HomeMy WebLinkAboutM40-3DIFFUSER/REGISTER/GRILLE SCHEDULE
TAG NECK
SIZE
FACE
SIZE
(IN.) MATERIAL
CFM
RANGE
MAX.
NC
MAX.
TOTAL A.P.D.
(IN. WG.)
MANUFACTURER MODEL NOTES
DESIGN REFERENCE
THROW
(FT. BASED ON
VELOCITY OF 50
FPM)
20 0.040 PRICE
SR1 10"x6" 10"x6"0 - 150 20 0.040 PRICE 640 11ALUMINUM
NOTES:
1. BRANCH DUCT RUNOUT TO THE DIFFUSER SHALL BE THE SAME SIZE AS THE DIFFUSER NECK UNLESS NOTED OTHERWISE ON THE DRAWINGS.
2. ALL SUPPLY DIFFUSER BACKPLATES SHALL BE INSULATED WITH A MINIMUM OF 1" INSULATION. INSULATION MAY BE FACTORY OR FIELD APPLIED.
3. PROVIDE FRAME STYPLE APPROPRIATE FOR CEILING TYPE (I.E. LAY-IN, SURFACE MOUNT, SIDEWALL, ETC.). REFER TO DRAWINGS AND ARCHITECTURAL
REFLECTED CEILING PLANS FOR LOCATIONS.
4. PLENUM RETURN GRILLES SHALL HAVE A RETURN BOOT WITH RETURN DAMPER ATTACHED TO THE BACK.
5. 1/8" BARS, 1/2" BLADE SPACING, 15° DEFLECTION.
AIR TERMINAL TYPE
SUPPLY REGISTER
1, 2, 3
1, 2, 3
SR2 14"x6" 14"x6"155 - 200 640 13ALUMINUM
SUPPLY REGISTER
RG1 RETURN GRILLE 8"x10" 8"x10" ALUMINUM 0 - 200 - 20 0.040 PRICE 630
FSR1
FSR2
LINEAR BAR FLOOR GRILLE
LINEAR BAR FLOOR GRILLE
12"x4"
12"x6"
0 - 125
130 - 200
12"x4"
12"x6"
ALUMINUM
ALUMINUM
15
17
20
20
0.040
0.040
PRICE
PRICE
LBPH
LBPH 2, 3, 5
1, 3, 4
2, 3, 5
RG2 RETURN GRILLE 20"x18" 20"x18" ALUMINUM 750 - 1000 - 20 0.040 PRICE 630 1, 3, 4
EG1 EXHAUST GRILLE 6"x6" 6"x6" ALUMINUM 20 - 75 - 20 0.040 PRICE 630 1, 3, 4
DRYER DUCT THROUGH ROOF
DRYER VENT, CONSTRUCTED OF
MINIMUM 26 GAUGE GALVANIZED
SHEETMETAL WITH NO SCREWS OR
DAMPERS THAT COULD CATCH LINT.
STEEL SLEEVE
FLEXIBLE SEALANT RATED FOR 400°F
FINISHED ROOF LINE
8" MINIMUM. TALLER
AS REQUIRED FOR
ROOFING WARRANTY
ANCHOR HOOD TO CURB, 6" O.C.
MINIMUM 3" CLEAR FROM
VENT TO METAL LINER
SEAL ALL EXPOSED SEAMS WATERTIGHT
HEIGHT ABOVE ROOF DECK.
MAKE HEIGHT AS LOW AS
POSSIBLE BUT NOT LESS
THAN 2'-0".
ALUMINUM EXHAUST HOOD
WITH SWING OUT DAMPER.
4" DISCHARGE SIZE
(NOT 2-1/2").
HIGH TEMPERATURE
SILICONE SEAL
STAINLESS STEEL HOOD 18
GAUGE. FORCE FIT TO VENT
WOOD NAILER
16" TALL SQUARE CURB
WITH METAL LINER
ROOF CONSTRUCTION
PACKED INSULATION
METAL ESCUTCHEON
FORCE FIT TO VENT
STRUCTURAL FRAME AROUND
OPENING. SEE STRUCTURAL
DRAWINGS OR PROVIDE
<4"X4"X5/16".
.
FLEXIBLE DUCTWORK BENDS SHALL NOT BE LESS THAN 1.5 TIMES THE DUCT DIAMETER.
INSULATION AND VAPOR BARRIERS PRESENT ON FACTORY -FABRICATED DUCTS SHALL BE FITTED OVER
THE CORE CONNECTION AND SHALL BE SECURED WITH A DRAW BAND. TAPE AND SEAL ALL JOINTS AND
SEAMS WITH FSK TAPE TO MAINTAIN VAPOR BARRIER.
SUPPORT FLEXIBLE DUCTWORK FROM STRUCTURE. DO NOT SUPPORT FLEXIBLE DUCTWORK FROM
ADJACENT ABOVE CEILING UTILITIES (DUCTWORK, PIPING, CONDUITS, ETC.)
A.
B.
C.
GENERAL DETAIL NOTES:
FLEX DUCT -MAXIMUM 8'-0"
LENGTH AND NO MORE THAN
TWO (2) 90° BENDS.
INSULATE BACK OF SUPPLY
DIFFUSERS WITH 1" MINERAL FIBER
INSULATION WITH FSK JACKET.
TAPE AND SEAL INSULATION
VAPOR BARRIER.
CEILING
SUPPLY DIFFUSER
ATTACH FLEXIBLE DUCTWORK
WITH DRAWBAND AND SEAL
INSULATION AND VAPOR BARRIER
TO FSK TAPE.
INSTALL MANUAL VOLUME DAMPER
AT ALL BRANCH DUCTS. PROVIDE
2" EXTENDED OPERATOR HANDLE
FOR INSULATED DUCTS.
SPIN -IN FITTING AT BRANCH/MAIN
CONNECTION.
ARCHITECT
BLACKLINE
1 N MERIDIAN ST, SUITE 400
INDIANAPOLIS, INDIANA 46204
BLACKLINESTUDIO.NET
317.803.790
M.E.P.
GENESIS ENGINEERING GROUP
91 SOUTH MAIN STREET, SUITE 200
ZIONSVILLE, IN 46077
GENESIS-ENGINEERING.COM
317.927.8307
STRUCTURAL
SCHWARZ ENGINEERING GROUP
WWW.SCHWARZINC.COM
317.850.5133
-
-
ALL INFORMATION CONTAINED IN THIS DOCUMENT IS
CONSIDERED TO BE BOTH CONFIDENTIAL AND
PROPRIETARY INTELLECTUAL PROPERTY OF BLACKLINE
STUDIO AND SHALL NOT BE COPIED, REPRODUCED,
DISTRIBUTED OR ASSIGNED TO A THIRD PARTY WITHOUT
PRIOR WRITTEN CONSENT OF BLACKLINE STUDIO.
UNAUTHORIZED USE OF THESE DOCUMENTS IS NOT
PERMITTED.
CERTIFICATION:
CHECKED:
DRAWN: C:\Users\jfakes\Documents\Custom Living Monon on Main Town Homes GEG R18_jfakes.rvt
4/12/2019 2:00:49 PM M40-3COPYRIGHT 2018 MECHANICAL SCHEDULES AND DETAILSMonon & Main Brownstones
Monon & Main St., Carmel INChecker
Author
Monon and Main Brownstone
Interior Remodel –Unit 40
04/12/2019
Lot 30 -ERNST RESIDENCE
NO SCALE2DRYER VENT DETAIL 40
NO SCALE3CEILING DIFFUSER/GRILLE DETAIL 40
NOTES:
1. DIRECT DRIVE WITH SOLID STATE SPEED CONTROLLER.
2. DISCONNECT BY MANUFACTURER.
3. FAN SHALL OPERATE VIA DISCONNECT (24/7).
NOTES:
1. R410A REFRIGERANT.
2. ANTI-SHORT CYCLE TIMER.
NOTES:
1. HEAT RATING BASED ON 40% LOW INPUT
2. VARIABLE SPEED BLOWER.
3. PROVIDE 1" TRAPPED CONDENSATE PIPED TO FLOOR DRAIN.
4. DX COIL CASED FOR UPFLOW.
5. DX COIL CASED FOR DOWNFLOW.
6. RETURN AIR SUB BASE BY MANUFACTURER.
7. CONCENTRIC VENT KIT BY MANUFACTURER.
8. SPACE TEMPERATURE MEASURED VIA COMMON RETURN AIR SENSOR. SYSTEM SHALL RESPOND TO MOST
RECENT INPUT FROM ANY CONNECTED THERMOSTAT.
# REVISION Date
AIR COOLED CONDENSING UNIT SCHEDULE 40
MARK
COOLING
CAPACITY (BTUH) MIN. SEER
ELECTRICAL DATA UNIT WEIGHT
(LBS)
BASIS OF DESIGN MAX SOUND
RATING (dB) NOTESMCA MOCP VOLTS PHASE MANUFACTURER MODEL
ACCU-1-40 36,000 15 23 35 208 1 240 TRANE 4TTV0036A100A 70 1,2
ACCU-2-40 36,000 15 23 35 208 1 240 TRANE 4TTV0036A100A 70 1,2
FAN SCHEDULE 40
TAG LOCATION
AIRFLOW
(CFM)
E.S.P.
(IN.W.G.)POWER FAN TYPE FAN RPM DRIVE
ELECTRICAL REQUIREMENTS
WEIGHT (LBS)DESIGN REFERENCE
NOTESAMPS VOLT/PHASE MANUFACTURER MODEL
EF-1-40 MECHANICAL 120 0.3 1/20 HP INLINE CENTRIFUGAL 1171 DIRECT 6 120/1 49 GREENHECK SQ-80-VG 1,2,3
FURNACE SCHEDULE 40
MARK CONFIGURATION
NOMINAL
TONS
AIRFLOW
(CFM)
FAN DATA COOLING DATA HEATING DATA ELECTRICAL DATA BASIS OF DESIGN UNIT WEIGHT
(LBS) NOTESESP DRIVE HP TOTAL BTU EAT DB (°F) EAT WB (°F) BTU INPUT BTU OUTPUT EAT DB (°F) AFUE (%) MCA MOCP VOLTS PHASE MANUFACTURER MODEL
F-1-40 VERTICAL UPFLOW CONDENSING GAS 2 700 0.3 DIRECT 0.5 24,000 75 63 24,000 23,000 70 95 11.1 15 120 1 TRANE TUHMB060ACV3VA 170 1,2,3,4,6,7
F-2-40 VERTICAL DOWNFLOW CONDENSING GAS 3.0 900 0.3 DIRECT 0.5 36,000 75 63 32,000 30,000 70 95 11.1 15 120 1 TRANE TDHMB080ACV3VB 170 1,2,3,5,6,7,8
05/02/19
Mike Sheeks