HomeMy WebLinkAbout[2] 181224 Lot 7 HVAC-M00245 DEG
RECTANGULAR
DUCT
BRANCH
OCLCONNECTION
TAKE OFF. HAMMER
LOCKED OR FLANGED AND
FULLY SEALED
ROUND SHEET METAL
DUCT TO DIFFUSER V.D.
45 DEG. HIGH EFFICIENCY
TAKE OFF COMPLETELY J
SEALED
O to.1mX
ECCENTRIC TRANSITION MAX,
30 DEG.
30° MAXIM`
{
OFFSET. PROVIDE MINIMUM 2"
STRAIGHT SECTION AT EACH
END. MAX 30 DEG.
0
LL
Q
NOTE:
IN GENERAL, ELBOWS TO HAVE
FULL TURNING RADIUS (R=A).
W HERE "R" IS EQUAL TO OR
GREATER THAN"A" MINIMUM
RADIUS (R) = 4 INCHES.
CONCENTRIC
TRANSITION MAX, 45
DEG. DIVERGING AND
60 DEG. CONVERGING
IYN
NOTE:
DOUBLE THICKNESS
TURNING VANES TO BE USED
WHERE NORMAL RADIUS
ELBOW IS IMPRACTICAL
& WHERE ELBOW IS WITHIN 5
FT OF A
BRANCH TAKE -OFF.
0DUCT CONSTRUCTION DETAILS
A SCALE: NONE
THIS DETAIL SHOWS TYPICAL ROUTING
OF DUCTWORK WITHIN THE ROOF
TRUSS STRUCTURE. REFERENCE
SHEET M101 FOR SPECIFIC DUCT
FSK R8.5 DUCT ROUTING INSTRUCTIONS.
WRAP. TYPICAL \
SUPPLY AIR
RUNS
INSULATED
FRESH AIR DUCT
RETURN AIR
RUNS
REFRIGERATION LINE
SET INSTALLED PER
\
MANUFACTURERS
RECOMMENDATIONS.
FAN
COIL
PROVIDE OPEN SITE TEE
UNIT
LINED RETURN
WITH MOISTURE SWITCH
AIR RISER.
ON SECONDARY DRAIN
CONNECTION. INTERLOCK
WITH HEAT PUMP.
3r4" PVC DRAIN LINE ROUTE
TO DRAIN. MINIMUM 1/4" PER MANUFACTURERS
FOOT, PROVIDE REMOVABLE 2" FILTER RACK
CAP ON CLEAN OUT TEE FOR 18"MIN. WITH MERV 7
LINE BLOW OUT. FILTER.
LJ
PROVIDE LINED SHEET METAL
RETURN AIR BOX UNDER FAN
COIL. NO SIDE CONNECTIONS
ALLOWED.
FAN COIL INSTALLATION DETAIL
B SCALE: NONE
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Carmel
DATE: 04/17/19
GOODERUM & ASSOCIATES ENGINEERING
MEP Engineer
Chelte
874 7.506. 151 Way
Avon, IN 46123
P: 317.745.5761
F: dave@5.5761
E: tlave@gnaengineering.mm
FAN COIL SCHEDULE ELECTRIC HEAT
MARK
MANUFACTURER
FCU
MODEL
HEATINGCAPACITV COOLING
HEAT KIT KW BTUH NOMINAL
MODEL @208 @208 TONS REFG.
ELECTRICAL SPECIFICATIONS
TOTAL
CFM
CA
CFM
STATIC
PRESS.
NOTES:
ELEC.
(V-Ph-Hz)
MCA
CIRCUIT
2
MOCP
CIRCUIT
1/2
FC-1,2
TRANE
TEM6AOC48H41SB
BAYHTR1522BRKA
1 15
51,195
4
R410A
208-1-60
49/43
50/45
1600
160
1 .5
1
O SINGLE PHASE CEILING HUNG HORIZONTAL FAN COIL, PROVIDE WITH MANUFACTURERS ELECTRIC HEATING KIT AS SPECIFIED.
HEAT PUMP SCHEDULE
MARK
MANUFACTURER
MODEL
COOLING
HEATING ELECTRICAL SPECIFICATIONS
NOMINAL
TONS
REFG.
KBTU
SEER
BTUH
HIGH
BTUH
LOW
HSPF ELEC.
(V-Ph-Hz)
MCA
MOCP
NOTES:
HP-1,2
TRANE
4TWA4048A3000A
4
1R-010A
48
14
48
1 32
1 8.7 1 208-3-60
118
30
1002
O ALL HVAC EQUIPMENT TO BE FIELD LABELED TO IDENTIFY WHICH UNIT OF THE BUILDING THEY SERVICE.
O2 PROVIDE CYCLE PROTECTOR, MOUNTING PAD WITH LEGS, CA THERMOSTAT, HIGH AND LOW PRESSURE SWITCHES.
DIFFUSERS, REGISTERS AND GRILLES
TAG
DESCRIPTION
MFR
MODEL
MAT'L.
CFM
MOUNT
STYLE
INTEGRAL
DAMPER
NOTES:
S-0
24"X24"LAY-IN DIFFUSER -6"NECK
PRICE
BCD
STL
100
LAY -IN
NO
iO
S-2
24"X24"LAY4N DIFFUSER -8"NECK
PRICE
BCD
STL
130-225
LAY -IN
NO
iO
S-3
24"X24"LAY-IN DIFFUSER -10"NECK
PRICE
BCD
STL
230-400
LAY -IN
NO
O1
S4
6"X4" LOUVERED SIDE WALL GRILLE
PRICE
520
STL
75
SURFACE
NO
1
R-1
24XI2 FIXED BLADE GRILLE
PRICE
530
STL
0-1000
LAY -IN
NO
11
R-2
24X24 FIXED BLADE GRILLE
PRICE
530
STL
0-2000
LAY -IN
NO
1O
iO COLOR: WHITE, SEE PLANS FOR CFMS
ELECTRIC
HEATER
SCHEDULE
MARK
MANUFCTR
MODEL NO.
HEATING KW
VOLTAGE
PHASE
ACCESSORIESIREMARKS
EWH
QMARK
AWM800
4.0
208
1
iO
O RECESSED WALL HEATER, PROVIDE WITH INTEGRAL THERMOSTAT.
EXHAUST FAN SCHEDULE
TAG
MANUFACTURER
MODEL#
LOCATION
TYPE FAN AND
DESCRIPTION
CFM
SP
SONES
AMPS
VOLT
NOTES
EF-1
GREENHECK
SP-B90
VARIES
CEILING
75
0.24
1.3
0.65
115
iO
iO PROVIDE WITH STEEL WALL CAPPER PLAN.
VENTILATION AIR CALCULATIONS
PEOPLE
AREA CFM
REQUIRE
PROVIDED
SYSTEM
AREA TYPE
TOTAL
OCCUPANTS
CALCULATED
CFM/PERSON
CFM
REQUIREMENT
AREA CFM
FRESH AIRD
FRESH AIR
NETAREA
PER1000 FT
OCCUPANCY
REQUIREMENT
REQUIRED
CFM/FT2
REQUIRED
CFM
CFM
FC-1
OFFICE
1,450
5
8
5
40
.06
87
127
160
FC-2
OFFICE
1,450
5
8
5
40
.06
87
127
160
CALCULATIONS ARE BASED ON IMC 2012 SECTION 403.
REFERENCE SCHEDULES FOR INDIVIDUAL UNIT OUTSIDE AIR QUANTITIES.
W
M
�
o
O
U
z
=
z
0
�
w
m
w
4
U
U w
Z
�
az�
N
/W�O
2
O
C
w
r
Z_
~
Q
o
J
r
z
O_
�
¢
o
o
O
�
o
�
Z J
J O W
Y�rr
LJ
O
0 N U
w
.Z
V
wmmw
di
0
-
z W
z ao ,'�
o
z
w
Ou
LL
a
a�
zx
o
J
°z6a
$
z
w
3
VI
SHEET NO
HVAC SCHEDULES
AND DETAILS
DATE
12/28/18
M002