HomeMy WebLinkAbout190523 PURE Pharmacy Permit 15-E40SECTION 16A GENERAL ELECTRICAL REQUIREMENTS:
16A 1 GENERAL INSTRUCTIONS
16A 1-1 GENERAL REQUIREMENTS
ALL REQUIREMENTS UNDER DIVISION 1 AND THE GENERAL AND
SUPPLEMENTARY CONDITIONS OF THESE SPECIFICATIONS APPLY TO
THIS SECTION AND DIVISION. WHERE THE REQUIREMENTS OF THIS
SECTION AND DIVISION EXCEED THOSE OF DIVISION 1, THIS SECTION
AND DIVISION TAKE PRECEDENCE. BECOME THOROUGHLY FAMILIAR
WITH ALL THEIR CONTENTS AS TO REQUIREMENTS THAT AFFECT THIS
DIVISION, SECTION OR BOTH. WORK REQUIRED UNDER THIS DIVISION
INCLUDES ALL MATERIAL, EQUIPMENT, APPLIANCES, AND LABOR
REQUIRED TO COMPLETE THE ENTIRE ELECTRICAL SYSTEM AS
REQUIRED BY THE DRAWINGS AND SPECIFICATIONS, OR REASONABLY
INFERRED TO BE NECESSARY TO FACILITATE EACH SYSTEM'S
FUNCTIONING AS IMPLIED BY THE DESIGN AND THE EQUIPMENT
SPECIFIED.
THE SPECIFICATIONS AND DRAWINGS FOR THE PROJECT ARE
COMPLEMENTARY, AND PORTIONS OF THE WORK DESCRIBED IN ONE,
SHALL BE PROVIDED AS IF DESCRIBED IN BOTH. IN THE EVENT OF
DISCREPANCIES, NOTIFY THE ENGINEER AND REQUEST CLARIFICATION
PRIOR TO PROCEEDING WITH THE WORK INVOLVED.
DRAWINGS ARE GRAPHIC REPRESENTATIONS OF THE WORK UPON
WHICH THE CONTRACT IS BASED. THEY SHOW THE MATERIALS AND
THEIR RELATIONSHIP TO ONE ANOTHER, INCLUDING SIZES, SHAPES,
LOCATIONS, AND CONNECTIONS. THEY ALSO CONVEY THE SCOPE OF
WORK, INDICATING THE INTENDED GENERAL ARRANGEMENT OF THE
EQUIPMENT, FIXTURES, OUTLETS AND CIRCUITS WITHOUT SHOWING
ALL OF THE EXACT DETAILS AS TO ELEVATIONS, OFFSETS, CONTROL
LINES, AND OTHER INSTALLATION REQUIREMENTS. USE THE DRAWINGS
AS A GUIDE WHEN LAYING OUT THE WORK AND TO VERIFY THAT
MATERIALS AND EQUIPMENT WILL FIT INTO THE DESIGNATED SPACES,
AND WHICH, WHEN INSTALLED PER MANUFACTURERS' REQUIREMENTS,
WILL ENSURE A COMPLETE, COORDINATED, SATISFACTORY AND
PROPERLY OPERATING SYSTEM.
DRAWINGS ARE SCHEMATIC IN NATURE, SHOW THE VARIOUS
COMPONENTS OF THE SYSTEMS APPROXIMATELY TO SCALE AND
ATTEMPT TO INDICATE HOW THEY SHALL BE INTEGRATED WITH OTHER
PARTS OF THE WORK. FIGURED DIMENSIONS TAKE PRECEDENCE TO
SCALED DIMENSIONS. DETERMINE EXACT LOCATIONS BY JOB
MEASUREMENTS, BY CHECKING THE REQUIREMENTS OF OTHER
TRADES, AND BY REVIEWING ALL CONTRACT DOCUMENTS. CORRECT
ERRORS THAT COULD HAVE BEEN AVOIDED BY PROPER CHECKING AND
INSPECTION, AT NO ADDITIONAL COST TO THE OWNER.
SPECIFICATIONS DEFINE THE QUALITATIVE REQUIREMENTS FOR
PRODUCTS, MATERIALS, AND WORKMANSHIP UPON WHICH THE
CONTRACT IS BASED.
16A 1 —2 DEFINITIONS
WHENEVER USED IN THESE SPECIFICATIONS OR DRAWINGS, THE
FOLLOWING TERMS SHALL HAVE THE INDICATED MEANINGS:
1. FURNISH: "TO SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR
UNLOADING, UNPACKING, ASSEMBLING, INSTALLING, AND SIMILAR
OPERATIONS."
2 INSTALL: "TO PERFORM ALL OPERATIONS AT THE PROJECT SITE,
INCLUDING, BUT NOT LIMITED TO, AND AS REQUIRED: UNLOADING,
UNPACKING, ASSEMBLING, ERECTING, PLACING, ANCHORING, APPLYING,
WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING,
TESTING, COMMISSIONING, STARTING UP AND SIMILAR OPERATIONS,
COMPLETE, AND READY FOR THE INTENDED USE."
3 PROVIDE: "TO FURNISH AND INSTALL COMPLETE, AND READY FOR THE
INTENDED USE."
4 FURNISHED BY OWNER (OR OWNER —FURNISHED) OR FURNISHED BY
OTHERS: "AN ITEM FURNISHED BY THE OWNER OR UNDER OTHER
DIVISIONS OR CONTRACTS, AND INSTALLED UNDER THE
REQUIREMENTS OF THIS DIVISION, COMPLETE, AND READY FOR THE
INTENDED USE, INCLUDING ALL ITEMS AND SERVICES INCIDENTAL TO
THE WORK NECESSARY FOR PROPER INSTALLATION AND OPERATION.
INCLUDE THE INSTALLATION UNDER THE WARRANTY REQUIRED BY THIS
DIVISION.
5, ENGINEER: WHERE REFERENCED IN THIS DIVISION, "ENGINEER" IS THE
ENGINEER OF RECORD AND THE DESIGN PROFESSIONAL FOR THE
WORK UNDER THIS DIVISION, AND IS A CONSULTANT TO, AND AN
AUTHORIZED REPRESENTATIVE OF, THE ARCHITECT, AS DEFINED IN
THE GENERAL AND/OR SUPPLEMENTARY CONDITIONS. WHEN USED IN
THIS DIVISION, IT MEANS INCREASED INVOLVEMENT BY, AND
OBLIGATIONS TO, THE ENGINEER, IN ADDITION TO INVOLVEMENT BY,
AND OBLIGATIONS TO, THE "ARCHITECT".
6AHJ: THE LOCAL CODE AND/OR INSPECTION AGENCY (AUTHORITY)
HAVING JURISDICTION OVER THE WORK.
7NRTL: NATIONALLY RECOGNIZED TESTING LABORATORY, AS DEFINED
AND LISTED BY OSHA IN 29 CFR 1910.7 (E.G., ILL, ETL, CSA), AND
ACCEPTABLE TO THE AHJ OVER THIS PROJECT.
8 THE TERMS "APPROVED EQUAL", "EQUIVALENT", OR "EQUAL" ARE USED
SYNONYMOUSLY AND SHALL MEAN "ACCEPTED BY OR ACCEPTABLE TO
THE ENGINEER AS EQUIVALENT TO THE ITEM OR MANUFACTURER
SPECIFIED". THE TERM "APPROVED" SHALL MEAN LABELED, LISTED,
CERTIFIED, OR ALL THREE, BY AN NRTL, AND ACCEPTABLE TO THE AHJ
OVER THIS PROJECT.
16A 1-3 PRE —BID SITE VISIT
PERSONALLY INSPECT THE SITE OF THE PROPOSED WORK AND
BECOME FULLY INFORMED OF CONDITIONS UNDER WHICH THE WORK IS
TO BE DONE. FAILURE TO DO SO WILL NOT BE CONSIDERED
SUFFICIENT JUSTIFICATION TO REQUEST OR OBTAIN EXTRA
COMPENSATION OVER AND ABOVE THE CONTRACT PRICE.
16A 1-4 MATERIAL AND WORKMANSHIP
PROVIDE ALL MATERIAL AND EQUIPMENT NEW AND IN FIRST CLASS
CONDITION. PROVIDE MARKINGS OR A NAMEPLATE FOR ALL MATERIAL
AND EQUIPMENT IDENTIFYING THE MANUFACTURER AND PROVIDING
SUFFICIENT REFERENCE TO ESTABLISH QUALITY, SIZE AND CAPACITY.
ALL WORKMANSHIP SHALL BE OF THE FINEST POSSIBLE BY
EXPERIENCED MECHANICS OF THE PROPER TRADE. IN GENERAL,
PROVIDE THE COMMERCIAL GRADE FOR ALL MATERIALS AND
EQUIPMENT LIGHT DUTY AND RESIDENTIAL TYPE EQUIPMENT WILL NOT
BE ACCEPTABLE.
PROVIDE ALL HOISTS, SCAFFOLDS, STAGING, RUNWAYS, TOOLS,
MACHINERY AND EQUIPMENT REQUIRED FOR THE PERFORMANCE OF
THE ELECTRICAL WORK. STORE AND MAINTAIN MATERIAL AND
EQUIPMENT IN CLEAN CONDITION, AND PROTECTED FROM WEATHER,
MOISTURE, AND PHYSICAL DAMAGE.
FURNISH ONLY MATERIAL AND EQUIPMENT THAT ARE LISTED, LABELED,
CERTIFIED, OR ALL THREE, BY A NATIONALLY RECOGNIZED TESTING
LABORATORY (NRTL), WHENEVER ANY LISTING OR LABELING EXISTS
FOR THE TYPES OF MATERIAL AND EQUIPMENT SPECIFIED.
AT A MINIMUM, GENERAL WORK PRACTICES FOR ELECTRICAL
CONSTRUCTION SHALL BE IN ACCORDANCE WITH NECA 1 (LATEST
EDITION), "STANDARD PRACTICES FOR GOOD WORKMANSHIP IN
ELECTRICAL CONSTRUCTION" .
16A 1-5 MANUFACTURERS
IN OTHER ARTICLES WHERE LISTS OF MANUFACTURERS ARE
''ICE WITH REQUIREMENTS,
RELEASED FOR CONSTRUCTION -MANUFACTURERS SPECIFIED.
Subject to compliance with all regulations 4CTURERS ARE LISTED
of State and local Codes '.DANCE WITH ANY RANKING OR
City offCarmel
�Nq�\D.kMWA�
WHERE MANUFACTURERS ARE NOT LISTED, PROVIDE PRODUCTS
SUBJECT TO COMPLIANCE WITH REQUIREMENTS FROM
MANUFACTURERS THAT HAVE BEEN ACTIVELY INVOLVED IN
MANUFACTURING THE SPECIFIED PRODUCT FOR NO LESS THAN 5
YEARS.
16A 1-6 COORDINATION
COORDINATE ALL WORK WITH OTHER DIVISIONS AND TRADES SO THAT
VARIOUS COMPONENTS OF THE ELECTRICAL SYSTEMS ARE INSTALLED
AT THE PROPER TIME, FIT THE AVAILABLE SPACE, AND ALLOW PROPER
SERVICE ACCESS TO ALL EQUIPMENT. REFER TO ALL DRAWINGS,
INCLUDING, BUT NOT LIMITED TO, CIVIL, ARCHITECTURAL, STRUCTURAL,
MECHANICAL, AND PLUMBING, AND TO RELEVANT EQUIPMENT
SUBMITTALS AND SHOP DRAWINGS TO DETERMINE THE EXTENT OF
CLEAR SPACES. MAKE ALL OFFSETS REQUIRED TO CLEAR EQUIPMENT,
BEAMS AND OTHER STRUCTURAL MEMBERS, AND TO FACILITATE
CONCEALING RACEWAYS IN THE MANNER ANTICIPATED IN THE DESIGN.
PROVIDE MATERIALS WITH TRIM THAT WILL FIT PROPERLY THE TYPES
OF CEILING, WALL, OR FLOOR FINISHES ACTUALLY INSTALLED.
16A 1-7 ORDINANCES CODES AND STANDARDS
COMPLY, AT A MINIMUM, WITH NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) STANDARDS, STATE AND LOCAL BUILDING CODES,
AND ALL OTHER APPLICABLE CODES AND ORDINANCES FOR
PERFORMANCE, WORKMANSHIP, EQUIPMENT, AND MATERIALS.
ADDITIONALLY, COMPLY WITH RULES AND REGULATIONS OF PUBLIC
UTILITIES AND MUNICIPAL DEPARTMENTS AFFECTED BY CONNECTION
OF SERVICES.
WHERE CONFLICTS BETWEEN VARIOUS CODES, ORDINANCES, RULES,
AND REGULATIONS EXIST, COMPLY WITH THE MOST STRINGENT.
WHEREVER REQUIREMENTS OF THESE SPECIFICATIONS, DRAWINGS,
OR BOTH, EXCEED THOSE OF THE ABOVE ITEMS, THE REQUIREMENTS
OF THESE SPECIFICATIONS, DRAWINGS, OR BOTH, SHALL GOVERN.
CODE COMPLIANCE, AT A MINIMUM, IS MANDATORY. CONSTRUE
NOTHING IN THESE CONSTRUCTION DOCUMENTS AS PERMITTING
WORK NOT IN COMPLIANCE, AT A MINIMUM, WITH THESE CODES.
BRING ALL CONFLICTS OBSERVED BETWEEN CODES, ORDINANCES,
RULES, REGULATIONS, REFERENCED STANDARDS, AND THESE
DOCUMENTS TO THE ENGINEER'S ATTENTION FOR FINAL RESOLUTION.
CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY VIOLATION OF THE
LAW.
PROVIDE AND MAINTAIN ALL NECESSARY SIGNAL LIGHTS AND GUARDS
FOR THE SAFETY OF THE PUBLIC. OBTAIN AND PAY FOR ALL PERMITS
FOR WORK IN THIS DIVISION.
16A 1-8 PROTECTION OF EQUIPMENT AND MATERIALS
STORE AND PROTECT FROM DAMAGE EQUIPMENT AND MATERIALS
DELIVERED TO JOB SITE IN ACCORDANCE WITH MANUFACTURERS'
RECOMMENDATIONS. FOR MATERIALS AND EQUIPMENT SUSCEPTIBLE
TO CHANGING WEATHER CONDITIONS, DAMPNESS, OR TEMPERATURE
VARIATIONS, STORE INSIDE IN CONDITION SPACES. FOR MATERIALS
AND EQUIPMENT NOT SUSCEPTIBLE TO THESE CONDITIONS, COVER
WITH WATERPROOF, TEAR —RESISTANT, HEAVY TARP OR
POLYETHYLENE PLASTIC AS REQUIRED TO PROTECT FROM PLASTER,
DIRT, PAINT, WATER, OR PHYSICAL DAMAGE. EQUIPMENT AND
MATERIAL THAT HAS BEEN DAMAGED BY CONSTRUCTION ACTIVITIES
WILL BE REJECTED, AND CONTRACTOR SHALL FURNISH NEW
EQUIPMENT AND MATERIAL OF A LIKE KIND.
PLUG OR CAP OPEN ENDS OF CONDUITS WHILE STORED AND
INSTALLED DURING CONSTRUCTION WHEN NOT IN USE TO PREVENT
THE ENTRANCE OF DEBRIS INTO THE SYSTEMS.
16A 1-9 SUBSTITUTIONS
INCLUDE IN THE BASE BID THE PRODUCTS SPECIFICALLY NAMED IN
THESE SPECIFICATIONS OR ON THE DRAWINGS. SUBMIT, IN THE FORM
OF ALTERNATES, WITH BID, PRODUCTS OF ANY OTHER
MANUFACTURERS FOR SIMILAR USE, PROVIDED THE DIFFERENCES IN
COST, IF ANY, ARE INCLUDED FOR EACH PROPOSED ALTERNATE.
PRIOR TO THE BID DATE, SUBSTITUTIONS WILL NOT BE CONSIDERED
UNLESS SUBMITTED [TO THE ARCHITECT,] FOR ENGINEER'S REVIEW, AT
LEAST TEN CALENDAR DAYS PRIOR TO THE DATE FOR RECEIPT OF BIDS.
INCLUDE THE NAME OF THE MATERIAL OR EQUIPMENT FOR WHICH IT IS
TO BE SUBSTITUTED AND A COMPLETE DESCRIPTION OF THE
PROPOSED SUBSTITUTE INCLUDING CUTSHEETS, PHOTOMETRIC DATA,
AND ALL OTHER INFORMATION NECESSARY FOR AN EVALUATION FOR
EACH SUCH REQUEST. PROVIDE FACTORY GENERATED POINT —BY —
POINT CALCULATIONS FOR ALL EXTERIOR LIGHT FIXTURES
(PHOTOMETRIC FILES SUPPLIED SO THE ENGINEER CAN GENERATE A
POINT —BY —POINT DO NOT SUFFICE FOR THE POINT —BY —POINT
CALCULATIONS). PROVIDE INTERIOR POINT —BY —POINT CALCULATIONS
AT THE DISCRETION OF THE ENGINEER. SUBMIT A $100.00 REVIEW FEE
TO THE ENGINEER WITH EACH SUCH POINT —BY —POINT CALCULATION
FOR USE OF ELECTRONIC BASE FILES.
AFTER THE BID DATE, PROPOSALS TO SUBSTITUTE LIGHT FIXTURES
FOR THOSE SHOWN ON THE DRAWINGS OR SPECIFIED HEREIN, WILL
ONLY BE CONSIDERED AS A DEDUCT. SUBMIT PROPOSED
SUBSTITUTIONS SEPARATELY, IN SUBMITTAL FORM, WITH A LIST OF
PROPOSED SUBSTITUTIONS TOGETHER WITH A DEDUCT PRICE FOR
EACH SUBSTITUTION. THE [ARCHITECT,] ENGINEER[, OR BOTH,] WILL
THEN REVIEW PROPOSED SUBSTITUTIONS.
THE ENGINEER WILL HAVE THE FINAL AUTHORITY AS TO WHETHER THE
LIGHT FIXTURE IS AN ACCEPTABLE REPLACEMENT TO THE SPECIFIED
ITEM. THE PROPOSED SUBSTITUTION MAY ALSO BE REJECTED [BY THE
ARCHITECT] FOR AESTHETIC REASONS IF FELT NECESSARY OR
DESIRABLE. IN THE EVENT THE PROPOSED SUBSTITUTIONS HEREIN
DESCRIBED ARE REJECTED, FURNISH THE SPECIFIED ITEM.
16A 1-10 SUBMITTALS
ASSEMBLE AND SUBMIT TO THE ARCHITECT, FOR ENGINEER'S REVIEW,
MANUFACTURERS' PRODUCT LITERATURE FOR MATERIAL AND
EQUIPMENT TO BE FURNISHED, INSTALLED, OR BOTH, UNDER THIS
DIVISION, INCLUDING SHOP DRAWINGS, MANUFACTURERS' PRODUCT
DATA AND PERFORMANCE SHEETS, SAMPLES, AND OTHER SUBMITTALS
REQUIRED BY THIS DIVISION. PROVIDE THE NUMBER OF SUBMITTALS
REQUIRED BY DIVISION 1; HOWEVER, AT A MINIMUM, SUBMIT SEVEN (7)
SETS. BEFORE SUBMITTING, VERIFY THAT ALL MATERIALS AND
EQUIPMENT SUBMITTED ARE MUTUALLY COMPATIBLE AND SUITABLE
FOR THE INTENDED USE, FIT THE AVAILABLE SPACES, AND ALLOW
AMPLE AND CODE —REQUIRED ROOM FOR ACCESS AND MAINTENANCE.
SUBMITTALS SHALL CONTAIN THE FOLLOWING INFORMATION.
SUBMITTALS NOT SO IDENTIFIED WILL BE RETURNED TO THE
CONTRACTOR WITHOUT ACTION:
1, THE PROJECT NAME.
2THE APPLICABLE SPECIFICATION SECTION AND PARAGRAPH.
3THE SUBMITTAL DATE.
4THE CONTRACTOR'S STAMP, WHICH SHALL CERTIFY THAT THE
STAMPED DRAWINGS HAVE BEEN CHECKED BY THE CONTRACTOR,
COMPLY WITH THE DRAWINGS AND SPECIFICATIONS, AND HAVE BEEN
COORDINATED WITH OTHER TRADES.
TRANSMIT SUBMITTALS AS EARLY AS REQUIRED TO SUPPORT THE
PROJECT SCHEDULE. ALLOW FOR TWO WEEKS ENGINEER REVIEW
TIME, PLUS MAILING TIME, PLUS A DUPLICATION OF THIS TIME FOR
RESUBMITTALS, IF REQUIRED. TRANSMIT SUBMITTALS AS SOON AS
POSSIBLE AFTER NOTICE TO PROCEED AND BEFORE CONSTRUCTION
STARTS. THE ENGINEER'S SUBMITTAL REVIEWS WILL NOT RELIEVE THE
CONTRACTOR FROM RESPONSIBILITY FOR ERRORS IN DIMENSIONS,
DETAILS, SIZE OF MEMBERS, OR QUANTITIES; OR FOR OMITTING
COMPONENTS OR FITTINGS; OR FOR NOT COORDINATING ITEMS WITH
ACTUAL BUILDING CONDITIONS.
16A 2-4 ROUGH —IN
16A 1-11 ELECTRONIC DRAWING FILES
IN PREPARATION OF SHOP DRAWINGS, CONTRACTOR MAY, AS AN
OPTION, OBTAIN ELECTRONIC DRAWING FILES IN AUTOCAD OR DXF
FORMAT FROM THE ENGINEER FOR A SHIPPING AND HANDLING FEE OF
$200 FOR A DRAWING SET UP TO 12 SHEETS AND S15 PER SHEET FOR
EACH ADDITIONAL SHEET. CONTACT THE ARCHITECT FOR WRITTEN
AUTHORIZATION; AND, CONTACT THE ENGINEER TO OBTAIN THE
NECESSARY RELEASE AGREEMENT FORM AND TO INDICATE THE
DESIRED SHIPPING METHOD AND DRAWING FORMAT. IF A 100 MB ZIP
DISK OR CD—ROM IS DESIRED, ADD THE APPROPRIATE CHARGE
INDICATED. IN ADDITION TO PAYMENT, ARCHITECT'S WRITTEN
AUTHORIZATION AND ENGINEER'S RELEASE AGREEMENT FORM MUST
BE RECEIVED BEFORE ELECTRONIC DRAWING FILES WILL BE SENT.
16A 1-12 OPERATION AND MAINTENANCE INSTRUCTIONS
SUBMIT TO THE ARCHITECT, FOR ENGINEER'S REVIEW, COPIES EACH OF
OPERATIONS AND MAINTENANCE INSTRUCTION MANUALS,
APPROPRIATELY BOUND INTO MANUAL FORM INCLUDING APPROVED
COPIES OF THE FOLLOWING, REVISED IF NECESSARY TO SHOW SYSTEM
AND EQUIPMENT AS ACTUALLY INSTALLED. PROVIDE THE NUMBER OF
SUBMITTALS REQUIRED BY DIVISION 1; HOWEVER, AT A MINIMUM,
SUBMIT THREE (3) SETS, AND INCLUDE, AT A MINIMUM, THE FOLLOWING
INFORMATION:
1 MANUFACTURERS' CATALOGS AND PRODUCT DATA SHEETS
2 WIRING DIAGRAMS
3MAINTENANCE INSTRUCTIONS
4OPERATING INSTRUCTIONS
5PARTS LISTS
6 TEST REPORTS AS DEFINED IN NETA ATS FOR THE SYSTEMS AND
EQUIPMENT PROVIDED OR FURNISHED OR INSTALLED UNDER THIS
CONTRACT.
7 NAMES, ADDRESSES, TELEPHONE NUMBERS, AND E—MAIL ADDRESSES
OF LOCAL CONTACTS FOR WARRANTEE SERVICES AND SPARE PARTS.
SUBMIT MANUALS PRIOR TO REQUESTING THE FINAL PUNCH LIST AND
BEFORE ANY REQUESTS FOR SUBSTANTIAL COMPLETION. ALSO
PROVIDE ADEQUATE VERBAL INSTRUCTIONS OF SYSTEM OPERATIONS
TO OWNER'S REPRESENTATIVE AT THE COMPLETION OF, AND BEFORE
FINAL ACCEPTANCE OF, THE WORK.
16A 1-13 TRAINING
AT A TIME MUTUALLY AGREED UPON BETWEEN THE OWNER AND
CONTRACTOR, PROVIDE THE SERVICES OF A FACTORY TRAINED AND
AUTHORIZED REPRESENTATIVE TO TRAIN OWNER'S DESIGNATED
PERSONNEL ON THE OPERATION AND MAINTENANCE OF THE
EQUIPMENT PROVIDED FOR THIS PROJECT.
PROVIDE TRAINING TO INCLUDE BUT NOT BE LIMITED TO AN OVERVIEW
OF THE SYSTEM AND/OR EQUIPMENT AS IT RELATES TO THE FACILITY
AS A WHOLE; OPERATION AND MAINTENANCE PROCEDURES AND
SCHEDULES RELATED TO STARTUP AND SHUTDOWN,
TROUBLESHOOTING, SERVICING, PREVENTIVE MAINTENANCE AND
APPROPRIATE OPERATOR INTERVENTION; AND REVIEW OF DATA
INCLUDED IN THE OPERATION AND MAINTENANCE INSTRUCTIONS.
SUBMIT A CERTIFICATION LETTER TO THE ARCHITECT STATING THAT
THE OWNER'S DESIGNATED REPRESENTATIVE HAS BEEN TRAINED AS
SPECIFIED HEREIN. LETTER SHALL INCLUDE DATE, TIME, ATTENDEES
AND SUBJECT OF TRAINING. THE CONTRACTOR AND THE OWNER'S
REPRESENTATIVE SHALL SIGN THE CERTIFICATION LETTER INDICATING
AGREEMENT THAT THE TRAINING HAS BEEN PROVIDED.
SCHEDULE TRAINING WITH OWNER WITH AT LEAST 7 DAYS' ADVANCE
NOTICE.
16A 1-14 WARRANTIES
WARRANT EACH SYSTEM AND EACH ELEMENT THEREOF AGAINST ALL
DEFECTS DUE TO FAULTY WORKMANSHIP, DESIGN OR MATERIAL FOR A
PERIOD OF 12 MONTHS FROM DATE OF SUBSTANTIAL COMPLETION,
UNLESS SPECIFIC ITEMS ARE NOTED TO CARRY A LONGER WARRANTY
IN THE CONSTRUCTION DOCUMENTS OR MANUFACTURER'S STANDARD
WARRANTY EXCEEDS 12 MONTHS. REMEDY ALL DEFECTS, OCCURRING
WITHIN THE WARRANTY PERIOD(S), AS STATED IN THE GENERAL
CONDITIONS AND DIVISION 1.
ALSO WARRANT THE FOLLOWING ADDITIONAL ITEMS:
1ALL RACEWAYS ARE FREE FROM OBSTRUCTIONS, HOLES, CRUSHING,
OR BREAKS OF ANY NATURE.
2 ALL RACEWAY SEALS ARE EFFECTIVE.
3 THE ENTIRE ELECTRICAL SYSTEM IS FREE FROM ALL SHORT CIRCUITS
AND UNWANTED OPEN CIRCUITS AND GROUNDS.
THE ABOVE WARRANTIES SHALL INCLUDE LABOR AND MATERIAL. MAKE
REPAIRS OR REPLACEMENTS WITHOUT ANY ADDITIONAL COSTS TO THE
OWNER.
PERFORM THE REMEDIAL WORK PROMPTLY, UPON WRITTEN NOTICE
FROM THE ENGINEER OR OWNER.
AT THE TIME OF SUBSTANTIAL COMPLETION, DELIVER TO THE OWNER
ALL WARRANTIES, IN WRITING AND PROPERLY EXECUTED, INCLUDING
TERM LIMITS FOR WARRANTIES EXTENDING BEYOND THE ONE YEAR
PERIOD, EACH WARRANTY INSTRUMENT BEING ADDRESSED TO THE
OWNER AND STATING THE COMMENCEMENT DATE AND TERM.
16A 1-15 MISCELLANEOUS REMODELING WORK
PROVIDE ALL DEMOLITION OF EXISTING ELECTRICAL SYSTEMS AND
NEW ELECTRICAL SYSTEM MODIFICATIONS REQUIRED BECAUSE OF
BUILDING REMODELING, AS NOTED ON THE DRAWINGS, OR NECESSARY
FOR PROPER OPERATION AND NEW CONSTRUCTION. REMOVE ALL
ABANDONED CABLES AND WIRING ABOVE ACCESSIBLE CEILINGS AND
VENTILATION SHAFTS.
16A 2 ELECTRICAL WORK
16A 2-1 BUILDING OPERATION
COMPLY WITH THE SCHEDULE OF OPERATIONS AS OUTLINED IN THE
ARCHITECTURAL PORTIONS OF THIS SPECIFICATION. BUILDING SHALL
BE IN CONTINUOUS OPERATION. ACCOMPLISH WORK THAT REQUIRES
INTERRUPTION OF BUILDING OPERATION AT A TIME WHEN THE
BUILDING IS NOT IN OPERATION, AND ONLY WITH WRITTEN APPROVAL
OF BUILDING OWNER AND/OR TENANT. COORDINATE INTERRUPTION OF
BUILDING OPERATION WITH THE OWNER AND/OR TENANT A MINIMUM OF
7 DAYS IN ADVANCE OF WORK.
16A 2-2 COINCIDENTAL DAMAGE
REPAIR ALL STREETS, SIDEWALKS, DRIVES, PAVING, WALLS, FINISHES,
AND OTHER FACILITIES DAMAGED IN THE COURSE OF THIS WORK.
REPAIR MATERIALS SHALL MATCH EXISTING CONSTRUCTION. REPAIR
MATERIALS SHALL GENERALLY MATCH EXISTING CONSTRUCTION. ALL
BACKFILLING AND REPAIRING SHALL MEET ALL REQUIREMENTS OF THE
OWNER, CITY AND OTHERS HAVING JURISDICTION. REPAIR WORK
SHALL BE THOROUGHLY FIRST CLASS. CONFORM TO ALL
REQUIREMENTS OF DIVISION 2 OF THESE SPECIFICATIONS.
16A 2-3 CUTTING AND PATCHING
FOLLOWING THE REQUIREMENTS IN DIVISION 1, CUT WALLS, FLOORS,
CEILINGS, AND OTHER PORTIONS OF THE FACILITY AS REQUIRED TO
PERFORM WORK UNDER THIS DIVISION. OBTAIN PERMISSION OF THE
ENGINEER, OWNER, OR BOTH, BEFORE DOING ANY CUTTING. CUT ALL
HOLES AS SMALL AS POSSIBLE. PATCH WALLS, FLOORS, AND OTHER
PORTIONS OF THE FACILITY AS REQUIRED BY WORK UNDER THIS
DIVISION. ALL PATCHING SHALL BE THOROUGHLY FIRST CLASS AND
SHALL MATCH THE ORIGINAL MATERIAL AND CONSTRUCTION,
INCLUDING FIRE RATINGS IF APPLICABLE.
COORDINATE WITHOUT DELAY ALL ROUGHING —IN WITH OTHER
DIVISIONS. CONCEAL ALL RACEWAYS EXCEPT IN UNFINISHED AREAS
AND WHERE OTHERWISE INDICATED ON THE DRAWINGS.
16A 2-5 SUPPORT SYSTEMS
STEEL SLOTTED SUPPORT SYSTEMS (SLOTTED CHANNEL): COMPLY
WITH MFMA-3, FACTORY —FABRICATED COMPONENTS FOR FIELD
ASSEMBLY; 12—GAUGE, 1-5/8—INCH BY 1-5/8—INCH; COOPER B—LINE, ERICO
INTERNATIONAL CORPORATION, HILTI, INC., POWER —STRUT, THOMAS &
BETTS CORPORATION, UNISTRUT.
FINISHES:
1, RETAIN ONE OR MORE COATING SYSTEMS IN FIRST THREE
SUBPARAGRAPHS BELOW (USUALLY GALVANIZED IS ACCEPTABLE FOR
MOST USES) — STAINLESS STEEL SHOULD NOT REQUIRE ANY
ADDITIONAL FINISHES. IF RETAINING MORE THAN ONE, SPECIFY WHERE
EACH COATING SYSTEM IS REQUIRED. USE STAINLESS STEEL
OUTDOORS OR INDOORS WHERE ADDED CORROSION PROTECTION IS
DESIRED (TYPE 316 STAINLESS STEEL IS AVAILABLE FOR USE IN VERY
CORROSIVE LOCATIONS). CONSULT WITH MANUFACTURER BEFORE
SPECIFYING EITHER STAINLESS TYPES, DUE TO USAGE LIMITATIONS
AND COSTS.
2, METALLIC COATINGS: HOT —DIP GALVANIZED AFTER FABRICATION AND
APPLIED ACCORDING TO MFMA-3.
3 NONMETALLIC COATINGS: MANUFACTURER'S STANDARD PVC,
POLYURETHANE, OR POLYESTER COATING APPLIED ACCORDING TO
MFMA-3.
4PAINTED COATINGS: MANUFACTURER'S STANDARD PAINTED COATING
APPLIED ACCORDING TO MFMA-3.
5STAINLESS STEEL: TYPE 304, PER ASTM A240.
ALUMINUM SLOTTED SUPPORT SYSTEMS (SLOTTED CHANNEL): COMPLY
WITH MFMA-3, TYPE 6063—T6, PER ASTM B221; FACTORY —FABRICATED
COMPONENTS FOR FIELD ASSEMBLY; 12—GAUGE, 1-5/8—INCH BY 1-5/8—
INCH; COOPER B—LINE, ERICO INTERNATIONAL CORPORATION, HILTI,
INC., POWER —STRUT, THOMAS & BETTS CORPORATION, UNISTRUT.
FIELD FABRICATION:
1 WHERE FIELD CUTTING OF STANDARD LENGTHS OF CHANNEL ARE
REQUIRED, MAKE CUTS STRAIGHT AND PERPENDICULAR TO
MANUFACTURED SURFACES.
2, FOR FIELD —CUT OR DAMAGED SURFACES OF COATED CHANNELS,
DRESS CUT ENDS, DAMAGED SURFACES, OR BOTH, WITH AN ABRASIVE
MATERIAL (E.G., FILE, GRINDING STONE, OR SIMILAR) AND CLEANSER TO
REMOVE OILS, RUST, SHARP EDGES AND SHARDS.
3 FOR CHANNEL WITH A FACTORY —APPLIED COATING, RE —FINISH CUT
EDGES WITH A COATING COMPATIBLE WITH THE FACTORY FINISH AND
AS RECOMMENDED BY THE MANUFACTURER (E.G., MANUFACTURER'S
TOUCH—UP PAINT OR ZINC —RICH COLD —GALVANIZING COMPOUND, AS
APPLICABLE).
16A 2-6 PENETRATIONS
COORDINATE SLEEVE SELECTION AND APPLICATION WITH SELECTION
AND APPLICATION OF FIRE —STOPPING SPECIFIED IN DIVISION 7 SECTION
"THROUGH —PENETRATION FIRESTOP SYSTEMS."
ROOFS:
1 COORDINATE ALL ROOF PENETRATIONS WITH ENGINEER, OWNER, AND
AS APPLICABLE, THE ROOFING CONTRACTOR PROVIDING A ROOF
WARRANTY.
2 KEEP ALL RACEWAY PENETRATIONS WITHIN MECHANICAL EQUIPMENT
CURBS WHEREVER POSSIBLE. COORDINATE WITH DIVISION 15 WORK.
3 FLASH AND COUNTERFLASH ALL OPENINGS THROUGH ROOF, AND/OR
PROVIDE PRE —FABRICATED MOLDED SEALS COMPATIBLE WITH THE
ROOF CONSTRUCTION INSTALLED, OR AS REQUIRED BY THE ENGINEER,
OWNER, OR ROOFING CONTRACTOR. ALL ROOF PENETRATIONS SHALL
BE LEAKTIGHT AT THE TERMINATION OF THE WORK AND SHALL NOT
VOID ANY NEW OR EXISTING ROOF WARRANTIES.
WALLS AND FLOORS:
1SLEEVES FOR RACEWAYS AND CABLES
A. STEEL PIPE SLEEVES: ASTM A 53/A 53M, TYPE E, GRADE B,
SCHEDULE 40, GALVANIZED STEEL, PLAIN ENDS AND DRIP RINGS.
B. CAST—IRON PIPE SLEEVES: CAST OR FABRICATED "WALL PIPE,"
EQUIVALENT TO DUCTILE —IRON PRESSURE PIPE, WITH PLAIN ENDS AND
INTEGRAL WATERSTOP, UNLESS OTHERWISE INDICATED.
2 SLEEVES FOR RECTANGULAR OPENINGS: GALVANIZED SHEET STEEL
WITH MINIMUM 0.052—INCH THICKNESS AS INDICATED AND OF LENGTH
TO SUIT APPLICATION.
16B 2-7 FIRE —STOPPING THROUGH PENETRATIONS
FIRE—RESISTANT THROUGH PENETRATION SEALANTS: TWO—PART,
FOAMED —IN —PLACE, SILICONE SEALANT FORMULATED FOR USE IN
THROUGH —PENETRATION FIRE —STOPPING AROUND CABLES, RACEWAYS,
AND CABLE TRAY PENETRATIONS THROUGH FIRE —RATED WALLS AND
FLOORS. SEALANTS AND ACCESSORIES SHALL HAVE FIRE —RESISTANCE
RATINGS INDICATED, AS ESTABLISHED BY TESTING IDENTICAL
ASSEMBLIES IN ACCORDANCE WITH ASTM E 814, BY UNDERWRITERS'
LABORATORIES, INC., OR OTHER NRTL ACCEPTABLE TO AHJ.
ACCEPTABLE MANUFACTURERS:
A. HILTI, INC.
B 3M CORP.
C RECTORSEAL.
DSPECIFY TECHNOLOGY INC.
E, UNITED STATES GYPSUM COMPANY.
SUBMITTALS
1SUBMIT PRODUCT DATA: MANUFACTURER'S SPECIFICATIONS AND
TECHNICAL DATA FOR EACH MATERIAL INCLUDING THE COMPOSITION
AND LIMITATIONS, DOCUMENTATION OF UL FIRESTOP SYSTEMS TO BE
USED AND MANUFACTURER'S INSTALLATION INSTRUCTIONS TO COMPLY
WITH DIVISION 1.
2 MANUFACTURER'S ENGINEERING JUDGMENT IDENTIFICATION NUMBER
AND DRAWING DETAILS WHEN NO UL SYSTEM IS AVAILABLE FOR AN
APPLICATION. ENGINEERING JUDGMENT SHALL INCLUDE BOTH
PROJECT NAME AND CONTRACTOR'S NAME WHO WILL INSTALL
FIRESTOP SYSTEM AS DESCRIBED IN DRAWINGS.
3SUBMIT MATERIAL SAFETY DATA SHEETS PROVIDED WITH PRODUCT
DELIVERED TO JOB —SITE.
16A 2-8 ACCESS DOORS
PROVIDE ACCESS DOORS IN CEILINGS AND WALLS, WHERE INDICATED
OR REQUIRED FOR ACCESS OR MAINTENANCE TO CONCEALED
EQUIPMENT INSTALLED UNDER THIS SECTION. PROVIDE CONCEALED
HINGES, SCREWDRIVER —TYPE LOCK, AND ANCHOR STRAPS.
MANUFACTURED BY MILCOR, ZURN, TITUS, OR EQUAL. OBTAIN
ARCHITECT'S APPROVAL OF TYPE, SIZE, LOCATION AND COLOR BEFORE
ORDERING.
16A 2-9 EQUIPMENT FURNISHED BY OTHERS
PROVIDE NECESSARY EQUIPMENT AND ACCESSORIES THAT ARE NOT
PROVIDED BY THE EQUIPMENT SUPPLIER OR OWNER TO COMPLETE
INSTALLATION OF EQUIPMENT FURNISHED BY OTHERS, IN LOCATIONS
AS INDICATED ON THE DRAWINGS, SPECIFIED HEREIN, OR BOTH.
EQUIPMENT AND ACCESSORIES NOT PROVIDED BY THE EQUIPMENT
SUPPLIER MAY INCLUDE SUCH ITEMS AS FLEXIBLE CORDS AND PL!.1:i.
AS REQUIRED FOR PROPER OPERATION OF THE COMPLETE SYSTEM, r.
ACCORDANCE WITH THE MANUFACTURERS' INSTRUCTIONS.
BE RESPONSIBLE FOR CORRECT ROUGH —IN DIMENSIONS, AND VERIFY
THEM WITH ENGINEER, OWNER'S REPRESENTATIVE, EQUIPMENT
SUPPLIER, OR ALL THREE, PRIOR TO ROUGH —IN AND SERVICE
INSTALLATIONS.
16A 2-10 CLEANING
IN ADDITION TO THE REQUIREMENTS OF DIVISION 1, REMOVE FROM THE
PREMISES DIRT AND REFUSE RESULTING FROM THE PERFORMANCE OF
THE ELECTRICAL WORK, AS REQUIRED, TO PREVENT ACCUMULATION.
COOPERATE IN MAINTAINING REASONABLY CLEAN PREMISES AT ALL
TIMES. IMMEDIATELY PRIOR TO FINAL INSPECTION, MAKE A FINAL
CLEANUP OF DIRT AND REFUSE RESULTING FROM THE WORK. CLEAN
ALL MATERIAL AND EQUIPMENT INSTALLED UNDER THIS DIVISION.
REMOVE DIRT, DUST, PLASTER, STAINS AND FOREIGN MATTER FROM
ALL SURFACES. TOUCH UP AND RESTORE ALL DAMAGED FINISHES TO
THEIR ORIGINAL CONDITION.
16A 2-11 ADJUSTING ALIGNING AND TESTING
ADJUST, ALIGN, AND TEST ALL ELECTRICAL EQUIPMENT ON THIS
PROJECT PROVIDED UNDER THIS DIVISION AND ALL ELECTRICAL
EQUIPMENT FURNISHED BY OTHERS FOR INSTALLATION OR WIRING
UNDER THIS DIVISION, FOR PROPER OPERATION.
TEST ALL SYSTEMS AND EQUIPMENT ACCORDING TO THE
REQUIREMENTS IN NETA ATS (LATEST EDITION) AND ALL ADDITIONAL
REQUIREMENTS SPECIFIED IN FOLLOWING SECTIONS.
MAINTAIN THE FOLLOWING ON THE PROJECT PREMISES AT ALL TIMES: A
TRUE RMS READING VOLTMETER, A TRUE EMS READING AMMETER, AND
A MEGOHMMETER INSULATION RESISTANCE TESTER. PROVIDE TEST
DATA READINGS AS REQUESTED OR AS REQUIRED BY THE ENGINEER.
16A 2-12 EQUIPMENT IDENTIFICATION
PROVIDE EQUIPMENT IDENTIFICATION NAMEPLATES:
1ON ALL PANELBOARDS AND SWITCHES.
NAMEPLATES:
1ENGRAVED, CONTRASTING COLOR, THREE —LAYER, LAMINATED PLASTIC
INDICATING THE NAME OF THE EQUIPMENT, LOAD, OR CIRCUIT AS
DESIGNATED ON THE DRAWINGS AND IN THE SPECIFICATIONS:
2. FIELD —APPLIED PERMANENT EPDXY ADHESIVE, COMPATIBLE WITH THE
EQUIPMENT FINISH.
3. ATTACHMENT METHOD SHALL BE ACCEPTABLE TO THE
MANUFACTURERS OF THE EQUIPMENT TO WHICH THE NAMEPLATES
ARE BEING APPLIED.
4. COLOR: BLACK BACKGROUND WITH WHITE LETTERS FOR NORMAL
POWER. LETTER HEIGHT: 1/2—INCH MINIMUM.
16A 2-13 SYSTEM START UP
PRIOR TO STARTING UP THE ELECTRICAL SYSTEMS:
1CHECK ALL COMPONENTS AND DEVICES.
2. LUBRICATE ITEMS ACCORDINGLY.
3. TIGHTEN SCREWS AND BOLTS FOR CONNECTORS AND TERMINALS
ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE —TIGHTENING
VALUES. IF MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED,
USE THOSE SPECIFIED IN UL 486A.
4. ADJUST TAPS ON EACH TRANSFORMER FOR RATED SECONDARY
VOLTAGE.
5. CHECK AND RECORD BUILDING'S SERVICE ENTRANCE VOLTAGE,
GROUNDING CONDITIONS, GROUNDING RESISTANCE, AND PROPER
PHASING,
6. IF ANY CHANGES ARE MADE TO PANEL SCHEDULES ON DRAWINGS, RE—
BALANCE ALL SINGLE—PHASE LOADS AT EACH PANELBOARD,
REDISTRIBUTING BRANCH CIRCUIT CONNECTIONS UNTIL BALANCE IS
ACHIEVED. DO NOT TYPE UP FINAL PANELBOARD DIRECTORIES UNTIL
ALL RE —BALANCING AND REDISTRIBUTION OF CIRCUITS ARE COMPLETE.
7. REPLACE ALL BURNED —OUT LAMPS AND LAMPS USED FOR TEMPORARY
CONSTRUCTION LIGHTING IN PERMANENT LIGHT FIXTURES.
8. AFTER ALL SYSTEMS HAVE BEEN INSPECTED AND ADJUSTED, CONFIRM
ALL OPERATING FEATURES REQUIRED BY THE DRAWINGS AND
SPECIFICATIONS AND MAKE FINAL ADJUSTMENTS AS NECESSARY.
16A 3 EXISTING EQUIPMENT REUSE AND REMOVAL
REMOVE ALL EXISTING WIRING, LIGHT FIXTURES, EXPOSED CONDUITS
AND OTHER ELECTRICAL INSTALLATIONS NOT REUSED PRIOR TO
SUBSTANTIAL COMPLETION OF THE WORK.
EXISTING RACEWAYS MAY BE REUSED IF THEIR POINTS OF
TERMINATIONS ARE SUITABLE; IF THEY ARE CLEAN INSIDE WITH NO
EVIDENCE OF RUST OR BURRS; IF FREE FROM CRACKS, FLATTENED
SECTIONS OR SHARP BENDS; AND, IF SUITABLY LOCATED TO AVOID
CONFLICTS WITH OTHER TRADES OR INSTALLATIONS. CAREFULLY
"FISH" ALL EXISTING CONDUITS REUSED UNDER THIS CONTRACT TO
REMOVE ALL DEBRIS AND OBSTRUCTIONS, AND SWAB UNTIL ALL
MOISTURE IS REMOVED.
CUT, PATCH, AND REPAIR WHERE REQUIRED FOR NEW ELECTRICAL
INSTALLATIONS, AND PATCH AND REPAIR ALL SURFACE DAMAGE
RESULTING FROM THIS WORK. CUT FLUSH WITH THE FLOOR AND PLUG
AT BOTH ENDS, RACEWAYS STUBBED ABOVE THE FLOOR AND NOT
USED AT SUBSTANTIAL COMPLETION OF THE WORK.
RELOCATE ALL EXISTING ELECTRICAL SYSTEMS REQUIRED TO BE IN
OPERATION AT SUBSTANTIAL COMPLETION OF THE CONTRACT, IF
REQUIRED, AS A RESULT OF WORK INCLUDED UNDER THIS CONTRA`
EVEN IF NOT SPECIFICALLY INDICATED IN THE DRAWINGS OR
SPECIFICATIONS.
Ia
',IC. ARCHITECTS PC
as4 TECHNOLOGY DRIVE
FISHERS, IN 46039
TEL 517!iSS a22
FAX S17,MS.LS27
mormderchimcesam
SP_ NC=R
=NGINEE2ING-
1533 EAST NQRTHFIELD DRIVE
SUITE 400
DW W SPENCQERMEP CON
N
Z
O
a
ci
LL
U
W
IL
U)
J
U_
Fm
F-
L)
W
J
W
No.
04C3982
STATE OF
1
ai
a
o
UO
O
UU
JLL
to
Wm
E
o
LU
w
"I<
Q3 €z
s -<
zQ Z�oeZ oaa
Q1 rWn1rOM
ogu
ova 01
�y
DATE: 05/30/19