Loading...
HomeMy WebLinkAbout190523 PURE Pharmacy Permit 14-E30PANEL NEW PANEL 'A' LUGS 200 AMPS 120Z208 VOLT 3 PHASE 4 WIRE MAIN BREAKER zoo AMPS USE CKT, N0. LOAD BKR SIZE A B C BKR SIZE LOAD CKT, N0. USE EMERGENCY LIGHTS 1 190 20/1 30/3 2534 2 REMAINING LIGHTS 3 1000 2534 4 CU-1 S-NH REC. 5 1080 2534 6 S-NH HOOD 7 1200 3 /3 2210 8 WOKE AREA #109 REC- 9 900 2210 10 CU-2 11 1080 2210 12 13 1080 25/1 1909 14 F-1 NS-NH REC. 15 1260 20/1 1254 16 F-2 WORK AREA #108 FRIDGE 17 600 400 18 WATER HEATER NS-H REC. 19 1440 1200 20 NS-NH HOOD NS-H HOOD #1 21 1200 1260 22 BREAKROOM REC. NS-H REFRIGERATOR 23 600 720 24 ANTE REC. ANTE REFRIGERATOR 25 600 900 26 STORAGE REC. WAITING REC. 27 1080 1260 28 OFFICE REC. 29 1080 600 30 WAITING WATER COOLER 31 720 1200 32 WAITING COFFEE SPARE 33 900 34 WORK AREA #108 REC. S-H HOOD 35 1200 1500 36 BREAKROOM MICROWAVE NS-H HOOD #2 37 1200 500 38 HOT WATER RECIRC PUMP NS-H HOOD #3 39 1200 1000 40 EF-1,2,3 NS-H DISHWASHER 41 1500 1440 42 S-H REC. EXISTING PANEL TO BE RELOCATED PHASE A. 16883 WATTS BALANCE: 3.0 % AND RECIRCUITED AS SHOWN PHASE B: 17058 WATTS PHASE C 16544 WATTS TOTAL: 50485 WATTS RELEASED FOR CONSTRUCTION Subject t0 compliance with all regulations at State and Local Codes City ofCarmel `/��}� ' V"DwW7110A.0L Y L-WRLRR LCL INPUT RACFCWt VA neal PoIntina. cash wonder, etc 1190 125 14M anowwndowor snW r nun at shcrePeftelowd 0 1.25 0 •Thai t hen 0 75.00 0 • min 0 0 ntowwndow S.C.equipment mu ahu w ek. -2 0w1 1. 31.0 331.35 0 ^a.0. equipment ahu cu e1C. -209 wok -ox. 35925 7537 to ment du ehu w alc. -208 wY 18A i8A 38028 8828 so Telal 157" NON LCL aaterheeter Ima Faster, eeneo Lame counter, ns. who. 18883 1 1B8B9 '••neo des 16200 13100 •^snow wn0ow camrequirement to bederon 0 1 0 eek Tebl 'Does MeiJI 1 47717 4BO wtt-fobs• eb 66 6uk 57.A 208 we -fobs@ auk 132.5 • Tmtl lgWng mW Ia d p r 2D14 NECMkk 220.43(B) •' MCA used Includes 125%of assert mabrper 2014 NEC Annie 220.1INA) •-•Rewptaclwmlo Wdpor20l4NECMok220.44 1N101An@100%,AIother@50% ^^ Show wlndow lighting calculated per 2014 NEC AMcle 220A3N) 200 VA per LF AT enoww.lndow minus actual fighting narrowed APPROXIMATELY 35' APPROXIMATELY 60' ELECTRICAL SYMBOLS ,d111,, DUPLEX RECEPTACLE' YY HUBBELL, MODEL #5362-W IGnn ISOLATED GROUND DUPLEX RECEPTACLE: H HUBBELL, MODEL #IG-5362-OR GFIQGROUND FAULT DUPLEX RECEPTACLE: �" HUBBELL, MODEL #GFRST20SNAPW USBQCOMBINATION USB RECEPTACLE: Yi' EATON, MODEL #TR7756W. W'PAA WEATHERPROOF DUPLEX RECEPTACLE: YY HUBBELL, MODEL GF-5362 WITH AEP ALUMINUM C VER PLATE ,p, QUAD RECEPTACLE: TY TWO (2) HUBBELL, MODEL #5362-W DUPLEX RECEPPTACLES IN A COMMON JUNCTION BOX WITH A 4 GANG COVER PLATE SINGLE POLE SWITCH: $ LUTRON, MODEL #CA-IPS-WH $yI 3-WAY SWITCH: LUTRON, MODEL #DVSTV-WH, 0-10V $D DIMMER SWITCH: LUTRON, MODEL #DVSTV-WH, 0-10V Soso OCCUPANCYEVACANCY DIMMER LUTRON, MAESTRO MODEL #MS-Z101-WH. $Uc UNDERCABINET LIGHTING DIMMER MODEL #IP701-LFZ ® CEILING MOUNTED OCCUPANCE SENSOR'. WATT STOPPER, MODEL #W-1000A. BZ-50 POWER PACK FOR USE WITH WALL SWITCH FOR MANUAL ON/AUTOMATIC OFF CAPABILITIES. $T TIMER SWITCH: BROAD, MODEL #61W. SPECIAL PURPOSE RECEPTACLE JQ JUNCTION BOX R7 COMBO VOICE/DATA OUTLET Q VOICE OUTLET FOR WALL PHONE O TELEVISION OUTLET E' DISCONNECT SANCTI O' PULL STATION LK CEILING MOUNTED HORN/STROBE Q CEILING MOUNTED STROBE ONLY Q SMOKE DETECTOR ED PHOTOCELL © DOOR CONTACT © CAMERA LOCATION EJ PANIC SWITCH KEY PAD NON SECURITY MONITOR El CARD READER A TRANSFORMER EXISTING SERVICE O O HOUSING O • O O O O O O Q1 RISER DIAGRAM NOTES 1. CONTRACTOR SHALL OBTAIN AUAI'. ABLE FAULT CURRENT RATING AND PROVIDE PROTECL I FOR MAIN CIRCUIT BREAKER AND ALL BRANCII '.I 9 AS REQUIRED. 2. CONTRACTOR TO MAINTAIN A - F �rV RED CLEARENCFS PER ARP" - II' r s.FC ELECTRICAL ABBREVIATION ELECTRICAL WORK NOTES 1, THE ENTIRE INSTALLATION SHALL BE MADE IN STRICT ACCORDANCE WITH THE LArvDLORD'S REQUIREMENTS. A AMPERES) 2. ELECTRICAL WORK SHALL BE COMPLETE IN EVERY DETAIL AND ALL MISCELLANEOUS ITEMS OF MATERIAL AND AFF ABOVE FINISHED FLOOR LABOR NECESSARY TO COMPLETE THE WORK DESCRIBED, SHOWN OR REASONABLY IMPLIED ON DRAWINGS OR SPECIFICATIONS SHALL BE INCLUDED IN THE CONTRACT. CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS TO AHJ AUTHORITY HAVING JURISDICTION THE WORK WHERE REQUESTED BY THE OWNER, WHEN SUCH ADJUSTMENTS ARE NECESSARY To PROPER OPERATION AND WITHIN THE INTENT OF THE CONTRACT. 3. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND VIEW ALL EXISTING CONDITIONS BEFORE SUBMITTING A AC AMPERES INTERRUPTING CURRENT PROPOSAL FOR THE WORK AS DEscRIBEO ANo seowN. rv0 EXTRAS WILL BE ENTERTAINED FOR GAILURE TO MAKE THIS VEIT. ATS AUTOMATIC TRANSFER SWITCH 4. ELECTRICAL CONTRACTOR SHALL ACCEPT SOLE AND COMPLETE RESPONSIBILITY FOR CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. C CIRCUIT 5. CONFORM TO GENERAL CONTRACTOR'S SCHEDULE AND INSTRUCTIONS THROUGHOUT THE DURATION OF THE PROJE..• AS REQUIRED TO COMIPTY IN EVERY WAY NECESSARY. AT NO TIME SHALL ANY WORK BE UNDERTAKEN CT CURRENT TRANSFORMER WHC4 $FAIL II E F RE.9FF THE NORMAL OPERATION OF BUSINESS. ANY SHUTDOWN MUST OCCUR AFTER R Fi ['I ST BE CLEARED WITH THE MANAGEMENT WITH PROPER PRIOR NOTICE GIVEN �I TC I I I DIST DISTRIBUTION -1I 6 COrT I "TF- T :;;NER OF ERRORS, OMISSIONS OR DISCREPANCIES BEFORE CONSTRUCTION OR Ti C T , T FCT [ ORK, OR, FAILING SUCH NOTICE, SHALL BE RESPONSIBLE FOR CORRECTING DS DISCONNECT SWITCH SAME WITI I.. T TO TENANT, ARCHITECT OR ENGINEER. 7, ORDER ECIII=:'FJ- ON A TIMELY BASIS (WITHIN 5 DAYS OF RECEIPT OF CONTRACT) TO MAINTAIN CONSTRUCTION EC ELECTRICAL CONTRACTOR SCHEDULE. 8. SUBMIT ELECTF FLO COPIES OF SHOP DRAWINGS OF ALL EQUIPMENT FOR REVIEW BY THE ARCHITECT/ENGINEER. EF EXHAUST FAN ONE (7) COPIES WILL BE RETAINED FOR RECORD. ONLY FURNISH SYSTEMS, EQUIPMENT AND MATERIAL IN COMPLIANCE WITH APPROVED SHOP DRAWINGS. EM EMERGENCY X WORK SHALL INCLUDE STARTUP OF ALL SYSTEMS, FURNISHING OF OPERATING AND MAINTENANCE INSTRUCTIONS, WARRANTEE FOR ALL EQUIPMENT AND ONE YEAR GUARANTEE OF ALL WORKMANSHIP, COMMENCING ON DATE OF ACCEPTANCE BY THE TENANT. EX EXISTING 10. WORK SHALL ALSO INCLUDE FULL ONE (1) YEAR MAINTENANCE, PARTS AND SERVICE CONTRACT FOR ALL EQUIPMENT FURNISHED UNDER THE CONTRACT. EXR EXISTING RELOCATED 11, ALL WIRE SHALL BE COPPER. MINIMUM SIZE #12 AWG. ALL CONDUCTORS #10 AND SMALLER SHALL HAVE LARGER THAN #10 SHALL HAVE TE 'THEM" INSULATION. TYPE THEW" INSULATION. CONDUCTORS ULIPS F FUSE 12, ALL WIRE SHALL BE IN CONDUIT AND SHALL BE CONCEALED FROM VIEW. EXPOSED CONDUIT SHALL BE INSTALLED IN STRAIGHT LINES PARALLEL WITH OR PERPENDICULAR TO COLUMN LINES OR BEAMS AND SHALL FLA FULL LOAD AMPS BE SEPERATED BY AT LEAST 3" INCHES FROM DOMESTIC WATER LINES WHENEVER ALONG SIDE OR ACROSS SUCH LINES. ROVER IS NOT PERMITTED. FLEXIBLE CONDUIT OR TYPE MC CABLE MAY BE USED FOR GO GARBAGE DISPOSAL FIXTURE AND EQUIPMENT CONNECTIONS ONLY, AND WHERE SO USED SHALL BE GROUNDED WITH A SEPERATE FULL SIZED GREEN GROUNDING CONDUCTOR. FLEXIBLE CONDUIT CONNECTIONS SHALL BE LIMITED TO 3'-0" GC GENERAL CONTRACTOR IN LENGTH. CONDUIT EXPOSED TO WEATHER SHALL BE RIGID. ALL OTHER CONDUIT SHALL BE EMT. CONDUIT FITTINGS SHALL BE COMPRESSION OR THREADED TYPE, USE OF SET SCREW FITTINGS IS NOT ACCEPTABLE. GFI GROUND FAULT INTERRUPTER 13. CONDUIT IN FINISHED AREAS SHALL BE CONCEALED. CONDUIT IN UNFINISHED AREAS MAY BE EXPOSED. 14. HOME RUNS OVER 100IN LENGTH SHALL BE #10 WIRE. AND GROUND 15. CONTRACTOR SHALL ENSURE THAT ENTIRE INSTALLATION IN ACCORDANCE WITH N.E.C. ARTICLE 110-26 AND THAT ALL REQUIRED OPERATING AND MAINTENANCE CLEARANCES ARE MAINTAINED AND ACCOUNTED FOR. ADJUSTMENTS HP HORSE POWER TO LAYOUT SHOWN TO ACCOMMODATE CLEARANCE REQUIREMENTS SHALL BE DISCUSSED WITH ARCHITECT AND/OR ENGINEER SO AS TO MINIMIZE IMPACT ON OTHER SYSTEMS. CONTACT ARCHITECT AND/OR ENGINEER IS ISOLATED GROUND FOR DISPOSITION. 16. CONTRACTOR SHALL OBTAIN AVAILABLE FAULT CURRENT RATING AND PROVIDE PROTECTION FOR MAIN CIRCUIT KVA KILOVOLT AMPERE(S) BREAKER AND BRANCH DEVICES AS REQUIRED. 17, SEAL ALL PENETRATIONS THROUGH WALLS, CEILINGS. FLOORS. ETC, SO THAT THEY ARE AIR, WATER AND FIRE TIGHT. KW KILOWATT S ( ) "SAD" 18. LIGHTING CIRCUITS WHICH ARE SWITCHED AT PANELS SHALL BE FITTED WITH TYPE BREAKERS SUITABLE FOR SWITCHING SERVICE MCA MINIMUM CIRCUIT AMPERE S ( ) 19. FURNISH AND INSTALL TYPEWRITTEN PANEL DIRECTORYBES). IDENTIFY AND LABEL ALL ELECTRICAL SERVICE EQUIPMENT. MOB MAIN CIRCUIT BREAKER 20. FURNISH TWO (2) COPIES OF THE ELECTRIC RISER DIAGRAM AND PANEL DIRECTORYNES) TO THE TENANT FOR REVIEW AND APPROVAL, OR SUBMIT A LETTER TO THE TENANT CONFIRMING THAT THE SYSTEM WAS INSTALLED MOO MAIN LUG ONLY AS PER PLANS AND SPECIFICATIONS. 21. FURNISH ALL EQUIPMENT MANUALS AND WARRANTIES TO TENANT AT THE COMPLETION OF THE PROJECT. NIC NOT IN CONTRACT 22. WIRE EMERGENCY BALLAST AND BATTERY LIGHTS ON SAME CIRCUIT IN AREA AND AHEAD OF LOCAL SWITCHING. NL NIGHT LIGHT 23, ALL LIGHTING FIXTURES WILL BE FURNISHED BY THE CONTRACTOR. 24. SWITCHES, NOT OTHERWISE CALLED OUT, SHALL BE MOUNTED T-6" ABOVE FLOOR. PH PHASE 25. RECEPTACLES AND TELEPHONE OUTLETS IN SPACE SHALL BE MOUNTED AT 18" A F.F. UNLESS NOTED. RECEPTACLES AND COVERS SHALL BE AS CALLED FOR IN THE SPECIFICATIONS. PNL PANEL 26, ALL COVERPLATES FOR ALL DEVICES SHALL BE AS REQUIRED TO MATCH ADJACENT FINISHES - COORDINATE WITH OWNER. RECHT RECEPTACLE 27. VERIFY EXACT LOCATION OF OUTLETS AND DEVICES WITH OWNER'S REPRESENTATIVE PRIOR TO INSTALLATION. FURNISH AND INSTALL OUTLET BOXES, DEVICES, COVERPLATES AND FLANGES AS REQUIRED. SW SWITCH 28, IG AND GFI RECEPTACLES SHALL BE RATED AT 20 AMPERES AND SHALL HAVE A DEDICATED INSULATED GREEN GROUND WIRE, THE GROUND WIRE SHALL BE RUN CONTINUOUS AND UNSPLICED BETWEEN THE DEVICE AND THE UON UNLESS OTHERWISE NOTED PANEL GROUND BUS. 29. MOUNTING HEIGHTS OF EQUIPMENT NOT SPECIFICALLY CALLED FOR ARE NOTED ON ARCHITECTURAL DRAWINGS - V VOLT(S) SEE ARCHITECTURAL DRAWINGS TO COORDINATE. 30. SUPPORT ALL FIXTURES ACROSS CEILING TEES OR FROM STRUCTURE ABOVE. IN NO CASE SHALL CEILING TILES INWATT(S) OR PLASTER CEILING SUPPORT ANY FIXTURES. WP WEATHERPROOF 31, SUPPORT ALL FIXTURES WITH UNISTRUT AS REQUIRED. 32. WORK SHALL INCLUDE STARTUP OF ALL SYSTEMS, FURNISHING OF OPERATING AND MAINTENANCE INSTRUCTIONS AND ONE YEAR GUARANTEE, COMMENCING ON DATE OF ACCEPTANCE BY THE TENANT. 33. FURNISH ALL MATERIAL AND EQUIPMENT AS SPECIFIED, EXCEPT WHERE SPECIFIC APPROVAL FOR SUBSTITUTION IS GIVEN BY THE OWNER. 34. PROPOSAL SHALL BE BASED ON SPECIFIED MATERIAL AND EQUIPMENT. IN ORDER TO PROMOTE COMPETITION, HOWEVER, BIDDERS ARE ENCOURAGED TO SUBMIT ALTERNATE PROPOSALS ON ANY ALTERNATE MATERIALS AND/OR EQUIPMENT THEY WISH TO PROPOSE, INCLUDING ANY PRICE CHANGES EFFECTED BY ACCEPTANCE OF ALTERNATES. 35. COST OF ANY CHANGES REQUIRED BY OTHER TRADES DUE TO SUBSTITUTION OF ALTERNATE EQUIPMENT SHALL BE INCLUDED IN THE ALTERNATE PROPOSAL. 36. UPON COMPLETION OF WORK, PREPARE LIGHTING AND POWER PROJECT RECORD RECORD SET. PRESENT THE COMPLETED DRAWINGS TO THE OWNER. AS -BUILT DRAWINGS SHALL INCLUDE ALL BRANCH CIRCUIT WORK, ANY PANELBOARD INFORMATION, FINAL SWITCHING. ETC. RECORD SETS SHALL BE IN PDT AND CAD FORMAT. 37, ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE FIRE PROOFED TO THE SAME OR GREATER RATING THAN THAT OF THE ASSEMBLY. WHERE CONFLICT OCCURS. NOTIFY THE ARCHITECT. 38, ALL FUSES 600 AMPERES OR LESS SHALL BE UL LISTED, CLASS RK1 OR J. LOW -PEAK. DUAL ELEMENT. TIME DELAY 600 VOLT. ACCEPTABLE MANUFACTURES ARE SUSSMAN, GOULD OR SHAWMUF 39, VERIFY LOCAL CONDITIONS AT SITE. 40, COMPLY WITH ALL APPLICABLE CODES. 41, SECURE AND PAY FOR ALL REQUIRED PERMITS ELECTRICAL RISER DIAGRAM NOT TO SCALE NL/M I. 120/208 V. 3 PHASE, 4 WIRE SERVICE FROM UTILITY COMPANY TO REMAIN 2 EXISTING METER TO REMAIN. ENGINEERING SURVEY UNABLE TO DETERMINE WHICH METER/SWITCH SERVES THIS SPACE. CONTRACTOR TO VERIFY PRIOR To BID 50 INDICATED MODIFICATIONS CAN BE PERFORMED. 3. EQUIPMENT IS EXISTING (UNKNOWN SERVICE)- NO CHANGE OR MODIFICATION ANTICIPATED OR CONTEMPLATED AS PART OF THIS WORK. 4, 120/208 V, 3 PHASE, 4 WIRE, 200 A. NEW FEEDER TO SPACE G-#3/0 AWG-2"0). CONTRACTOR TO COORDINATE START POINT OF ORIGINATION AND DISTRIBUTION - UTILIZE EXISTING FEEDER IF LENGTH PERMITS. 5, ASSUMED METER FOR SPACE TO REMAIN - VERIFY IN FIELD PRIOR TO BID. CONTACT ENGINEER OF RECORD FOR DISPOSITION IF NOT AS ASSUMED, 6. EXTEND EXISTING 200 AMP (4-#3/0 AWG-2"0) TO NEW PANEL IF LENGTH PERMITS - SEE NOTE 4 ABOVE - IF NOT FURNISH ADD INSTALL NEW 4-#3/0 AWG-2"C) BACK TO POINT OF DISTRIBUTION. 7, DO NOT SPLICE SERVICE ENTRANCE CONNECTIONS. 8 EXISTING DISCONNECT (NIC) TO REMAIN. 9. REMOVE EXISTING PANEL. 10, NEW 120/208 V, 3 PHASE, 4 WIRE - 200 AMP PANEL. SQUARE D, MODEL #NOOD. 11, JUNCTION BOX IF NEEDED TO EXTEND FEEDERS. Ia .10. ARCHITECTS, PC a184 TECHNOLOGY DRIVE FISHERS, IN 41038 TEL 317558.2822 FAX 317.558.2827 rvlw.mdemhiack.am SP_ NC=R �NGINEE2ING- 1533 EAST NORTHFIELD DRIVE SUITE 400 BWWW SPENCGERMEP CON J Fm W J Q U_ `M r tU W J W VU. 34C3982 STATE OF d � Q 9Je U� J � EW M ow. W DLL 0 NFM EF0 s zQ LZ 'o'aa OEM o zSo �3r oga ova o3 �m DATE: 05/30/19