HomeMy WebLinkAboutE30-0ALL SYMBOLS AND ABBREVIATIONS MAY NOT BE USED ON THIS PROJECT3
ST - 20 AMP, 125VAC, SAFETY TYPE
S - 20 AMP, 125VAC, SURGE GUARD PROTECTION TYPE
WP - 20 AMP, 125VAC, WEATHERPROOF TYPE
HM - 20 AMP, 125VAC, HORIZONTAL MOUNT TYPE
IG - 20 AMP, 125VAC, ISOLATED GROUND TYPE
NONE - 20 AMP, 125VAC
ELECTRICAL RECEPTACLES
DUPLEX RECEPTACLE - NORMAL POWER CIRCUIT
DESCRIPTIONSYMBOL
DUPLEX GFCI RECEPTACLE - NORMAL POWER CIRCUIT
QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUIT
QUADRAPLEX GFCI RECEPTACLE -NORMAL POWER CIRCUIT
SIMPLEX RECEPTACLE - NORMAL POWER CIRCUIT
SPECIAL RECEPTACLE - NORMAL POWER CIRCUIT
DUPLEX RECEPTACLE - TOP SWITCHED
"X" DENOTES AS FOLLOWS:
CEILING DUPLEX RECEPTACLE - NORMAL POWER CIRCUIT
CEILING QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUIT
FLOOR BOX DUPLEX RECEPTACLE - NORMAL POWER CIRCUIT
FLOOR BOX QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUIT
FLOOR BOX POWER AND TELECOM
FLOOR BOX BLANK
MULTI-OUTLET ASSEMBLY (POWER AND/OR TELECOM)
ELECTRICAL SWITCHES
DESCRIPTION SYMBOL
TOGGLE SWITCH - 20 AMP, 120/277VAC
TOGGLE SWITCH - 3 WAY
4 TOGGLE SWITCH - 4 WAY
K TOGGLE SWITCH - KEY OPERATED
T TOGGLE SWITCH - HORSE POWER RATED MANUAL MOTOR
STARTER WITH THERMAL OVERLOAD PROTECTION
P TOGGLE SWITCH - PILOT LIGHT
D DIMMER SWITCH - 20 AMP, 120/277VAC
D DIMMER SWITCH - 3 WAY 3
4 D DIMMER SWITCH - 4 WAY
OC1 WALL OCCUPANCY SENSOR - 1 BUTTON CONTROL
OC2 WALL OCCUPANCY SENSOR - 2 BUTTON CONTROL
OC3 WALL OCCUPANCY SENSOR - DUAL RELAY FOR
EXHAUST FAN CONTROL
OC CEILING OCCUPANCY SENSOR
VS1 WALL VACANCY SENSOR - 1 BUTTON CONTROL
VS2 WALL VACANCY SENSOR - 2 BUTTON CONTROL
LC LOW VOLTAGE LIGHTING CONTROLLER
T 0 - 3 HOUR TIMER SWITCH - 20 AMP, 120/277VAC
INFORMATION SYSTEMS
DESCRIPTIONSYMBOL
VOICE AND DATA ONLY OUTLET
WAP - WIRELESS ACCESS
POINT
FLOOR BOX - VOICE AND DATA
CEILING - VOICE AND DATA
TELECOMMUNICATIONS EQUIPMENT RACK
X
R - ROUGH-IN ONLY
# -QUANTITY OF JACK(S) AND CABLE(S)
"X" DENOTES AS FOLLOWS:
NEUTRAL
GROUND
RACEWAY SYSTEM
DESCRIPTION
PHASE CONDUCTORS
SYMBOL
LIGHT/SCREENED SOLID OR DASHED LINES INDICATE EXISTING TO REMAIN
HEAVY CONTINUOUS LINES INDICATE NEW WORK
LINE SYMBOLS
HEAVY DASHED LINES INDICATE EXISTING TO BE REMOVED
J JUNCTION OR PULL BOX
PUSHBUTTON OR PUSH PLATE
PAD MOUNTED TRANSFORMER
BRANCH PANELBOARD - SURFACE MOUNT
COMBINATION MOTOR CONTROLLER / DISCONNECT
DISCONNECT SWITCH - NON-FUSED
MOTOR CONTROLLER
DISCONNECT SWITCH - FUSED
MOTOR ("X" DENOTES HORSEPOWER)
GROUND CONNECTION
ELECTRIC THERMOSTATT
DESCRIPTION
MOLDED CASE CIRCUIT BREAKER
ELECTRICAL EQUIPMENT
SYMBOL
GROUND POINT
GROUND ROD
X
PC PHOTO CELL
SUSPENDED TRANSFORMER
DISTRIBUTION PANELBOARD
BRANCH PANELBOARD - RECESSED MOUNT
TELECOM TERMINAL BOARD
GROUND BAR
TV
AV
TV SYSTEM OUTLET
AUDIO/VISUAL CONTROLLER
CLOCK SYSTEM OUTLETC
M
M
MICROPHONE INPUT RECEPTACLE - WALL MOUNTED
SPEAKER - WALL MOUNTED
SPEAKER - CEILING MOUNTED
VOLUME CONTROL
MICROPHONE INPUT RECEPTACLE - CEILING MOUNTED
S
S
V
WAP
X
X
RECEPTACLE ABOVE COUNTERTOP AT +2" ABOVE
BACKSPLASH TO BOTTOM OF DEVICE. COORDINATE WITH
CASEWORK TO BE INSTALLED.
RECEPTACLE INSTALLED BELOW COUNTERTOP AT +18"
A.F.F. COORDINATE WITH CASEWORK TO BE INSTALLED.
X
RECEPTACLE LEGEND
FXX
FEEDER SIZE. (REFER TO FEEDER
SCHEDULE FOR ADDITIONAL INFORMATION
1. COORDINATE INSTALLATION OF LIGHT FIXTURES WITH ARCHITECTURAL REFLECTED CEILING PLAN, HVAC EQUIPMENT, DUCTWORK, PIPING AND
SUPPORTS.
2. ELECTRICAL CONTRACTOR SHALL VERIFY THE CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL.
3. ELECTRICAL CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS TO FAMILIARIZE HIMSELF WITH EXTENT OF THE WORK.
4. ALL WORK SHALL CONFORM TO OR EXCEED THE MINIMUM REQUIREMENTS OF THE CURRENT ANSI / NFPA 70 WITH STATE AMENDMENTS, ENERGY
CODE, ANSI / IEEE C2 AND ALL FEDERAL, STATE, LOCAL AND MUNICIPAL CODES AND ORDINANCES. THE ELECTRICAL SUBCONTRACTOR SHALL
COMPLY WITH THE DIRECTIONS OF ALL AUTHORITIES HAVING JURISDICTION.
5. INSTALL WORK USING PROCEDURES DEFINES IN NECA STANDARDS OF INSTALLATION. ALL WORK SHALL PRESENT A NEAT MECHANICAL
APPEARANCE WHEN COMPLETED.
6. REFER TO THE ARCHITECTURAL DRAWINGS FOR CEILING WORK BY THE GENERAL CONTRACTOR. COORDINATE ALL ELECTRICAL WORK.
7. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL FLOOR, WALL, AND CEILING PENETRATIONS TO COMPLETE HIS WORK. PROVIDE PROPER
FIRESTOPPING/ FIRE SAFEING FOR ALL PENETRATIONS MADE. PROVIDE APPROPRIATE SEALANT (I.E. FIRESAFEING) TO MAINTAIN CONSTRUCTION
INTEGRITY FOR ANY PENETRATIONS THROUGH FLOORS, STRUCTURAL CEILING, AND FIRE WALLS. REFER TO THE ARCHITECTURAL
SPECIFICATIONS FOR REQUIREMENTS.
8. COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES TO ENSURE EFFECTIVE AND EFFICIENT OVERALL INSTALLATION.
9. THE LOCATION OF RECEPTACLES, PHONE / DATA JACKS, AND ROOM EQUIPMENT SHOWN ON THESE DRAWINGS ARE APPROXIMATE. FINAL
LOCATIONS WILL BE DETERMINED WITH THE ARCHITECT DURING THE CONSTRUCTION PHASE.
10. ALL EQUIPMENT SHALL BE SUBMITTED FOR APPROVAL PRIOR TO ORDERING.
11. PHYSICAL SIZES AND LOCATIONS OF ALL MECHANICAL EQUIPMENT SHOWN ON THESE DRAWINGS ARE APPROXIMATE. COORDINATE ELECTRICAL
WORK FOR THIS EQUIPMENT WITH THE OTHER TRADES.
12. ALL BRANCH CIRCUITS SHALL UTILIZE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS. DO NOT COMBINE NEUTRAL CONDUCTORS.
13. ALL FEEDER NEUTRAL / GROUNDED CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. DERATE MULTIPLE CONDUCTORS IN A RACEWAY
ACCORDINGLY WITH NEC TABLES.
14. INSTALL ALL CONDUITS, RACEWAYS, AND CABLE TRAY FOR MAXIMUM HEAD CLEARANCE IN MECHANICAL AREAS.
15. WIRING SHALL BE INSTALLED ABOVE ACCESSIBLE CEILINGS AND WITHIN WALL CAVITIES WHERE POSSIBLE.
16. WIRING THAT IS TO BE INSTALLED IN AREAS WHERE THERE ARE NO CEILINGS SHALL BE INSTALLED EXPOSED. THIS WIRING SHALL BE INSTALLED
NEATLY AND AT RIGHT ANGLES TO STRUCTURE. WIRING SHALL BE INDEPENDENTLY SUPPORTED AS REQUIRED. WIRING SHALL NOT LAY OVER
OTHER TRADES.
17. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR HIS OWN STORING OF ELECTRICAL EQUIPMENT AND MATERIAL.
18. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR ELECTRICAL WORK. ALL CUTTING,
PATCHING, REPAIRING, REPLACEMENT AND REFINISHING, SHALL MATCH THE GENERAL CONSTRUCTION AS NEARLY AS POSSIBLE. REFER TO THE
ARCHITECTURAL SPECIFICATIONS FOR REQUIREMENTS.
19. BLOCKING: ELECTRICAL CONTRACTOR SHALL PROVIDE ALL IN-WALL BLOCKING REQUIRED TO SUPPORT ELECTRICAL EQUIPMENT.
GENERAL NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. WHERE OCCUPANCY SENSORS ARE INDICATED ON PLANS, THE ENTIRE ROOM SHALL BE COVERED. MANUFACTURER IS RESPONSIBLE FOR SENSOR
LAYOUT. ADDITIONAL SENSORS REQUIRED DUE TO LACK OF COVERAGE SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
PROVIDE QUANTITY AS REQUIRED. CEILING AND WALLMOUNTED SENSORS SHALL BE DUAL-TECHNOLOGY TYPE. SENSORS SHALL INCLUDE ALL
POWER SUPPLIES AND RELAYS NECESSARY TO CONTROL LIGHT FIXTURES IN ROOM/AREA. SENSORS SHALL OPERATE IN "VACANCY" MODE -
MANUAL ON/AUTO OFF. ACCEPTABLE MANUFACTURERS ARE: HUBBELL, SENSOR SWITCH, LEVITON, LIGHTOLIER, WATTSTOPPER.
2. ALL LIGHT FIXTURES SHOWN WITH EMERGENCY BATTERY BALLASTS OR BACKUP SHALL HAVE UNSWITCHED "HOT" WIRE INSTALLED TO FIXTURE
FROM INDICATED LIGHTING CIRCUIT.
GENERAL LIGHTING NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
GENERAL WIRING DEVICE NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. AT LOCATIONS WITH TWO OR MORE WALL SWITCHES, ALL SWITCHES SHALL BE INSTALLED GANGED IN A COMMON SWITCH BOX.
2. ALL RECEPTACLES SHALL BE TAMPER-RESISTANT TYPE
3. RECEPTACLE LOCATIONS IN ALL UNITS SHALL COMPLY WITH NATIONAL ELECTRICAL CODE REQUIREMENTS AND MEET ALL SPACING REQUIREMENTS.
ELECTRICAL CONTRACTOR SHALL ADJUST LAYOUT SHOWN OR ADD RECEPTACLES AS REQUIRED TO COMPLY WITH APPLICABLE CODES.
TELEPHONE AND DATA SYSTEMS NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUITS AND OTHER RACEWAYS REQUIRED FOR TELEPHONE AND DATA SYSTEMS.
2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL TELEPHONE AND DATA SYSTEMS WIRING AND CABLING REQUIRED WITHIN EACH UNIT AND ALL
OTHER WIRING AND CABLING INDICATED ON THE DRAWINGS. TELEPHONE AND DATA WIRING WITHIN UNITS MAY BE RUN WITHOUT CONDUIT OR
OTHER RACEWAY.
3. TELEPHONE AND DATA SYSTEMS WIRING AND CABLING FOR UTILITY SERVICES TO THE PROJECT BUILDINGS WILL BE PROVIDE BY THE UTILITY
SERVICE PROVIDERS UNLESS OTHERWISE INDICATED.
TELEVISION/CATV SYSTEMS NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUITS AND OTHER RACEWAYS INDICATED AND REQUIRED FOR TELEVISION/CATV SYSTEMS.
2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL TELEVISION/CATV WIRING AND CABLING REQUIRED WITHIN EACH UNIT AND OTHER WIRING AND
CABLING INDICATED ON THE DRAWINGS. TELEVISION/CATV WIRING WITHIN UNITS MAY BE RUN WITHOUT CONDUIT OR OTHER RACEWAY.
3. TELEVISION/CATV SYSTEMS WIRING AND CABLING FOR UTILITY SERVICES TO THE PROJECT BUILDINGS WILL BE PROVIDE BY THE UTILITY SERVICE
PROVIDER UNLESS OTHERWISE INDICATED.
VOLTAGE DROP NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. VOLTAGE DROP IS NOT SHOWN ON THE DRAWINGS. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ADJUSTING ALL FEEDER AND
BRANCH CIRCUIT CONDUCTOR SIZES TO COMPLY THE NATIONAL ELECTRICAL CODE AND ALL STATE AND LOCAL CODES VOLTAGE DROP
REQUIREMENTS.
2. THE ELECTRICAL CONTRACTOR SHALL UPSIZE FEEDER AND BRANCH CIRCUIT CONDUCTORS AS REQUIRED BASED ON ACTUAL INSTALLED CONDUCTOR
LENGHTS.
3. VOLTAGE DROP ON FEEDERS SHALL NOT EXCEED 2 PERCENT.
4. VOLTAGE DROP ON BRANCH CIRCUITS SHALL NOT EXCEED 3 PERCENT.
MECHANICAL EQUIPMENT DISCONNECT NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE MAXIMUM OVERCURRENT PROTECTION (MCOP) VALUE FOR MECHANICAL EQUIPMENT WHERE THE
EQUIPMENT DISCONNECT IS PROVIDED BY THE EQUIPMENT MANUFACTURER.
2. THE ELECTRICAL CONTRACTOR SHALL ADJUST THE EQUIPMENT CIRCUIT CONDUCTOR AND CIRCUIT BREAKER SIZES AS REQUIRED TO NOT EXCEED
THE EQUIPMENT MCOP.
3. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL REQUIREMENTS PRIOR TO ORDERING AND INSTALLING PANELBOARDS, CONDUCTORS, AND
CONDUITS.
ARC FLASH STUDY
1. THE CONTRACTOR SHALL INCLUDE IN THE BID A COMPLETE ARC FLASH AND SHORT CIRCUIT STUDY FOR THE PROJECT PERFORMED BY A LICENSED
ENGINEER.
2. ALL EQUIPMENT SHORT CIRCUIT RATINGS SHALL BE ADJUSTED IN ACCORDANCE WITH THE SHORT CIRCUIT STUDY PRIOR TO ORDERING
EQUIPMENT.
3. PROVIDE ARC FLASH LABELS ON ALL EQUIPMENT / PANELBOARDS.
ARCHITECT
BLACKLINE
1 N MERIDIAN ST, SUITE 400
INDIANAPOLIS, INDIANA 46204
BLACKLINESTUDIO.NET
317.803.790
M.E.P.
GENESIS ENGINEERING GROUP
91 SOUTH MAIN STREET, SUITE 200
ZIONSVILLE, IN 46077
GENESIS-ENGINEERING.COM
317.927.8307
STRUCTURAL
SCHWARZ ENGINEERING GROUP
WWW.SCHWARZINC.COM
317.850.5133
-
-
ALL INFORMATION CONTAINED IN THIS DOCUMENT IS
CONSIDERED TO BE BOTH CONFIDENTIAL AND
PROPRIETARY INTELLECTUAL PROPERTY OF BLACKLINE
STUDIO AND SHALL NOT BE COPIED, REPRODUCED,
DISTRIBUTED OR ASSIGNED TO A THIRD PARTY WITHOUT
PRIOR WRITTEN CONSENT OF BLACKLINE STUDIO.
UNAUTHORIZED USE OF THESE DOCUMENTS IS NOT
PERMITTED.
CERTIFICATION:
CHECKED:DRAWN: C:\Users\jfakes\Documents\Custom Living Monon on Main Town Homes GEG R18_jfakes.rvt
4/5/2019 3:09:51 PM E30-0COPYRIGHT 2018 ELECTRICAL SYMBOLS AND ABBREVIATIONS
Monon & Main Brownstones
Monon & Main St., Carmel INJAWJAW
Monon and Main Brownstone
Interior Remodel –Unit 30
04/05/2019 Lot 30 -ERNST RESIDENCE# REVISION Date