HomeMy WebLinkAboutS&S COMcheck - PURE PharmacyCOMcheck Software Version COMcheck-Web
Interior Lighting Compliance Certificate
Project Information
Energy Code:
Project Title:
Project Type:
2018 IECC
PURE Pharmacy
Alteration
Construction Site: Owner/Agent:
Designer/Contractor:
12425 Old Meridian St., Suite B3
Carmel, Indiana 46032
Allowed Interior Lighting Power
A
B
C
D
Area Category
Floor Area
Allowed
Allowed Watts
(ft2)
Watts / ft2
1-Hospital
1913
1.05
2009
Total Allowed Watts =
2009
Proposed Interior Lighting Power
A
B
C
D
E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
Lamps/
# of
Fixture
(C X D)
Fixture
Fixture
Watt.
Hospital (1913 sq.ft.)
LED: D1:6" DOWNLIGHT: Other:
1
1
20
20
LED: D2:6" DOWNLIGHT: Other:
1
4
16
62
LED: D4: 2" WALL WASHED LIGHT: Other:
1
4
16
62
LED: Rt: 2'X4' LAY-IN/GRID: LED Linear 33W:
1
14
38
532
LED: R2:2'X4' LAY-IN/GRID W/ACRYLIC LE: LED Panel 40W:
1
4
48
192
LED: VIA: FLEXIBLE LINEAR: Other:
1
1
20
20
LED: VIA/EM: EMERGENCY FLEXIBLE LINEAR: Other:
1
1
40
40
LED: Fl: 2'X4' FLAT PANEL: LED Panel 70W:
1
2
72
144
LED: F2: VX4' FLAT PANEL: LED Panel 40W:
1
4
45
180
LED: UC: UNDERCABINET LIGHTING: LED Undercabinet Unit 5.7W:
1
20
6
120
LED: X: EXIT SIGN: Other:
1
3
4
12
Total Proposed Watts =
1384
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application, The proposed interior lighting
systems have been designed to meet the 2018 IECC requirements in COMcheck Version COMcheck-Web and to comply with any
applicable mandatory requirements listed in the InspIsa fnut++ _
VE
ame - Title - — SignarL4 Dat
w
srarIT OF
Project Title: PURE Pharmacy Report date; 04/15/19
Data filename: Page 1 of 15
COMcheck Software Version COMcheck-Web
Mechanical Compliance Certificate
Project Information
Energy Code: 2018 IECC
Project Title: PURE Pharmacy
Location: Carmel, Indiana
Climate Zone: 5a
Project Type: Alteration
Construction Site: Owner/Agent: Designer/Contractor:
12425 Old Meridian St., Suite B3
Carmel, Indiana 46032
Mechanical Systems List
Quantity System Type & Description
1 HVAC System (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 120 kBtu/h
Proposed Efficiency = 96.00% Et, Required Efficiency: 80.00 % Et or 80% AFUE
Cooling: 1 each - Split System, Capacity = 56 kBtu/h, Air -Cooled Condenser, Air Economizer
Proposed Efficiency= 13.75 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 1680 CFM, 1.0 motor nameplate hp, 0.0 fan efficiency grade
1 HVAC System (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 100 kBtu/h
Proposed Efficiency = 95,00% Et, Required Efficiency: 80.00 % Et or 80% AFUE
Cooling: 1 each - Split System, Capacity= 47 kBtu/h, Air -Cooled Condenser, Air Economizer
Proposed Efficiency= 15.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 1380 CFM, 0.8 motor nameplate hp, 0.0 fan efficiency grade
1 Water Heater:
Gas Instantaneous Water Heater, Capacity: 10 gallons, Input Rating: 199 kBtu/h w/Circulation Pump
No minimum efficiency requirement applies
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented In this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2018 IECC requirements in COMcheck Version COMcheck-Web and to comply with any applicable
mandatory requirements listed in the Inspection Checkli -
ame - Title _ - Sig ur ,!p\IAv ItYVy'�Q.,,, Date
Project Title: PURE Pharmacy
Data filename:
Report date: 04/15/19
Page 2 of 15
COMcheck Software Version COMcheck-Web
Inspection Checklist
Energy Code: 2018 IECC
Requirements: 100.0% were addressed directly In the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Plan Review
Complies?
Comments/Assumptions r
& Req,I
C103,2
Plans, specifications, and/or❑Complies
Requirement will be met.
[PR211
'calculations provide all information
Not
;with which compliance can be
�❑Does
Observable'
determined for the mechanical❑Not
Applicable
systems and equipment and❑Not
; document where exceptions to the
;standard are claimed. Load
'calculations per acceptable
;engineering standards and
',handbooks.
C103,2
Plans, specifications, and/or
❑Complies
Requirement will be met.
[PR311
(calculations provide all information❑Does
Not
;with which compliance can be
j❑Not Observable;
determined for the service water
Applicable
heating systems and equipment and❑Nat
document where exceptions to the
;standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C103.2
;Plans, specifications, and/or
;❑Complies
'Requirement will be met.
[PR4I1
'calculations provide all information❑Does
Not
;with which compliance can be
Observable
;determined for the interior lighting❑Not
Applicable
'and electrical systems and equipment❑Not
$and document where exceptions to
the standard are claimed. Information
'provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
'control devices.
C406
'Plans, specifications, and/or❑Complies
Requirement will be met.
[PR911
I calculations provide all information❑Does
Not
with which compliance can be
Observable
determined for the additional energy❑Not
;❑Not Applicable
efficiency package options.
Additional Comments/Assumptions:
1 High Impact (Tier 1) '2. Medium Impact (Tier 2) ':3 Low Impact (Tier 3)
Protect Title: PURE Pharmacy
Data filename:
Report date: 04/15/19
Page 3 of is
Snow/ice melting system and freeze ;Complies Requirement will be met,
protection systems have sensors and :ODoes Not
controls configured to limit service for
pavement temperature and outdoor �oNot Observable;
temperature. future connection to ;Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3:. Low Impact (Tier 3)
Project Title: PURE Pharmacy
Data filename:
Report date: 04/15/19
Page 4 of 15
Section
#
Plumbing RoughAn Inspection
Complies?
Comments/Assumptions
& Re ,ID
C404 5,
Heated water supply piping conforms❑complies
; Requirement will be met.
C404.5.1;
'to pipe length and volume
❑Does Not
C404.5.2
C requirements. Refer to section details.❑Not
Observable;
[PL6]3
:❑Not Applicable
C404.51 ,`
`:' Heated water supply piping conforms
I❑Complies
! Requirement will be met.
C404,5,11
to pipe length and volume❑Does
Not
C404.5.2
requirements. Refer to section details.
I
Observable;
[PL6]3.:- `'
li❑Not
'❑Not
Applicable
C404.5, ':
Heated water supply piping conforms❑Complies
;Requirement will be met.
C404,5 1;'.'to
pipe length and volume
❑Does Not
C404.5 2
requirements, Refer to section details.
; Observable;
[PL6]3 >,"❑Not
❑Not Applicable
,
C404.6.11
Automatic time switches installed to❑Complies
Requirement will be met.
C404.6.2
automatically switch off the❑Does
Not
[PL3]1
recirculating hot-water system or heat
❑Not Observable
;
;trace.
I
❑Not Applicable
C404,6:3
Pumps that circulate water between a
;❑Complies
Requirement will be met.
[PL7]3
' heater and storage tank have controls❑Does
Not
j
'.
that limit operation from startup to❑Not
Observable;
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6:3.
; Pumps that circulate water between a❑Complies
Requirement will be met.
[PL7j3
heater and storage tank have controls❑Does
Not
that limit operation from startup to
Observable
<= 5 minutes after end of heating❑Not
j❑Not Applicable
lcyde.
C404.6.3:':;
Pumps that circulate water between a❑Complies
;Requirement will be met.
[PL7]3 -'.i
heater and storage tank have controls❑Does
Not
that limit operation from startup to
Observable
--:j
<= 5 minutes after end of heating❑Not
Applicable
cycle.❑Not
C404 7
Demand recirculation water systems❑Complies
Requirement will be met.
[PL8]3
' have controls that start the pump
❑Does Not
upon receiving a signal from the
Observable
:..`,appliance
action of a user of a fixture or❑Not
❑Not Applicable
and limits the temperature
<:of
the water entering the cold -water
7.I
piping to 104°F.
C404 7 '..
Demand recirculation water systems❑Complies
Requirement will be met.
[PL8]3
'have controls that start the pump
❑Does Not
[;1
upon receiving a signal from the
❑Not Observable
"]appliance
'action of a user of a fixture or
and limits the temperature❑Not
Applicable
of the water entering the cold-water
-':1
piping to 104°F.
C404.7 r`-:I
Demand recirculation water systems❑Complies
Requirement will be met.
[PL8]3 i
'have controls that start the pump❑Does
Not
i upon receiving a signal from the
Observable;
action of a user of a fixture or
appliance and limits the temperature❑Not
'❑Not
Applicable
of the water entering the cold -water
'..I
piping to 104°F.
Additional Comments/Assumptions:
1 High Impact (Tier 1) ' 2`-s-s Medium Impact (Tier 2) '31. Low Impact (Tier 3)
Project Title: PURE Pharmacy Report date; 04/15/19
Data filename: Page 5 of 15
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3`i low Impact (Tier 3)
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename: Page 6 of 15
Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C402.2.6
;Thermally ineffective panel surfaces of;❑Complies
'Requirement will be met,
[ME41]3.'.
'sensible heating panels have
❑Does Not
insulation >= R-3.5.
❑Not Observable;
❑Not Applicable
C403.113 HVAC piping insulation insulated in❑Complies
;Requirement will be met.
[ME61]2 ,1
'accordance with Table C40311.3.
❑Does Not
Insulation exposed to weather is
Observable
protected from damage and is❑Not
Applicable
provided with shielding from solar❑Not
radiation.
C403.11.3l HVAC piping insulation Insulated in❑Complies',
Requirement will be met.
[ME61]' :.
':'accordance with Table C403.11.3.❑Does
Not
f
Insulation exposed to weather is
Observable
,'.
protected from damage and is❑Not
provided with shielding from solar❑Not
Applicable
r,
radiation.
C403,8.4
Motors for fans that are not less than',❑Complies
Requirement will be met,
[ME142]2
' 1/12 hp and less than 1 hp are
❑Does Not
,electronically commutated motors or
Observable
have a minimum motor efficiency of
'❑Not
1❑Not Applicable
;
70 percent. These motors have the
means to adjust motor speed.
C403,84`::;
Motors for fans that are not less than
;❑Complies
'Requirement will be met.
[ME142]2;.i
1/12 hp and less than 1 hp are❑Does
Not
`;electronically
commutated motors or❑Not
Observable;
<.
have a minimum motor efficiency of
I
Applicable
70 percent. These motors have the❑Not
means to adjust motor speed.
C403 8,5`.
Each DX cooling system > 65 kBtu
;❑Complies
:Requirement will be met.
[ME143]2:
`; and chiller water/evaporative cooling
'❑Does Not
system with fans > 1/4 hp are❑Nat
Observable
'designed to vary the indoor fan airflow
3 as a function of load and comply with
❑Not Applicable
PP
detailed requirements of this section.
j
C403,8 5=
Each DX cooling system > 65 kBtu
;❑Complies
;Requirement will be met.
[ME143]2::'and
chiller water/evaporative coaling
i❑Does Not
.:.;system
with fans > 1/4 hp are❑Not
Observable;
designed to vary the indoor fanairflowl❑NotAPP
as a function of load and comply with
Applicable
Sl
detailed requirements of this section.
j
C403,12,11j
Systems that heat outside the building;❑Complies
!Requirement will be met.
[ME71]2
'envelope are radiant heat systems❑Does
Not
controlled by an occupancy sensing
❑Not Observable
',device or timer switch.
❑Not Applicable
C403.2.3'
Si HVAC equipment efficiency verified,❑Complies
;See the Mechanical Systems list for values.
[ME55]2
❑Does Not
❑Not Observable;
"...'❑Not
Applicable
C403.5.5:>;.
Fault detection and diagnostics
❑complies
'Requirement will be met.
[ME113]2.''installed
with air-cooled unitary DX❑Does
Not
';units having economizers.
❑Not Observable;
;:.❑Not
Applicable
C403.2.2
;Natural or mechanical ventilation is
❑Complies
:Requirement will be met,
[ME59]1
'provided in accordance with❑Does
Not
;International Mechanical Code
Observable;
;Chapter 4. Mechanical ventilation has❑Not
Applicable
capability to reduce outdoor air supply❑Not
to minimum per IMC Chapter 4,
1 High Impact (Tier 1) `r2i'. Medium Impact (Tier 2) 13: Low Impact (Tier 3)
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename: Page 7 of 15
Section
#
Mechanical Rough -in Inspection
Complies?
Comments/Assumptions:
& Req:ID
C403.7.1
;Demand control ventilation provided
❑Complies
;Requirement will be met.
(ME5911
'for spaces >500 ft2 and >25❑Does
Not
people/1000 ft2 occupant density and
Observable
served by systems with air side❑Nat
;ONot Applicable
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
C403,7,2 '.;
Enclosed parking garage ventilation
I❑Complies
Exception: Requirement does not apply.
[ME115]3=
has automatic contaminant detection
I❑Does Not
and capacity to stage or modulate
Observable
P
I
-,fans
to 50 % or less of design capacity.
;❑Not
❑Not Applicable
;
C403.7,6';
HVAC systems serving guestrooms in❑Complies
Exception: Requirement does not apply.
[ME141]3
'Group R-1 buildings with > 50
❑Does Not
j
guestrooms: Each guestroom is
❑Not Observable
;.,
provided with controls that
Applicable
automatically manage temperature❑Not
(`
setpoint and ventilation (see sections
C403.7.6.1 and C403,7,6,2).
C403.7A
Exhaust air energy recovery on
❑Complies
Requirement will be met.
[ME5711
;systems meeting Table C403.7.4(1)❑Does
Not
;and C403.7.4(2).
;❑Not Observable'
❑Not Applicable
C4033,5
Kitchen exhaust systems comply with
IOCompiies
Exception: Requirement does not apply,
[ME116]3.:.'replacement
air and conditioned
;[]Does Not
C.
;supply air limitations, and satisfy hood
Observable
'I
rating requirements and maximum❑Not
Applicable
exhaust rate criteria.❑Not
C403.11.1`
HVAC ducts and plenums insulated in
❑Complies
Requirement will be met.
accordance with C403.11,1 and❑Does
Not
C403.11.2constructed
in accordance with
IONot Observable
P
[ME6072.. `:
C403.11.2, verification may need to
Soccur
❑Not Applicable
during Foundation Inspection,
C403,51
;Air economizers provided where
I❑Complies
Requirement will be met.
C403.5.1,
required, meet the requirements for
ODoes Not
C403,5.2
design capacity, control signal,
Not Observable;
[ME6211
ventilation controls, high -limit shut-off,'❑NotA
'integrated
Applicable
economizer control, and
pP
provide a means to relieve excess
'outside air during operation.
C403.5.3.:Air
economizers automatically reduce
;❑Complies
Requirement will be met.
3
outdoor air intake to the design❑Does
Not
[ME124]1
'minimum outdoor air quantity when
Observable:
outdoor air intake will not reduce❑Not
Applicable
cooling energy usage. See Table❑Not
C403,533 for applicable device types
;and climate zones.
C403.5.3.
'System capable of relieving excess
❑Complies
Requirement will be met.
4
outdoor air during air economizer
;[]Does Not
[ME125]1
;operation to prevent overpressurizing
:❑Not Observable'
'the building. The relief air outlet
'located
Applicable
to avoid recirculation into the
;❑Not
;building.
C403.5.3.
Return, exhaust/relief and outdoor air
;[]Complies
j Requirement will be met.
5
dampers used in economizers have
ODoes Not
[ME126]1
'motorized dampers that automatically
❑Not Observable;
shut when not in use and meet
'maximum leakage rates, Reference
[]Not Applicable
j section C403,7.7 for details.
1 High Impact (Tier 1) 2' Medium Impact (Tier 2) 3I'. Low Impact (Tier 3)
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename: Page 8 of 15
Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions 1.
& Req.ID
C403.4 1,
Heating for vestibules and air curtains
❑Complies
Requirement will be met.
4
with integral heating include
Not
[ME63]2
automatic controls that shut off the❑Not
Observable;
'.
j heating system when outdoor air
'temperatures
�ONot Applicable
> 45F. Vestibule
heating and cooling systems
controlled by a thermostat in the
vestibule with heating setpoint <=
'.:
6OF and cooling setpoint >= 80F,
C403.3.3
;Hot gas bypass limited to: <=240
',❑Complies ,Requirement
will be met.
(ME35]1
I ketu/h - 50 % >240 kBtu/h - 25 %
I❑Does Not
I❑Not Observable j
❑Not Applicable
C403.3.3
Hot gas bypass limited to: <=240❑Complies
Requirement will be met.
[ME35]1
; kBtu/h - 50 % >240 kBtu/h - 25 LIDoes
Not
I❑Not Observable;
❑Not Applicable
C408,2,2:.
;Air outlets and zone terminal devices
❑Complies
Requirement will be met,
1 '
have means for air balancing.❑Does
Not
(ME53]3 `.
;❑Not Observable
`.i
j❑Not Applicable
C403.51 `
Refrigerated display cases, walk-in❑Complies
Requirement will be met.
C403.541,
coolers or walk-in freezers served by❑Does
Not
C4035r2 I,
remote compressors and remote
❑ Not Observable;
[ME123]3
=l
'condensers not located in a
Applicable
condensing unit, have fan-powered❑Not
'condensers that comply with Sections
)�C403.5,1 and refrigeration compressor;
systems that comply with C403.5,2..
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3` Low Impact (Tier 3)
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename: Page 9 of 15
Section
#
Rough -In Electrical Inspection
Complies? Comments/Assumptions'
& Req.ID
C405.2.2.
;Spaces required to have light-
❑Complies , Requirement will be met.
2
reduction controls have a manual❑Does
Not
[EL22]1
'control that allows the occupant to❑Not
Observable;
'reduce the connected lighting load in
Applicable
'a reasonably uniform illumination❑Not
;pattern >= 50 percent.
C405.2,11
;Occupancy sensors installed in❑Complies
;Requirement will be met.
C405.2,1.
(classrooms/lecture/training rooms,;❑Does
Not
1
jconference/meeting/multipurpose
[EL18]1
',rooms, copy/print rooms,
I❑Not Observable
Applicable
' lounges/breakrooms, enclosed offices,❑Not
;
,open plan office areas, restrooms,
;storage rooms, locker rooms,
'warehouse storage areas, and other
spaces <= 300 sqft that are enclosed
by floor -to -ceiling height partitions.
'Reference section language
C405.2,1,2 for control function in
warehouses and section C405.2.1.3
;for open plan office spaces.
C405.2.1.
Occupancy sensors control function in
;❑Complies Exception: Requirement does not apply.
2
'warehouses: In warehouses, the
;❑Does Not
[EL1911
:lighting in aisleways and open areas is;
Observable
,controlled with occupant sensors that
:❑Not
Applicable
automatically reduce lighting power❑Not
by 50 % or more when the areas are
unoccupied, The occupant sensors
control lighting In each aisleway
independently and do not control
lighting beyond the aisleway being
controlled by the sensor.
C405.2.1.
;Occupant sensor control function in❑Complies
;Requirement will be met.
3
open plan office areas: Occupant
❑Does Not
[EL20]1
;sensor controls in open office spaces
;❑Not Observable
(>= 300 sq.ft, have controls 1)
'configured
Applicable
so that general lighting can;❑Not
be controlled separately in control
;zones with floor areas <= 600 sq.ft.
'within the space, 2) automatically turn
1
'off general lighting in all control zones
;within 20 minutes after all occupants
have left the space, 3) are configured
tso that general lighting power in each
;control zone is reduced by >= 80 % of
'the full zone general lighting power
;within 20 minutes of all occupants
leaving that control zone, and 4) are
;configured such that any daylight
responsive control will activate space
general lighting or control zone
;general lighting only when occupancy
;for the same area is detected.
C405 2.2,E
i Each area not served by occupancy
❑Complies Exception: Lighting that is related to means of egress in
C405.2.2sensors
(per C405.21) have time -❑Does
Not 'stairways, ramps, corridors, or emergency routes.
1,
;switch controls and functions detailed❑Not
Observable;
C405.2.2i
) in sections C405.2.2.1 and C405.2.2.2.
❑Not Applicable j
[EL21]2
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 31: Low Impact (Tier 3)
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename; Page 10 of 15
Section
#
Rough -in Electrical Inspection
Complies?
Comments/Assumptions
& Req.ID
C405.2 3,
Daylight zones provided with
❑Complies
,Requirement will be met.
C405.2.3,
.) individual controls that control the
❑Does Not
1,
lights independent of general area;
Observable
ot e
C405.2.3::-,
lighting. See code section C405.2.3
❑❑NN
,t
Applicable
j
2 '.
] Daylight -responsive controls for
[EL23]2 -„applicable
spaces, C405.2.3.1 Daylight',
,responsive control function and
-1
section C405.2.3.2 Sidelit zone.
C405.2A
I Separate lighting control devices for
❑Complies
Requirement will be met.
[EL26]1
specific uses installed per approved❑Does
Not
;lighting plans.❑Not
Observable;
❑Not Applicable
C405.2.4
:Additional interior lighting power
❑Complies
;Requirement will be met.
[EL2711
allowed for special functions per the❑Does
Not
;approved lighting plans and is
Observable
automatically controlled and❑Not
Applicable
separated from general lighting.❑Not
C405.3
Exit signs do not exceed 5 watts per
❑Complies
;Requirement will be met.
[EL6]1
(face.❑Does
Not
FF
;❑Not Observable;
❑Not Applicable
C405.6
; Low -voltage dry -type distribution❑Complies
Requirement will be met.
[EL26]2 ':
i electric transformers meet the❑Does
Not
minimum efficiency requirements of
I❑Not Observable'
Table C405.6.
I
;ONot Applicable
C405.7 `
Electric motors meet the minimum❑Complies
; Requirement will be met.
[EL27]2
:I efficiency requirements of Tables❑Does
Not
�C405.7(1) through C405.7(4).❑Not
Observable
j
Efficiency verified through certification,❑Not
Applicable
PP
under an approved certification
program or the equipment efficiency
`',ratings
shall be provided by motor
I manufacturer (where certification
programs do not exist).
C405.8.2; :;
Escalators and moving walks comply
i❑Complies
Exception: Requirement does not apply.
C405,8.2 i'
with ASME A17.1/CSA B44 and have❑Does
Not
1
;automatic controls configured to
';
❑ Not Observable;
[EL28]2 ';
reduce speed to the minimum
Applicable
l permitted speed in accordance with❑Not
'
ASME A17.1/CSA B44 or applicable
I
local code when not conveying
l passengers.
C405.9-'I
Total voltage drop across the
!❑Complies
;Requirement will be met.
[EL29]2 `
i combination of feeders and branch
❑Does Not
,
,circuits a=5%.
',❑Not Observable;
Applicable
,❑Not
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 : Medium Impact (Tier 2) 3+:. Low Impact (Tier 3)
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename: Page 11 of 15
Section
#
' Final Inspection
Complies?
Comments/Assumptions
& Req.ID
C303.3, :'.
11 Furnished O&M instructions for❑Complies
;Requirement
will be met.
C4082.5.',i
systems and equipment to the❑Does
Not
2
; building owner or designated❑Not
Observable j
[F]17]3
`representative.
jDNot Applicable
C303.3,
I Furnished O&M manuals for HVAC
;❑Complies
Requirement will be met.
C408 2,5, ;I
systems within 90 days of system
❑Does Not
3
.'acceptance.
[FI8] 3
;❑Not Observable',
❑Not Applicable
C403 2.2
HVAC systems and equipment❑complies
Requirement will be met.
(FI2713 '
:' capacity does not exceed calculated
❑Does Not
:l loads.
I❑Not Observable;
❑Not Applicable
C403 2.4.::
Heating and cooling to each zone is
❑Complies
Requirement will be met.
1 -<(
controlled by a thermostat control.
:[]Does Not
(FI47]3
'Minimum one humidity control device
Observable;
per installed❑Not
I humidification/dehumidification❑Not
Applicable
system.
C403.2 A,
EI Heating and cooling to each zone is
❑Complies ;
Requirement will be met.
1
'controlled by a thermostat control.
!❑Does Not
[FI47]3
Minimum one humidity control device
Observable;
iI
'.'
per installed❑Not
'humidification/dehumidification❑Not
Applicable j
system.
C403AJ,
"Thermostatic controls have a 5 OF
I
❑Complies 'Requirement
will be met.
2
deadband.❑Does
Not
[FI38]3❑Not
Observable;
❑Not Applicable
C403.2A,,:i
Temperature controls have setpoint
❑Complies
Requirement will be met.
143
overlap restrictions.❑Does
Not
[FI20]3❑Not
Observable;
,I
;❑Not Applicable
C403,2 4
' Each zone equipped with setback
❑Complies ;Requirement
will be met.
2
controls using automatic time clock or
;❑Does Not
[FI39]3
programmable control system.❑Not
Observable;
❑Not Applicable
C403.2.4:
-; Automatic Controls; Setback to 55"F❑Complies
;Requirement
will be met.
2,11 I;
1(heat) and 850F (cool); 7-day clock, 2-
❑Does Not
C403.2A,
hour occupant override, 10-hour
;❑Not Observable;
2.2 -:;
[F14013.. ;;:i❑Not
backup
Applicable
C403.2.4.
Systems include optimum start❑Complies
Requirement will be met.
23 ''controls.
'❑Does Not
[FI41]3
;❑Not Observable;
;❑Not Applicable
C4033:4 1:,
Systems include optimum start
❑Complies
Requirement will be met,
2.3 :.I
controls.
Not
[F]4113
;❑Not Observable;
I❑Not Applicable
C404.3
'I Heat traps installed on supply and
;❑Complies
Requirement will be met.
[FI11)3 ';
dl discharge piping of non -circulating
j❑Does Not
systems.
j❑Not Observable 'I
I❑Not
Applicable
1 High Impact (Tier 1) 2'r Medium Impact (Tier 2) 3.. Law Impact (Tier 3)
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename: Page 12 of 15
Section
#
'Final Inspection
Complies?
Comments/Assumptions
& RegJ
C404A `.
; All piping Insulated in accordance with
❑Complies
Requirement will be met.
[FI2512
3
'; section details and Table C403.11.
❑Does Not
P
❑Not Observable
'❑Not Applicable
C404,6.1 i';
Controls are installed that limit the❑Complies
Requirement will be met,
[FI12]3
'operation of a recirculation pump
❑Does Not
`.
installed to maintain temperature of a
❑Not Observable
storage tank. System return pipe is a
Applicable
dedicated return pipe or a cold water❑Not
:.
I supply pipe.
C405.4.1
;Interior installed lamp and fixture❑Complies
See the Interior Lighting fixture schedule for values.
[FI1811
'lighting power is consistent with what❑Does
Not
is shown on the approved lighting
I❑Not Observable,
plans, demonstrating proposed watts
Applicable
;
are less than or equal to allowed❑Not
;watts,
C408.1,1
;Building operations and maintenance❑Complies
Requirement will be met.
[FI57]1
'documents will be provided to the
❑Does Not
;owner, Documents will cover
❑Not Observable)
manufacturers' information,
Applicable
,specifications, programming❑Not
procedures and means of illustrating
j
',to owner how building, equipment and'
systems are intended to be Installed,
maintained, and operated.
C408.2.1
;Commissioning plan developed by❑Complies
;Requirement will be met.
[F12811
'registered design professional or❑Does
Not
;approved agency.
;❑Not Observable;
❑Not Applicable
C408.2.3.
! HVAC equipment has been tested to
!OComplies
Requirement will be met.
1
ensure proper operation.❑Does
Not
[FI31]'
;❑Not Observable;
❑Not Applicable
C408.2.3.
HVAC control systems have been
I❑Complies
Requirement will be met.
2
;tested to ensure proper operation,❑Does
Not
[FI10]1
'calibration and adjustment of controls.
, ❑Not Observable;
❑Not Applicable
C408,23.
;Economizers have been tested to
I❑Complies
Requirement will be met.
3
1 ensure proper operation.
Not
[FI32]1❑Not
Observable
j
❑Not Applicable
C408.2,4
Preliminary commissioning report❑Complies
Requirement will be met.
[FI2911
'completed and certified by registered
❑Does Not
design professional or approved
Observable;
;agency.❑Not
❑Not Applicable
C40825';
Furnished HVAC as -built drawings❑Complies
Requirement will be met.
1 i'I
submitted within 90 days of system❑Does
Not
[FI7]3
,acceptance.
;❑Not Observable;
❑Not Applicable
C408.2.5,
f Furnished as -built drawings for
❑Complies
Requirement will be met.
1 '.
1 electric power systems within 90 days❑Does
Not
[FI1613 I
;of system acceptance.
;❑Not Observable;
❑Not Applicable
1 High Impact (Tier 1) I2+i Medium Impact (Tier 2) 13t Low Impact (Tier 3)
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename: Page 13 of 15
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Req.ID
-
C408.2.5.
An air and/or hydronic system❑Complies
;Requirement will
be met.
3
'balancing report is provided for HVAC
I❑Does Not
[F143]1
'systems.
I❑Not Observable
j❑Not Applicable
C408,2.5.
Final commissioning report due to
1❑Complies ;Requirement will
be met.
4
building owner within 90 days of
❑Does Not
[F130]1
receipt of certificate of occupancy.
'❑Not Observable ;
❑Not Applicable
C4083
;Lighting systems have been tested to
❑Complies 'Requirement will
be met,
[F133]1
ensure proper calibration, adjustment,❑Does
Not
programming, and operation.
❑Not Observable;
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2' Medium Impact (Tier 2) 3:. Low Impact (Tier 3)
Project Titie: PURE Pharmacy Report date: 04/15/19
Data filename: Page 14 of 15
Project Title: PURE Pharmacy Report date: 04/15/19
Data filename: Page 15 of 15