS THAT ARE GUIDEDBY RIDING AGAINST OUTSIDE OF BOXES.2.KEEP OUTLET BOXES FREE OF PLASTER, DRYWALL JOINTCOMPOUND, MORTAR, CEMENT, CONCRETE, DUST, PAINT, ANDOTHER MATERIAL THAT MAY CONTAMINATE THE RACEWAYSYSTEM, CONDUCTORS, AND CABLES.3.INSTALL DEVICE BOXES IN BRICK OR BLOCK WALLS SO THATTHE COVER PLATE DOES NOT CROSS A JOINT UNLESS THEJOINT IS TROWELED FLUSH WITH THE FACE OF THE WALL.4.INSTALL WIRING DEVICES AFTER ALL WALL PREPARATION,INCLUDING PAINTING, IS COMPLETE.C.CONDUCTORS:1.DO NOT STRIP INSULATION FROM CONDUCTORS UNTIL RIGHTBEFORE THEY ARE SPLICED OR TERMINATED ON DEVICES.2.STRIP INSULATION EVENLY AROUND THE CONDUCTOR USINGTOOLS DESIGNED FOR THE PURPOSE. AVOID SCORING ORNICKING OF SOLID WIRE OR CUTTING STRANDS FROMSTRANDED WIRE.3.THE LENGTH OF FREE CONDUCTORS AT OUTLETS FOR DEVICESSHALL MEET PROVISIONS OF NFPA 70, ARTICLE 300, WITHOUTPIGTAILS.D.EXISTING CONDUCTORS:a.CUT BACK AND PIGTAIL, OR REPLACE ALL DAMAGEDCONDUCTORS.b.STRAIGHTEN CONDUCTORS THAT REMAIN AND REMOVECORROSION AND FOREIGN MATTER.c.PIGTAILING EXISTING CONDUCTORS IS PERMITTED,PROVIDED THE OUTLET BOX IS LARGE ENOUGH.E.DEVICE INSTALLATION:1.REPLACE DEVICES THAT HAVE BEEN IN TEMPORARY USEDURING CONSTRUCTION AND THAT WERE INSTALLED BEFOREBUILDING FINISHING OPERATIONS WERE COMPLETE.2.KEEP EACH WIRING DEVICE IN ITS PACKAGE OR OTHERWISEPROTECTED UNTIL IT IS TIME TO CONNECT CONDUCTORS.3.DO NOT REMOVE SURFACE PROTECTION, SUCH AS PLASTICFILM AND SMUDGE COVERS, UNTIL THE LAST POSSIBLEMOMENT.4.CONNECT DEVICES TO BRANCH CIRCUITS USING PIGTAILS THATARE NOT LESS THAN 6 INCHES (152 MM) IN LENGTH.5.WHEN THERE IS A CHOICE, USE SIDE WIRING WITHBINDING-HEAD SCREW TERMINALS. WRAP SOLID CONDUCTORTIGHTLY CLOCKWISE, TWO-THIRDS TO THREE-FOURTHS OF THEWAY AROUND TERMINAL SCREW.6.USE A TORQUE SCREWDRIVER WHEN A TORQUE ISRECOMMENDED OR REQUIRED BY MANUFACTURER.7.WHEN CONDUCTORS LARGER THAN NO. 12 AWG ARE INSTALLEDON 15- OR 20-A CIRCUITS, SPLICE NO. 12 AWG PIGTAILS FORDEVICE CONNECTIONS.8.TIGHTEN UNUSED TERMINAL SCREWS ON THE DEVICE.9.WHEN MOUNTING INTO METAL BOXES, REMOVE THE FIBER ORPLASTIC WASHERS USED TO HOLD DEVICE-MOUNTING SCREWSIN YOKES, ALLOWING METAL-TO-METAL CONTACT.F.RECEPTACLE ORIENTATION:INSTALL GROUND PIN OF VERTICALLY MOUNTED RECEPTACLES UP,AND ON HORIZONTALLY MOUNTED RECEPTACLES TO THE RIGHT.G.DEVICE PLATES: DO NOT USE OVERSIZED OR EXTRA-DEEP PLATES.REPAIR WALL FINISHES AND REMOUNT OUTLET BOXES WHENSTANDARD DEVICE PLATES DO NOT FIT FLUSH OR DO NOT COVERROUGH WALL OPENING.H.ARRANGEMENT OF DEVICES: UNLESS OTHERWISE INDICATED,MOUNT FLUSH, WITH LONG DIMENSION VERTICAL AND WITHGROUNDING TERMINAL OF RECEPTACLES ON TOP. GROUP ADJACENTSWITCHES UNDER SINGLE, MULTIGANG WALL PLATES.I.ADJUST LOCATIONS OF FLOOR SERVICE OUTLETS AND SERVICEPOLES TO SUIT ARRANGEMENT OF PARTITIONS AND FURNISHINGS.3.2IDENTIFICATIONA.IDENTIFY EACH RECEPTACLE WITH PANELBOARD IDENTIFICATION ANDCIRCUIT NUMBER. USE HOT, STAMPED, OR ENGRAVED MACHINEPRINTING WITH BLACK-FILLED LETTERING ON FACE OF PLATE, ANDDURABLE WIRE MARKERS OR TAGS INSIDE OUTLET BOXES.SECTION 262813 - FUSESPART 1 - GENERAL1.1SUBMITTALSA.PRODUCT DATA: FOR EACH TYPE OF PRODUCT. INCLUDECONSTRUCTION DETAILS, MATERIAL DESCRIPTIONS, DIMENSIONS OFINDIVIDUAL COMPONENTS AND PROFILES, AND FINISHES FORSPARE-FUSE CABINETS.1.2MAINTENANCE MATERIAL SUBMITTALSA.FURNISH EXTRA MATERIALS THAT MATCH PRODUCTS INSTALLED ANDTHAT ARE PACKAGED WITH PROTECTIVE COVERING FOR STORAGEAND IDENTIFIED WITH LABELS DESCRIBING CONTENTS.1.FUSES: EQUAL TO 10 PERCENT OF QUANTITY INSTALLED FOREACH SIZE AND TYPE, BUT NO FEWER THAN THREE OF EACHSIZE AND TYPE.PART 2 - PRODUCTS2.1MANUFACTURERSA.SOURCE LIMITATIONS: OBTAIN FUSES, FOR USE WITHIN A SPECIFICPRODUCT OR CIRCUIT, FROM SINGLE SOURCE FROM SINGLEMANUFACTURER.2.2CARTRIDGE FUSESA.CHARACTERISTICS: NEMA FU 1, CURRENT-LIMITING, NONRENEWABLECARTRIDGE FUSES WITH VOLTAGE RATINGS CONSISTENT WITHCIRCUIT VOLTAGES.B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTEDAND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTINGAGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.C.COMPLY WITH NEMA FU 1 FOR CARTRIDGE FUSES.D.COORDINATE FUSE RATINGS WITH UTILIZATION EQUIPMENTNAMEPLATE LIMITATIONS OF MAXIMUM FUSE SIZE AND WITH SYSTEMSHORT-CIRCUIT CURRENT LEVELS.2.3SPARE-FUSE CABINETA.CHARACTERISTICS: WALL-MOUNTED STEEL UNIT WITH FULL-LENGTH,RECESSED PIANO-HINGED DOOR AND KEY-CODED CAM LOCK ANDPULL.1.SIZE: ADEQUATE FOR STORAGE OF SPARE FUSES SPECIFIEDWITH 15 PERCENT SPARE CAPACITY MINIMUM.2.FINISH: GRAY, BAKED ENAMEL.3.IDENTIFICATION: "SPARE FUSES" IN 1-1/2-INCH- (38-MM-) HIGHLETTERS ON EXTERIOR OF DOOR.4.FUSE PULLERS: FOR EACH SIZE OF FUSE, WHERE APPLICABLEAND AVAILABLE, FROM FUSE MANUFACTURER.PART 3 - EXECUTION3.1FUSE APPLICATIONSA.CARTRIDGE FUSES:1.SERVICE ENTRANCE: CLASS L, FAST ACTING2.FEEDERS: CLASS RK1, FAST ACTING3.MOTOR BRANCH CIRCUITS: CLASS RK1, TIME DELAY.4.LARGE MOTOR BRANCH (601-4000 A): CLASS L, TIME DELAY.5.OTHER BRANCH CIRCUITS: CLASS RK1, TIME DELAY6.ELEVATOR POWER MODULES: CLASS J3.2INSTALLATIONA.INSTALL FUSES IN FUSIBLE DEVICES. ARRANGE FUSES SO RATINGINFORMATION IS READABLE WITHOUT REMOVING FUSE.B.INSTALL SPARE-FUSE CABINET(S) IN LOCATION SHOWN ON THEDRAWINGS OR AS INDICATED IN THE FIELD BY OWNER.SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERSPART 1 - GENERAL1.1SUBMITTALSA.PRODUCT DATA: FOR EACH TYPE OF ENCLOSED SWITCH, CIRCUITBREAKER, ACCESSORY, AND COMPONENT INDICATED. INCLUDENAMEPLATE RATINGS, DIMENSIONED ELEVATIONS, SECTIONS,WEIGHTS, AND MANUFACTURERS' TECHNICAL DATA ON FEATURES,PERFORMANCE, ELECTRICAL CHARACTERISTICS, RATINGS,ACCESSORIES, AND FINISHES.1.2MAINTENANCE MATERIAL SUBMITTALSA.FURNISH EXTRA MATERIALS THAT MATCH PRODUCTS INSTALLED ANDTHAT ARE PACKAGED WITH PROTECTIVE COVERING FOR STORAGEAND IDENTIFIED WITH LABELS DESCRIBING CONTENTS.1.FUSES: EQUAL TO 10 PERCENT OF QUANTITY INSTALLED FOREACH SIZE AND TYPE, BUT NO FEWER THAN THREE OF EACHSIZE AND TYPE.PART 2 - PRODUCTS2.1GENERAL REQUIREMENTSA.SOURCE LIMITATIONS: OBTAIN ENCLOSED SWITCHES AND CIRCUITBREAKERS, OVERCURRENT PROTECTIVE DEVICES, COMPONENTS,AND ACCESSORIES, WITHIN SAME PRODUCT CATEGORY, FROMSINGLE MANUFACTURER.B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTEDAND LABELED AS DEFINED IN NFPA 70, BY AN NRTL, AND MARKEDFOR INTENDED LOCATION AND APPLICATION.C.ACCEPTABLE MANUFACTURERS ARE EATON, SIEMENS, SQUARE D,AND GE.2.2FUSIBLE SWITCHESA.FUSIBLE SWITCH, 800 A AND SMALLER: NEMA KS 1, TYPE HD, WITHCLIPS OR BOLT PADS TO ACCOMMODATE SPECIFIED FUSES,LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT TWO PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED POSITION.B.ACCESSORIES:1.EQUIPMENT GROUND KIT: INTERNALLY MOUNTED AND LABELEDFOR COPPER AND ALUMINUM GROUND CONDUCTORS.2.NEUTRAL KIT: INTERNALLY MOUNTED; INSULATED, CAPABLE OFBEING GROUNDED, AND BONDED; AND LABELED FOR COPPERAND ALUMINUM NEUTRAL CONDUCTORS.3.AUXILIARY CONTACT KIT: AUXILIARY SET OF CONTACTSARRANGED TO OPEN BEFORE SWITCH BLADES OPEN. PROVIDEWHEN USED AS REMOTE DISCONNECT FOR VARIABLEFREQUENCY MOTOR CONTROLLER CIRCUITS.4.SERVICE-RATED SWITCHES: LABELED FOR USE AS SERVICEEQUIPMENT.2.3NONFUSIBLE SWITCHESA.NONFUSIBLE SWITCH, 800 A AND SMALLER: NEMA KS 1, TYPE HD,LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT TWO PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED POSITION.B.ACCESSORIES:1.EQUIPMENT GROUND KIT: INTERNALLY MOUNTED AND LABELEDFOR COPPER AND ALUMINUM GROUND CONDUCTORS.2.NEUTRAL KIT: INTERNALLY MOUNTED; INSULATED, CAPABLE OFBEING GROUNDED, AND BONDED; AND LABELED FOR COPPERAND ALUMINUM NEUTRAL CONDUCTORS.3.AUXILIARY CONTACT KIT: AUXILIARY SET OF CONTACTSARRANGED TO OPEN BEFORE SWITCH BLADES OPEN. PROVIDEWHEN USED AS REMOTE DISCONNECT FOR VARIABLEFREQUENCY MOTOR CONTROLLER CIRCUITS.4.SERVICE-RATED SWITCHES: LABELED FOR USE AS SERVICEEQUIPMENT.2.4MOLDED-CASE CIRCUIT BREAKERSA.MOLDED-CASE CIRCUIT BREAKER: NEMA AB 1, WITH INTERRUPTINGCAPACITY TO MEET AVAILABLE FAULT CURRENTS.1.THERMAL-MAGNETIC CIRCUIT BREAKERS: INVERSETIME-CURRENT ELEMENT FOR LOW-LEVEL OVERLOADS ANDINSTANTANEOUS MAGNETIC TRIP ELEMENT FOR SHORTCIRCUITS. ADJUSTABLE MAGNETIC TRIP SETTING FORCIRCUIT-BREAKER FRAME SIZES 250 A AND LARGER.2.ADJUSTABLE INSTANTANEOUS-TRIP CIRCUIT BREAKERS:MAGNETIC TRIP ELEMENT WITH FRONT-MOUNTED,FIELD-ADJUSTABLE TRIP SETTING.3.ELECTRONIC TRIP-UNIT CIRCUIT BREAKERS: RMS SENSING;FIELD-REPLACEABLE RATING PLUG; WITH THE FOLLOWINGFIELD-ADJUSTABLE SETTINGS:a.INSTANTANEOUS TRIP.b.LONG- AND SHORT-TIME PICKUP LEVELS.c.LONG- AND SHORT-TIME TIME ADJUSTMENTS.d.GROUND-FAULT PICKUP LEVEL, TIME DELAY, AND I2TRESPONSE.B.MOLDED-CASE CIRCUIT-BREAKER FEATURES AND ACCESSORIES:1.STANDARD FRAME SIZES, TRIP RATINGS, AND NUMBER OFPOLES.2.LUGS: MECHANICAL STYLE SUITABLE FOR NUMBER, SIZE, TRIPRATINGS, AND CONDUCTOR MATERIAL.3.APPLICATION LISTING: HACR FOR HEATING, AIR-CONDITIONING,AND REFRIGERATING EQUIPMENT.4.GROUND-FAULT PROTECTION: INTEGRALLY MOUNTED RELAYAND TRIP UNIT WITH ADJUSTABLE PICKUP AND TIME-DELAYSETTINGS, PUSH-TO-TEST FEATURE, AND GROUND-FAULTINDICATOR.5.SHUNT TRIP: 120-V TRIP COIL ENERGIZED FROM SEPARATECIRCUIT, SET TO TRIP AT 55 PERCENT OF RATED VOLTAGE.6.UNDERVOLTAGE TRIP: SET TO OPERATE AT 35 TO 75 PERCENTOF RATED VOLTAGE WITHOUT INTENTIONAL OR WITHFIELD-ADJUSTABLE 0.1- TO 0.6-SECOND TIME DELAY.7.AUXILIARY SWITCH: ONE SPDT SWITCH OR TWO SPDTSWITCHES WITH "A" AND "B" CONTACTS; "A" CONTACTS MIMICCIRCUIT-BREAKER CONTACTS, "B" CONTACTS OPERATE INREVERSE OF CIRCUIT-BREAKER CONTACTS.2.5ENCLOSURESA.NEMA AB 1 AND NEMA KS 1 TO MEET ENVIRONMENTAL CONDITIONS OFINSTALLED LOCATION.1.INDOOR LOCATIONS: NEMA 250, TYPE 1.2.OUTDOOR LOCATIONS: NEMA 250, TYPE 3R.3.OTHER WET OR DAMP INDOOR LOCATIONS: NEMA 250, TYPE 4.B.CONDUIT ENTRY: NEMA 250 TYPES 4, 4X, AND 12 ENCLOSURES SHALLCONTAIN NO KNOCKOUTS. NEMA 250 TYPES 7 AND 9 ENCLOSURESSHALL BE PROVIDED WITH THREADED CONDUIT OPENINGS IN BOTHENDWALLS.C.ENCLOSURES DESIGNATED AS NEMA 250 TYPE 4, 4X STAINLESSSTEEL, 12, OR 12K SHALL HAVE A DUAL COVER INTERLOCKMECHANISM TO PREVENT UNINTENTIONAL OPENING OF THEENCLOSURE COVER WHEN THE CIRCUIT BREAKER IS ON AND TOPREVENT TURNING THE CIRCUIT BREAKER ON WHEN THE ENCLOSURECOVER IS OPEN.D.ALL ENCLOSURES SHALL INCLUDE A BONDED EQUIPMENT BUS.PART 3 - EXECUTION3.1INSTALLATIONA.COORDINATE LAYOUT AND INSTALLATION OF SWITCHES, CIRCUITBREAKERS, AND COMPONENTS WITH EQUIPMENT SERVED ANDADJACENT SURFACES. MAINTAIN REQUIRED WORKSPACECLEARANCES AND REQUIRED CLEARANCES FOR EQUIPMENT ACCESSDOORS AND PANELS.B.INSTALL INDIVIDUAL WALL-MOUNTED SWITCHES AND CIRCUITBREAKERS WITH TOPS AT UNIFORM HEIGHT UNLESS OTHERWISEINDICATED.C.INSTALL FUSES IN FUSIBLE DEVICES.D.COMPLY WITH NFPA 70 AND NECA 1.SECTION 265119 - LED LIGHTINGPART 1 - PART 1 - GENERAL1.1SUBMITTALSA.PRODUCT DATA: FOR EACH TYPE OF PRODUCT.B.PRODUCT SCHEDULE: FOR LUMINAIRES AND LAMPS. USE SAMEDESIGNATIONS INDICATED ON DRAWINGS.1.2QUALITY ASSURANCEA.LUMINAIRE PHOTOMETRIC DATA TESTING LABORATORYQUALIFICATIONS: PROVIDED BY AN INDEPENDENT AGENCY, WITH THEEXPERIENCE AND CAPABILITY TO CONDUCT THE TESTING INDICATED,THAT IS AN NRTL AS DEFINED BY OSHA IN 29 CFR 1910.7, ACCREDITEDUNDER THE NVLAP FOR ENERGY EFFICIENT LIGHTING PRODUCTS,AND COMPLYING WITH THE APPLICABLE IES TESTING STANDARDS.B.PROVIDE LUMINAIRES FROM A SINGLE MANUFACTURER FOR EACHLUMINAIRE TYPE.C.EACH LUMINAIRE TYPE SHALL BE BINNED WITHIN A THREE-STEPMACADAM ELLIPSE TO ENSURE COLOR CONSISTENCY AMONGLUMINAIRES.D.MOCKUPS: FOR INTERIOR LUMINAIRES IN ROOM OR MODULEMOCKUPS, COMPLETE WITH POWER AND CONTROL CONNECTIONS.1.OBTAIN ARCHITECT'S APPROVAL OF LUMINAIRES IN MOCKUPSBEFORE STARTING INSTALLATIONS.2.MAINTAIN MOCKUPS DURING CONSTRUCTION IN ANUNDISTURBED CONDITION AS A STANDARD FOR JUDGING THECOMPLETED WORK.3.APPROVAL OF MOCKUPS DOES NOT CONSTITUTE APPROVAL OFDEVIATIONS FROM THE CONTRACT DOCUMENTS CONTAINED INMOCKUPS UNLESS ARCHITECT SPECIFICALLY APPROVES SUCHDEVIATIONS IN WRITING.4.SUBJECT TO COMPLIANCE WITH REQUIREMENTS, APPROVEDMOCKUPS MAY BECOME PART OF THE COMPLETED WORK IFUNDISTURBED AT TIME OF SUBSTANTIAL COMPLETION.1.3DELIVERY, STORAGE, AND HANDLINGA.PROTECT FINISHES OF EXPOSED SURFACES BY APPLYING ASTRIPPABLE, TEMPORARY PROTECTIVE COVERING BEFORE SHIPPING.1.4WARRANTYA.WARRANTY: MANUFACTURER AND INSTALLER AGREE TO REPAIR ORREPLACE COMPONENTS OF LUMINAIRES THAT FAIL IN MATERIALS ORWORKMANSHIP WITHIN SPECIFIED WARRANTY PERIOD. WARRANTYPERIOD: FIVE YEAR(S) FROM DATE OF SUBSTANTIAL COMPLETION.PART 2 - PRODUCTS2.1LUMINAIRE REQUIREMENTSA.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTEDAND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTINGAGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.B.CRI AS INDICATED IN LIGHTING FIXTURE SCHEDULE. CCT ASINDICATED IN LIGHTING FIXTURE SCHEDULE.C.RATED LAMP LIFE OF 50,000 HOURS TO L70.D.LAMPS DIMMABLE FROM 100 PERCENT TO 0 PERCENT OF MAXIMUMLIGHT OUTPUT.E.INTERNAL DRIVER.F.NOMINAL OPERATING VOLTAGE: AS INDICATED IN LIGHTING FIXTURESCHEDULE.2.2LUMINAIRE SUPPORTA.SINGLE-STEM HANGERS: 1/2-INCH (13-MM) STEEL TUBING WITHSWIVEL BALL FITTINGS AND CEILING CANOPY. FINISH SAME ASLUMINAIRE.B.WIRES: ASTM A 641/A 641 M, CLASS 3, SOFT TEMPER, ZINC-COATEDSTEEL, 12 GAGE (2.68 MM)C.ROD HANGERS: 3/16-INCH (5-MM) MINIMUM DIAMETER,CADMIUM-PLATED, THREADED STEEL ROD.D.HOOK HANGERS: INTEGRATED ASSEMBLY MATCHED TO LUMINAIRE,LINE VOLTAGE, AND EQUIPMENT WITH THREADED ATTACHMENT,CORD, AND LOCKING-TYPE PLUG.PART 3 - EXECUTION3.1INTERIOR LIGHTING INSTALLATIONA.COMPLY WITH NECA 1.B.INSTALL LUMINAIRES LEVEL, PLUMB, AND SQUARE WITH CEILINGSAND WALLS UNLESS OTHERWISE INDICATED.C.INSTALL LAMPS IN EACH LUMINAIRE.D.SUPPORTS:1.SIZED AND RATED FOR LUMINAIRE WEIGHT.2.ABLE TO MAINTAIN LUMINAIRE POSITION AFTER CLEANING ANDRELAMPING.3.PROVIDE SUPPORT FOR LUMINAIRE WITHOUT CAUSINGDEFLECTION OF CEILING OR WALL.4.LUMINAIRE MOUNTING DEVICES SHALL BE CAPABLE OFSUPPORTING A HORIZONTAL FORCE OF 100 PERCENT OFLUMINAIRE WEIGHT AND VERTICAL FORCE OF 400 PERCENT OFLUMINAIRE WEIGHT.E.FLUSH-MOUNTED LUMINAIRE SUPPORT:1.SECURED TO OUTLET BOX.2.ATTACHED TO CEILING STRUCTURAL MEMBERS AT FOUR POINTSEQUALLY SPACED AROUND CIRCUMFERENCE OF LUMINAIRE.3.TRIM RING FLUSH WITH FINISHED SURFACE.F.WALL-MOUNTED LUMINAIRE SUPPORT:1.ATTACHED TO STRUCTURAL MEMBERS IN WALLS.2.DO NOT ATTACH LUMINAIRES DIRECTLY TO GYPSUM BOARD.G.CEILING-MOUNTED LUMINAIRE SUPPORT:1.CEILING MOUNT WITH FOUR-POINT PENDANT MOUNT WITH5/32-INCH- (4-MM-) DIAMETER AIRCRAFT CABLE SUPPORTSADJUSTABLE TO 120 INCHES (6 M) IN LENGTH.2.CEILING MOUNT WITH HOOK MOUNT.H.SUSPENDED LUMINAIRE SUPPORT:1.PENDANTS AND RODS: WHERE LONGER THAN 48 INCHES (1200MM), BRACE TO LIMIT SWINGING.2.STEM-MOUNTED, SINGLE-UNIT LUMINAIRES: SUSPEND WITHTWIN-STEM HANGERS. SUPPORT WITH APPROVED OUTLET BOXAND ACCESSORIES THAT HOLD STEM AND PROVIDE DAMPINGOF LUMINAIRE OSCILLATIONS. SUPPORT OUTLET BOXVERTICALLY TO BUILDING STRUCTURE USING APPROVEDDEVICES.3.CONTINUOUS ROWS OF LUMINAIRES: USE TUBING OR STEM FORWIRING AT ONE POINT AND WIRE SUPPORT FOR SUSPENSIONFOR EACH UNIT LENGTH OF LUMINAIRE CHASSIS, INCLUDINGONE AT EACH END.4.DO NOT USE CEILING GRID AS SUPPORT FOR PENDANTLUMINAIRES. CONNECT SUPPORT WIRES OR RODS TO BUILDINGSTRUCTURE.I.CEILING-GRID-MOUNTED LUMINAIRES:1.SECURE TO ANY REQUIRED OUTLET BOX.2.SECURE LUMINAIRE TO THE LUMINAIRE OPENING USINGAPPROVED FASTENERS IN A MINIMUM OF FOUR LOCATIONS,SPACED NEAR CORNERS OF LUMINAIRE.3.USE APPROVED DEVICES AND SUPPORT COMPONENTS TOCONNECT LUMINAIRE TO CEILING GRID AND BUILDINGSTRUCTURE IN A MINIMUM OF FOUR LOCATIONS, SPACED NEARCORNERS OF LUMINAIRE.3.2ADJUSTINGA.OCCUPANCY ADJUSTMENTS: WHEN REQUESTED WITHIN 12 MONTHSOF DATE OF SUBSTANTIAL COMPLETION, PROVIDE ON-SITEASSISTANCE IN ADJUSTING THE DIRECTION OF AIM OF LUMINAIRESTO SUIT OCCUPIED CONDITIONS. MAKE UP TO TWO VISITS TOPROJECT DURING OTHER-THAN-NORMAL HOURS FOR THIS PURPOSE.SOME OF THIS WORK MAY BE REQUIRED DURING HOURS OFDARKNESS. ADJUST THE AIM OF LUMINAIRES IN THE PRESENCE OFTHE ARCHITECT.3.3GENERAL EXTERIOR LIGHTING INSTALLATION REQUIREMENTSA.COMPLY WITH NECA 1.B.USE FASTENING METHODS AND MATERIALS SELECTED TO RESISTSEISMIC FORCES DEFINED FOR THE APPLICATION AND APPROVED BYMANUFACTURER.C.INSTALL LAMPS IN EACH LUMINAIRE.D.FASTEN LUMINAIRE TO STRUCTURAL SUPPORT.E.SUPPORTS:1.SIZED AND RATED FOR LUMINAIRE WEIGHT.2.ABLE TO MAINTAIN LUMINAIRE POSITION AFTER CLEANING ANDRELAMPING.3.SUPPORT LUMINAIRES WITHOUT CAUSING DEFLECTION OFFINISHED SURFACE.4.LUMINAIRE-MOUNTING DEVICES SHALL BE CAPABLE OFSUPPORTING A HORIZONTAL FORCE OF 100 PERCENT OFLUMINAIRE WEIGHT AND A VERTICAL FORCE OF 400 PERCENTOF LUMINAIRE WEIGHT.F.INSTALL LUMINAIRES LEVEL, PLUMB, AND SQUARE WITH FINISHEDGRADE UNLESS OTHERWISE INDICATED. INSTALL LUMINAIRES ATHEIGHT AND AIMING ANGLE AS INDICATED ON DRAWINGS.G.COORDINATE LAYOUT AND INSTALLATION OF LUMINAIRES WITHOTHER CONSTRUCTION.H.ADJUST LUMINAIRES THAT REQUIRE FIELD ADJUSTMENT OR AIMING.3.4BOLLARD LUMINAIRE INSTALLATION:A.ALIGN UNITS FOR OPTIMUM DIRECTIONAL ALIGNMENT OF LIGHTDISTRIBUTION.1.INSTALL ON CONCRETE BASE WITH TOP 4 INCHES (100 MM)ABOVE FINISHED GRADE OR SURFACE AT LUMINAIRE LOCATION.CAST CONDUIT INTO BASE, AND SHAPE BASE TO MATCH SHAPEOF BOLLARD BASE. FINISH BY TROWELING AND RUBBINGSMOOTH.3.5INSTALLATION OF INDIVIDUAL GROUND-MOUNTED LUMINAIRESA.AIM AS INDICATED ON DRAWINGS.B.INSTALL ON CONCRETE BASE WITH TOP 4 INCHES (100 MM) ABOVEFINISHED GRADE OR SURFACE AT LUMINAIRE LOCATION. CASTCONDUIT INTO BASE, AND FINISH BY TROWELING AND RUBBINGSMOOTH.SECTION 283111 - ADDRESSABLE FIRE ALARM SYSTEMPART 1 - GENERAL1.1GENERAL DESCRIPTION - PROVIDE ADDRESSABLE DIGITAL FIREALARM SYSTEM INSTALLED AS SHOWN ON DRAWINGS ANDDESCRIBED HEREIN. THE OPERATION SHALL BE SUCH THATACTUATION OF ANY MANUAL FIRE ALARM STATION OR ANY OTHERINITIATION DEVICE SHALL CAUSE AUDIBLE/VISIBLESIGNAL DEVICES THROUGHOUT THE BUILDING TO OPERATE, SHALLCAUSE THE MAIN ANNUNCIATOR TO DISPLAY THE"ADDRESS"/"ZONE" OF THE INITIATING DEVICE UNTIL THE DEVICE ISRESTORED TO ITS NORMAL POSITION AND THE CONTROL PANEL ISRESET AND SHALL CAUSE AN ALARM SIGNAL TO BE TRANSMITTED TOA CENTRAL STATION. ALL INITIATING DEVICES SHALL BE FULLYCOMPATIBLE WITH EXISTING SYSTEMS AND SHALL BE PERMANUFACTURER'S RECOMMENDATIONS. ALL COMPONENTS SHALLBE ADDRESSABLE OR BE PROVIDED WITH ADDRESSABLE ZONEINTERFACE MODULES.1.2SUBMITTALSA.GENERAL SUBMITTAL REQUIREMENTS:1.SUBMITTALS SHALL BE APPROVED BY AUTHORITIES HAVINGJURISDICTION PRIOR TO SUBMITTING THEM TO ARCHITECT.2.SHOP DRAWINGS SHALL BE PREPARED BY PERSONS WITH THEFOLLOWING QUALIFICATIONS:a.TRAINED AND CERTIFIED BY MANUFACTURER INFIRE-ALARM SYSTEM DESIGN.b.NICET-CERTIFIED FIRE-ALARM TECHNICIAN, LEVEL IIIMINIMUM.c.LICENSED OR CERTIFIED BY AUTHORITIES HAVINGJURISDICTION.B.PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED.C.SHOP DRAWINGS: FOR FIRE-ALARM SYSTEM. INCLUDE PLANS,ELEVATIONS, SECTIONS, DETAILS, AND ATTACHMENTS TO OTHERWORK.1.COMPLY WITH RECOMMENDATIONS IN THE "DOCUMENTATION"SECTION OF THE "FUNDAMENTALS OF FIRE ALARM SYSTEMS"CHAPTER IN NFPA 72.2.INCLUDE VOLTAGE DROP CALCULATIONS FOR NOTIFICATIONAPPLIANCE CIRCUITS.3.INCLUDE BATTERY-SIZE CALCULATIONS.4.INCLUDE PERFORMANCE PARAMETERS AND INSTALLATIONDETAILS FOR EACH DETECTOR, VERIFYING THAT EACHDETECTOR IS LISTED FOR COMPLETE RANGE OF AIR VELOCITY,TEMPERATURE, AND HUMIDITY POSSIBLE WHEN AIR-HANDLINGSYSTEM IS OPERATING.5.INCLUDE AUDIO/ALARM SIGNALING-SERVICE EQUIPMENT RACKOR CONSOLE LAYOUT, GROUNDING SCHEMATIC, AMPLIFIERPOWER CALCULATION, AND SINGLE-LINE CONNECTIONDIAGRAM.6.INCLUDE FLOOR PLANS TO INDICATE FINAL OUTLET LOCATIONSSHOWING ADDRESS OF EACH ADDRESSABLE DEVICE. SHOWSIZE AND ROUTE OF CABLE AND CONDUITS.1.3QUALITY ASSURANCEA.INSTALLER QUALIFICATIONS: PERSONNEL SHALL BE TRAINED ANDCERTIFIED BY MANUFACTURER FOR INSTALLATION OF UNITSREQUIRED FOR THIS PROJECT.B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTEDAND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTINGAGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.C.NFPA CERTIFICATION: OBTAIN CERTIFICATION ACCORDING TO NFPA 72BY A UL-LISTED ALARM COMPANY.1.4EXTRA MATERIALSA.FURNISH EXTRA MATERIALS THAT MATCH PRODUCTS INSTALLED ANDTHAT ARE PACKAGED WITH PROTECTIVE COVERING FOR STORAGEAND IDENTIFIED WITH LABELS DESCRIBING CONTENTS.1.LAMPS FOR REMOTE INDICATING LAMP UNITS: QUANTITYEQUAL TO 10 PERCENT OF AMOUNT INSTALLED.2.LAMPS FOR STROBE UNITS: QUANTITY EQUAL TO 10 PERCENTOF AMOUNT INSTALLED.3.SMOKE DETECTORS, FIRE DETECTORS: QUANTITY EQUAL TO 10PERCENT OF AMOUNT OF EACH TYPE INSTALLED, BUT NOFEWER THAN 1 UNIT OF EACH TYPE.4.DETECTOR BASES: QUANTITY EQUAL TO 2 PERCENT OFAMOUNT OF EACH TYPE INSTALLED, BUT NO FEWER THAN 1UNIT OF EACH TYPE.5.KEYS AND TOOLS: ONE EXTRA SET FOR ACCESS TO LOCKEDAND TAMPERPROOFED COMPONENTS.6.AUDIBLE AND VISUAL NOTIFICATION APPLIANCES: ONE OF EACHTYPE INSTALLED.7.FUSES: TWO OF EACH TYPE INSTALLED IN THE SYSTEM.1.5SEQUENCING AND SCHEDULINGA.EXISTING FIRE-ALARM EQUIPMENT: MAINTAIN EXISTING EQUIPMENTFULLY OPERATIONAL UNTIL NEW EQUIPMENT HAS BEEN TESTED ANDACCEPTED. AS NEW EQUIPMENT IS INSTALLED, LABEL IT "NOT INSERVICE" UNTIL IT IS ACCEPTED. REMOVE LABELS FROM NEWEQUIPMENT WHEN PUT INTO SERVICE, AND LABEL EXISTINGFIRE-ALARM EQUIPMENT "NOT IN SERVICE" UNTIL REMOVED FROMTHE BUILDING.B.EQUIPMENT REMOVAL: AFTER ACCEPTANCE OF NEW FIRE-ALARMSYSTEM, REMOVE EXISTING DISCONNECTED FIRE-ALARM EQUIPMENTAND WIRING.1.6WARRANTYA.SPECIAL WARRANTY: MANUFACTURER AGREES TO REPAIR ORREPLACE FIRE-ALARM SYSTEM EQUIPMENT AND COMPONENTS THATFAIL IN MATERIALS OR WORKMANSHIP WITHIN SPECIFIED WARRANTYPERIOD.1.WARRANTY EXTENT: ALL EQUIPMENT AND COMPONENTS NOTCOVERED IN THE MAINTENANCE SERVICE AGREEMENT.2.WARRANTY PERIOD: FIVE YEARS FROM DATE OF SUBSTANTIALCOMPLETION.PART 2 - PRODUCTS2.1MANUFACTURERSMANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:1.NOTIFIER; A HONEYWELL COMPANY.2.SIEMENS BUILDING TECHNOLOGIES, INC.; FIRE SAFETYDIVISION.3.SIMPLEX GRINNELL LP; A TYCO INTERNATIONAL COMPANY.4.EDWARDS2.2SYSTEM DESCRIPTIONA.NONCODED, UL-CERTIFIED ADDRESSABLE SYSTEM, WITHMULTIPLEXED SIGNAL TRANSMISSION AND HORN/STROBEEVACUATION.B.AUTOMATIC SENSITIVITY CONTROL OF CERTAIN SMOKE DETECTORS.C.ALL COMPONENTS PROVIDED SHALL BE LISTED FOR USE WITH THESELECTED SYSTEM.D.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTEDAND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTINGAGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.2.3FIRE-ALARM CONTROL UNITA.GENERAL REQUIREMENTS FOR FIRE-ALARM CONTROL UNIT:1.FIELD-PROGRAMMABLE, MICROPROCESSOR-BASED, MODULAR,POWER-LIMITED DESIGN WITH ELECTRONIC MODULES,COMPLYING WITH UL 864 AND LISTED AND LABELED BY ANNRTL.a.SYSTEM SOFTWARE AND PROGRAMS SHALL BE HELD INNONVOLATILE FLASH, ELECTRICALLY ERASABLE,PROGRAMMABLE, READ-ONLY MEMORY, RETAINING THEINFORMATION THROUGH FAILURE OF PRIMARY ANDSECONDARY POWER SUPPLIES.b.INCLUDE A REAL-TIME CLOCK FOR TIME ANNOTATION OFEVENTS ON THE EVENT RECORDER AND PRINTER.c.PROVIDE COMMUNICATION BETWEEN THE FACP ANDREMOTE CIRCUIT INTERFACE PANELS, ANNUNCIATORS, ANDDISPLAYS.d.THE FACP SHALL BE LISTED FOR CONNECTION TO ACENTRAL-STATION SIGNALING SYSTEM SERVICE.e.PROVIDE NONVOLATILE MEMORY FOR SYSTEM DATABASE,LOGIC, AND OPERATING SYSTEM AND EVENT HISTORY.THE SYSTEM SHALL REQUIRE NO MANUAL INPUT TOINITIALIZE IN THE EVENT OF A COMPLETE POWER DOWNCONDITION. THE FACP SHALL PROVIDE A MINIMUM500-EVENT HISTORY LOG.2.ADDRESSABLE INITIATION DEVICES THAT COMMUNICATEDEVICE IDENTITY AND STATUS.a.SMOKE SENSORS SHALL ADDITIONALLY COMMUNICATESENSITIVITY SETTING AND ALLOW FOR ADJUSTMENT OFSENSITIVITY AT FIRE-ALARM CONTROL UNIT.b.TEMPERATURE SENSORS SHALL ADDITIONALLY TEST FORAND COMMUNICATE THE SENSITIVITY RANGE OF THEDEVICE.3.ADDRESSABLE CONTROL CIRCUITS FOR OPERATION OFMECHANICAL EQUIPMENT.B.ALPHANUMERIC DISPLAY AND SYSTEM CONTROLS: ARRANGED FORINTERFACE BETWEEN HUMAN OPERATOR AT FIRE-ALARM CONTROLUNIT AND ADDRESSABLE SYSTEM COMPONENTS INCLUDINGANNUNCIATION AND SUPERVISION. DISPLAY ALARM, SUPERVISORY,AND COMPONENT STATUS MESSAGES AND THE PROGRAMMING ANDCONTROL MENU.C.INITIATING-DEVICE, NOTIFICATION-APPLIANCE, AND SIGNALING-LINECIRCUITS:1.PATHWAY CLASS DESIGNATIONS: NFPA 72, CLASS B.D.PRIMARY POWER: 24-V DC OBTAINED FROM 120-V AC SERVICE AND APOWER-SUPPLY MODULE. INITIATING DEVICES, NOTIFICATIONAPPLIANCES, SIGNALING LINES, TROUBLE SIGNALS, SUPERVISORYAND DIGITAL ALARM COMMUNICATOR TRANSMITTERS SHALL BEPOWERED BY 24-V DC SOURCE.1.ALARM CURRENT DRAW OF ENTIRE FIRE-ALARM SYSTEM SHALLNOT EXCEED 80 PERCENT OF THE POWER-SUPPLY MODULERATING.E.SECONDARY POWER: 24-V DC SUPPLY SYSTEM WITH BATTERIES,AUTOMATIC BATTERY CHARGER, AND AUTOMATIC TRANSFERSWITCH.1.BATTERIES: SEALED LEAD CALCIUM.2.GENERAL DESCRIPTION - PROVIDE ADDRESSABLE DIGITAL FIREALARM SYSTEM INSTALLED AS SHOWN ON DRAWINGS ANDDESCRIBED HEREIN. THE OPERATION SHALL BE SUCH THATACTUATION OF ANY MANUAL FIRE ALARM STATION OR ANYOTHER INITIATION DEVICE SHALL CAUSE AUDIBLE/VISIBLESIGNAL DEVICES THROUGHOUT THE BUILDING TO OPERATE,SHALL CAUSE THE MAIN ANNUNCIATOR TO DISPLAY THE"ADDRESS"/"ZONE" OF THE INITIATING DEVICE UNTIL THE DEVICEIS RESTORED TO ITS NORMAL POSITION AND THE CONTROLPANEL IS RESET AND SHALL CAUSE AN ALARM SIGNAL TO BETRANSMITTED TO A CENTRAL STATION. ALL INITIATINGDEVICES SHALL BE FULLY COMPATIBLE WITH EXISTINGSYSTEMS AND SHALL BE PER MANUFACTURER'SRECOMMENDATIONS. ALL COMPONENTS SHALL BEADDRESSABLE OR BE PROVIDED WITH ADDRESSABLE ZONEINTERFACE MODULES.2.4MANUAL FIRE-ALARM BOXESA.PROVIDE NON-CODED DOUBLE ACTION MANUAL STATIONS WHERESHOWN ON THE DRAWINGS, TO BE FLUSH OR SURFACE MOUNTEDAS REQUIRED. PULL STATION ACTIVATION SHALL PROVIDE ALARMINPUT TO THE SYSTEM AND ALARM OUTPUT FROM THE SYSTEMWITHIN FOUR (4) SECONDS. THE MANUAL STATION SHALL BEEQUIPPED WITH TERMINAL STRIP AND PRESSURE STYLE SCREWTERMINALS FOR THE CONNECTION OF FIELD WIRING. HOUSINGSSHALL BE MADE OF THERMOPLASTIC MATERIAL WITH RAISED FIREALARM LETTERING AND BE COLORED RED. STATIONS THAT REQUIRETHE BREAKING OF GLASS WILL NOT BE ACCEPTABLE. SURFACEMOUNTED STATIONS WHERE INDICATED ON THE DRAWINGS SHALLBE MOUNTED USING A MANUFACTURER'S PRESCRIBED MATCHINGRED ENAMEL OUTLET BOX.2.5SYSTEM SMOKE DETECTORSA.PROVIDE PHOTOELECTRIC TYPE. DETECTORS SHALL BE LISTED FORUSE AS OPEN AREA PROTECTIVE COVERAGE AND SHALL BEINSENSITIVE TO AIR VELOCITY CHANGES. THE SMOKE DETECTORSHALL CONTAIN A MULTI-COLORED LED INDICATOR THAT WILL FLASHGREEN TO INDICATE THAT THE DETECTOR IS OPERATIONAL ANDFLASH RED WHEN THE DETECTOR IS IN ALARM. THE DETECTORSHALL BE CONTINUALLY SELF-TESTING AND SHALL BE DESIGNED TOELIMINATE CALIBRATION ERRORS ASSOCIATED WITH FIELD CLEANINGOF THE CHAMBER. DETECTOR SHALL TWIST LOCK INTO A BASEASSEMBLY WITH SCREW CLAMP TERMINALS. DETECTOR ACTIVATIONSHALL PROVIDE ALARM INPUT TO THE SYSTEM AND ALARM OUTPUTFROM THE SYSTEM WITHIN FOUR (4) SECONDS. THE DETECTORSHALL SUPPORT THE USE OF A RELAY OR LED REMOTE INDICATOR.DETECTOR SPACING AND LOCATION SHALL BE IN ACCORDANCEWITH MANUFACTURER'S RECOMMENDATIONS, THE REQUIREMENTS OFNFPA 72, AND AS INDICATED. NO DETECTOR SHALL BE LOCATEDCLOSER THAN 12 INCHES TO ANY PART OF ANY LIGHTING FIXTURENOR SHALL ANY DETECTOR BE MOUNTED CLOSER THAT 36 INCHESTO ANY AHU AIR DIFFUSER.2.6HEAT DETECTORSA.HEAT DETECTOR (SYSTEM) - THERMAL DETECTORS SHALL BE RATEDAT 135 DEGREES FIXED TEMPERATURE AND 15 DEGREES PER MINUTERATE OF RISE. DETECTORS SHALL BE CONSTRUCTED TOCOMPENSATE FOR THE THERMAL LAG INHERENT IN CONVENTIONALTYPE DETECTORS DUE TO THE THERMAL MASS, AND ALARM AT THESET POINT OF 135 DEGREES FAHRENHEIT. THE DETECTORSFURNISHED SHALL HAVE A LISTED SPACING FOR COVERAGE UP TO2,500 SQUARE FEET AND SHALL BE INSTALLED ACCORDING TO THEREQUIREMENTS OF NFPA 72 FOR OPEN AREA COVERAGE.2.7NOTIFICATION APPLIANCESA.NOTIFICATION APPLIANCES - THE HORN, STROBE OR HORN/STROBEAPPLIANCE AS INDICATED ON THE DRAWINGS SHALL BE ASYNCHRONIZED TEMPORAL HORN WITH A SYNCHRONIZED STROBELIGHT WITH MULTIPLE CANDELA TAPS TO MEET THE INTENDEDAPPLICATION. THE STROBE LIGHT TAPS SHALL BE ADJUSTABLE FOR15, 30, 75, AND 110 CANDELA. THE STROBE SHALL FLASH AT A RATEBETWEEN 1/3 AND 3 FLASHES/SECOND. THE APPLIANCE SHALL BERED FOR WALL MOUNTED AND WHITE FOR CEILING MOUNTED.CEILING MOUNTED APPLIANCES SHALL BE RATED FOR THATAPPLICATION.2.8REMOTE ANNUNCIATORA.PROVIDE ANNUNCIATOR WITH FUNCTIONS TO MATCH THOSE OFFIRE-ALARM CONTROL UNIT FOR ALARM, SUPERVISORY, ANDTROUBLE INDICATIONS. MANUAL SWITCHING FUNCTIONS SHALLMATCH THOSE OF FIRE-ALARM CONTROL UNIT, INCLUDINGACKNOWLEDGING, SILENCING, RESETTING, AND TESTING. MOUNTINGSHALL BE FLUSH CABINET, NEMA 250, TYPE 1. ALPHANUMERICDISPLAY AND LED INDICATING LIGHTS SHALL MATCH THOSE OF FIREALARM CONTROL UNIT. PROVIDE CONTROLS TO ACKNOWLEDGE,SILENCE, RESET, AND TEST FUNCTIONS FOR ALARM, SUPERVISORY,AND TROUBLE SIGNALS.2.9ADDRESSABLE INTERFACE DEVICEA.PROVIDE ADDRESSABLE INTERFACE DEVICES WITH THE FOLLOWINGFUNCTIONS:1.INCLUDE ADDRESS-SETTING MEANS ON THE MODULE.2.STORE AN INTERNAL IDENTIFYING CODE FOR CONTROL PANELUSE TO IDENTIFY THE MODULE TYPE.3.LISTED FOR CONTROLLING HVAC FAN MOTOR CONTROLLERS.B.MONITOR MODULE: MICROELECTRONIC MODULE PROVIDING ASYSTEM ADDRESS FOR ALARM-INITIATING DEVICES FOR WIREDAPPLICATIONS WITH NORMALLY OPEN CONTACTS.C.INTEGRAL RELAY: CAPABLE OF PROVIDING A DIRECT SIGNAL TOELEVATOR CONTROLLER TO INITIATE ELEVATOR RECALL OR TOCIRCUIT-BREAKER SHUNT TRIP FOR POWER SHUTDOWN.1.ALLOW THE CONTROL PANEL TO SWITCH THE RELAY CONTACTSON COMMAND.2.HAVE A MINIMUM OF TWO NORMALLY OPEN AND TWONORMALLY CLOSED CONTACTS AVAILABLE FOR FIELD WIRING.D.CONTROL MODULE:1.OPERATE NOTIFICATION DEVICES.2.OPERATE SOLENOIDS FOR USE IN SPRINKLER SERVICE.2.10DIGITAL ALARM COMMUNICATOR TRANSMITTERA.PROVIDE DIGITAL ALARM COMMUNICATOR TRANSMITTERACCEPTABLE TO THE REMOTE CENTRAL STATION AND COMPLYINGWITH UL 632.B.FUNCTIONAL PERFORMANCE: UNIT SHALL RECEIVE AN ALARM,SUPERVISORY, OR TROUBLE SIGNAL FROM FIRE-ALARM CONTROLUNIT AND AUTOMATICALLY CAPTURE TWO TELEPHONE LINE(S) ANDDIAL A PRESET NUMBER FOR A REMOTE CENTRAL STATION. WHENCONTACT IS MADE WITH CENTRAL STATION(S), SIGNALS SHALL BETRANSMITTED. IF SERVICE ON EITHER LINE IS INTERRUPTED FORLONGER THAN 45 SECONDS, TRANSMITTER SHALL INITIATE A LOCALTROUBLE SIGNAL AND TRANSMIT THE SIGNAL INDICATING LOSS OFTELEPHONE LINE TO THE REMOTE ALARM RECEIVING STATION OVERTHE REMAINING LINE. TRANSMITTER SHALL AUTOMATICALLY REPORTTELEPHONE SERVICE RESTORATION TO THE CENTRAL STATION. IFSERVICE IS LOST ON BOTH TELEPHONE LINES, TRANSMITTER SHALLINITIATE THE LOCAL TROUBLE SIGNAL.C.LOCAL FUNCTIONS AND DISPLAY AT THE DIGITAL ALARMCOMMUNICATOR TRANSMITTER SHALL INCLUDE THE FOLLOWING:1.VERIFICATION THAT BOTH TELEPHONE LINES ARE AVAILABLE.2.PROGRAMMING DEVICE.3.LED DISPLAY.4.MANUAL TEST REPORT FUNCTION AND MANUAL TRANSMISSIONCLEAR INDICATION.5.COMMUNICATIONS FAILURE WITH THE CENTRAL STATION ORFIRE-ALARM CONTROL UNIT.D.SECONDARY POWER: INTEGRAL RECHARGEABLE BATTERY ANDAUTOMATIC CHARGER.E.SELF-TEST: CONDUCTED AUTOMATICALLY EVERY 24 HOURS WITHREPORT TRANSMITTED TO CENTRAL STATION.PART 3 - EXECUTION3.1EQUIPMENT INSTALLATIONA.COMPLY WITH NFPA 72, NFPA 101, AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION FOR INSTALLATION AND TESTINGOF FIRE-ALARM EQUIPMENT. INSTALL ALL ELECTRICAL WIRING TOCOMPLY WITH REQUIREMENTS IN NFPA 70 INCLUDING, BUT NOTLIMITED TO, ARTICLE 760, "FIRE ALARM SYSTEMS."B.CONNECTING TO EXISTING EQUIPMENT: VERIFY THAT EXISTINGFIRE-ALARM SYSTEM IS OPERATIONAL BEFORE MAKING CHANGES ORCONNECTIONS.C.INSTALL WALL-MOUNTED EQUIPMENT, WITH TOPS OF CABINETS NOTMORE THAN 78 INCHES (1980 MM) ABOVE THE FINISHED FLOOR.D.MANUAL FIRE-ALARM BOXES:1.INSTALL MANUAL FIRE-ALARM BOX IN THE NORMAL PATH OFEGRESS WITHIN 60 INCHES (1520 MM) OF THE EXIT DOORWAY.2.MOUNT MANUAL FIRE-ALARM BOX ON A BACKGROUND OF ACONTRASTING COLOR.3.THE OPERABLE PART OF MANUAL FIRE-ALARM BOX SHALL BEBETWEEN 42 INCHES (1060 MM) AND 48 INCHES (1220 MM)ABOVE FLOOR LEVEL. ALL DEVICES SHALL BE MOUNTED ATTHE SAME HEIGHT UNLESS OTHERWISE INDICATED.E.SMOKE- OR HEAT-DETECTOR SPACING: COMPLY WITH NFPA 72.F.DUCT SMOKE DETECTORS: COMPLY WITH NFPA 72 AND NFPA 90A.INSTALL SAMPLING TUBES SO THEY EXTEND THE FULL WIDTH OFDUCT. TUBES MORE THAN 36 INCHES (9100 MM) LONG SHALL BESUPPORTED AT BOTH ENDS.G.SINGLE-STATION SMOKE DETECTORS: WHERE MORE THAN ONESMOKE ALARM IS INSTALLED WITHIN A DWELLING OR SUITE, THEYSHALL BE CONNECTED SO THAT THE OPERATION OF ANY SMOKEALARM CAUSES THE ALARM IN ALL SMOKE ALARMS TO SOUND.H.REMOTE STATUS AND ALARM INDICATORS: INSTALL IN A VISIBLELOCATION NEAR EACH SMOKE DETECTOR, SPRINKLER WATER-FLOWSWITCH, AND VALVE-TAMPER SWITCH THAT IS NOT READILY VISIBLEFROM NORMAL VIEWING POSITION.I.AUDIBLE ALARM-INDICATING DEVICES: INSTALL NOT LESS THAN 6INCHES (150 MM) BELOW THE CEILING. INSTALL BELLS AND HORNSON FLUSH-MOUNTED BACK BOXES WITH THE DEVICE-OPERATINGMECHANISM CONCEALED BEHIND A GRILLE. INSTALL ALL DEVICESAT THE SAME HEIGHT UNLESS OTHERWISE INDICATED.J.VISIBLE ALARM-INDICATING DEVICES: INSTALL ADJACENT TO EACHALARM BELL OR ALARM HORN AND AT LEAST 6 INCHES (150 MM)BELOW THE CEILING. INSTALL ALL DEVICES AT THE SAME HEIGHTUNLESS OTHERWISE INDICATED.K.DEVICE LOCATION-INDICATING LIGHTS: LOCATE IN PUBLIC SPACENEAR THE DEVICE THEY MONITOR.3.2PATHWAYSA.PATHWAYS SHALL BE INSTALLED IN EMT. FIRE ALARM MC CABLE ISSUITABLE ONLY WHERE NOT EXPOSED.B.FIRE ALARM BOXES SHALL BE PAINTED RED ENAMEL.C.WIRING SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THENATIONAL ELECTRIC CODE AND NFPA 72, AND ALL OTHERAPPLICABLE STATE AND LOCAL CODES. THE CONTRACTOR SHALLPROVIDE, IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS,ALL WIRING, CONDUIT, AND OUTLET BOXES REQUIRED FOR THEERECTION OF THE COMPLETE SYSTEM AS DESCRIBED HEREIN ANDAS SHOWN ON THE DRAWINGS. CONDUIT AND WIRE SHALLCONFORM TO THE APPLICABLE REQUIREMENTS FOR LIGHTING ANDRECEPTACLE BRANCH CIRCUITS. THE SIZES OF THE DIFFERENTWIRES SHALL BE AS REQUIRED FOR SYSTEM OPERATION.COLOR-CODED WIRES SHALL BE USED.3.3CONNECTIONSA.FOR FIRE-PROTECTION SYSTEMS RELATED TO DOORS IN FIRE-RATEDWALLS AND PARTITIONS AND TO DOORS IN SMOKE PARTITIONS,COMPLY WITH REQUIREMENTS IN SECTION 087100 "DOORHARDWARE." CONNECT HARDWARE AND DEVICES TO FIRE-ALARMSYSTEM.1.VERIFY THAT HARDWARE AND DEVICES ARE LISTED FOR USEWITH INSTALLED FIRE-ALARM SYSTEM BEFORE MAKINGCONNECTIONS.B.MAKE ADDRESSABLE CONNECTIONS WITH A SUPERVISED INTERFACEDEVICE TO THE FOLLOWING DEVICES AND SYSTEMS. INSTALL THEINTERFACE DEVICE LESS THAN 36 INCHES (910 MM) FROM THEDEVICE CONTROLLED. MAKE AN ADDRESSABLE CONFIRMATIONCONNECTION WHEN SUCH FEEDBACK IS AVAILABLE AT THE DEVICEOR SYSTEM BEING CONTROLLED.1.SMOKE DAMPERS IN AIR DUCTS OF DESIGNATED HVAC DUCTSYSTEMS.2.MAGNETICALLY HELD-OPEN DOORS.3.ELECTRONICALLY LOCKED DOORS AND ACCESS GATES.4.ALARM-INITIATING CONNECTION TO ELEVATOR RECALL SYSTEMAND COMPONENTS.5.ALARM-INITIATING CONNECTION TO ACTIVATE EMERGENCYLIGHTING CONTROL.6.ALARM-INITIATING CONNECTION TO ACTIVATE EMERGENCYSHUTOFFS FOR GAS AND FUEL SUPPLIES.7.SUPERVISORY CONNECTIONS AT VALVE SUPERVISORYSWITCHES.8.SUPERVISORY CONNECTIONS AT LOW-AIR-PRESSURE SWITCHOF EACH DRY-PIPE SPRINKLER SYSTEM.9.SUPERVISORY CONNECTIONS AT ELEVATOR SHUNT-TRIPBREAKER.10.SUPERVISORY CONNECTIONS AT FIRE-EXTINGUISHERLOCATIONS.3.4GROUNDINGA.GROUND FIRE-ALARM CONTROL UNIT AND ASSOCIATED CIRCUITS;COMPLY WITH IEEE 1100. INSTALL A GROUND WIRE FROM MAINSERVICE GROUND TO FIRE-ALARM CONTROL UNIT.3.5FIELD QUALITY CONTROLA.FIELD TESTS SHALL BE WITNESSED BY AUTHORITIES HAVINGJURISDICTION.B.PERFORM THE FOLLOWING TESTS AND INSPECTIONS WITH THEASSISTANCE OF A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE:1.VISUAL INSPECTION: CONDUCT VISUAL INSPECTION PRIOR TOTESTING.a.INSPECTION SHALL BE BASED ON COMPLETED RECORDDRAWINGS AND SYSTEM DOCUMENTATION THAT ISREQUIRED BY NFPA 72 IN ITS "COMPLETION DOCUMENTS,PREPARATION" TABLE IN THE "DOCUMENTATION" SECTIONOF THE "FUNDAMENTALS" CHAPTER.b.COMPLY WITH THE "VISUAL INSPECTION FREQUENCIES"TABLE IN THE "INSPECTION" SECTION OF THE "INSPECTION,TESTING AND MAINTENANCE" CHAPTER IN NFPA 72; RETAINTHE "INITIAL/REACCEPTANCE" COLUMN AND LIST ONLY THEINSTALLED COMPONENTS.2.SYSTEM TESTING: COMPLY WITH THE "TEST METHODS" TABLE INTHE "TESTING" SECTION OF THE "INSPECTION, TESTING ANDMAINTENANCE" CHAPTER IN NFPA 72.3.TEST AUDIBLE APPLIANCES FOR THE PUBLIC OPERATING MODEACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS.PERFORM THE TEST USING A PORTABLE SOUND-LEVEL METERCOMPLYING WITH TYPE 2 REQUIREMENTS IN ANSI S1.4.4.TEST AUDIBLE APPLIANCES FOR THE PRIVATE OPERATING MODEACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS.5.TEST VISIBLE APPLIANCES FOR THE PUBLIC OPERATING MODEACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS.6.FACTORY-AUTHORIZED SERVICE REPRESENTATIVE SHALLPREPARE THE "FIRE ALARM SYSTEM RECORD OF COMPLETION"IN THE "DOCUMENTATION" SECTION OF THE "FUNDAMENTALS"CHAPTER IN NFPA 72 AND THE "INSPECTION AND TESTING FORM"IN THE "RECORDS" SECTION OF THE "INSPECTION, TESTING ANDMAINTENANCE" CHAPTER IN NFPA 72.C.REACCEPTANCE TESTING: PERFORM REACCEPTANCE TESTING TOVERIFY THE PROPER OPERATION OF ADDED OR REPLACED DEVICESAND APPLIANCES.D.FIRE-ALARM SYSTEM WILL BE CONSIDERED DEFECTIVE IF IT DOESNOT PASS TESTS AND INSPECTIONS.3.6DEMONSTRATIONA.TRAIN OWNER'S MAINTENANCE PERSONNEL TO ADJUST, OPERATE,AND MAINTAIN FIRE-ALARM SYSTEM.123456781011121314151617BA91234567810111213141516179DrawnProject ManagerCheckedContract Drawing DateProject NumberQPNMLKJHGFEDCBA18191819QPNMLKJHGFEDCB202120212222TSRTSRRevit Template Versionv16: 2017.10.05This document is the product and property of Baxter Hodell Donnelly Preston, Inc. Neither the document nor the information itcontains may be copied or used for other than the specific project for which it was prepared without the written consent of BaxterHodell Donnelly Preston, Inc. CINCINNATI COLUMBUS RALEIGH PITTSBURGH ATLANTA LAWRENCE DIGENNARO, ARCHITECT 302 WEST THIRD STREET SUITE 500 CINCINNATI, OHIO 45202 PHONE 513.271.1634HIG02.21THE HARTFORD GROUP - 3RD FLOOR RENOVATION 501 PENNSYLVANIA PKWY #400 INDIANAPOLIS, IN 46280 No.Issue/Revision/Submission Date 1 ISSUED FOR BID AND PERMIT 12/14/20182016.05.27E003ELECTRICAL SPECIFICATIONSJRHJRHDEB