VENTURI VALVE & CONTROLLER
(S—NH #113)
vv_1
TX
GENERATORPROTECTED
OVAC
18 AWG/2 CONDUCTOR/SHIELDED 16 AWG/2 CONDUCTOR
SIGNAL WIRING 24 VAC POWER WIRING
RPM 1 ' 10 RPM 2
ROOM PRESSURE MONITOR ROOM PRESSURE MONITOR
(S—NH #113) (ANTE $112)
S-NH #113 PRESSURE MONITOR RPM1 & RPM2
INSTALLATION & WIRING DETAIL
VENTURI VALVE & CONTROLLER
(ANTE #112)
TVTM
Tx
GENERATOR PROTECTED
12WAC
r
18 AWG/2 CONDUCTOR/SHIELDED 16 AWG/2 CONDUCTOR
SIGNAL WIRING 24 VAC POWER WIRING
FET00kiNaf !-
ROOM PRESSURE MONITOR ROOM PRESSURE MOU.TOR
(ANTE #112) (WORK AREA #109)
ANTE #112 PRESSURE MONITOR RPM1 & RPM2
INSTALLATION & WIRING DETAIL
GENERAL NOTES
NEW DUCTWORK SHALL BE INSTALLED USING THE FOLLOWING MATERIALS:
—RIGID: GALVANIZED SHEET METAL, IN ACCORDANCE WITH ASHRAE AND SMACNA
REQUIREMENTS FOR LOW PRESSURE DUCTWORK. (1" WC)
—WRAP: 1.5" THICK, 3/4 LB. DENSITY FIBERGLASS INSULATION WITH VAPOR
BARRIER JACKET.
—FLEXIBLE: WIREMOLD TYPE WON OR EQUAL FLEXIBLE CLASS 1 AIR DUCT, THICK,
3/4 LB. DENSITY FIBERGLASS INSULATION AND FIRE RETARDANT REINFORCED
METALIZED POLYESTER FILM LAMINATED ON SHEET WIRE REINFORCING, WITH 1.5"
VAPOR BARRIER (HI —VINYL) AND SHALL MEET NFPA 90A AND UL STANDARD 181.
2. ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH A
MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASES
WHEN SUBJECT TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIED FOR
FIRE STOPS ASTM—E814.
3. DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
4. ALL DUCTWORK THROUGHOUT SPACE (SUPPLY & RETURN) IS TO BE INSULATED
WITH WRAP MATERIAL DESCRIBED ABOVE.
KEYNOTES
1. FURNISH AND INSTALL NEW T-STAT IN LOCATION SHOWN. LIGHTSTAT, MODEL
#TME-POI.
2, NEW CONDENSING UNITS ARE OUTSIDE BUILDING ON GRADE NORTH IN PLAN PAST
ADJACENT TENANT SPACE.
NEW MECHANICAL EQUIPMENT LOCATED APPROXIMATELY IN SAME LOCATION AS
3' EXISTING EQUIPMENT. (UP ABOVE THE JOIST SPACE). ROUTE NEW 3/4"
CONDENSATE DRAIN LINE FROM DRAIN PAN SIMILAR TO EXISTING LOCATION.
RECONNECT/EXTEND EXISTING VENT, OUTDOOR AIR DUCTWORK, AND GAS
CONNECTIONS OF APPROPRIATE SIZES TO NEW EQUIPMENT.
4. FURNISH AND INSTALL NEW 8"0 EXHAUST DUCT UP THROUGH ROOF TO ROOF
MOUNTED EXHAUST FAN (EF-1) WITH BACKDRAFT DAMPER. ENSURE THAT EXTERIOR
EXHAUST IS A MINIMUM 10'-0" AWAY FROM ANY AND ALL OUTDOOR AIR INTAKES.
TO BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR INSIDE MODULAR
SPACE. COORDINATE INSTALLATION WITH BIOLOGICS MODULAR.
5, FURNISH AND INSTALL NEW 10"0 EXHAUST DUCT UP THROUGH ROOF TO ROOF
MOUNTED EXHAUST FAN (EF-2) WITH BACKDRAFT DAMPER AND BIRD SCREEN.
ENSURE THAT EXTERIOR EXHAUST IS A MINIMUM 10'-0" AWAY FROM ANY AND ALL
OUTDOOR AIR INTAKES.
6, FURNISH AND INSTALL NEW 4"0 EXHAUST DUCT UP THROUGH ROOF WITH ROOF
CAP AND BIRD SCREEN.
7, CU-1 WILL REQUIRE AN ADAPTER FITTING TO BE FIELD INSTALLED BY CONTRACTOR
FOR THE REQUIRED 1 1/8" LINE SET.
8, INDICATES THAT DUCTWORK (BOTH SUPPLY ® AND RETURN 1a ) TO DROP
THROUGH ATTIC SPACE INTO SPACE ABOVE FINISHED CEILING AND CONTINUE AS
SHOWN.
9, COORDINATE WITH WALL MANUFACTURER TO ENSURE LOW WALL RETURNS AS
SHOWN. WALL MANUFACTURER TO PROVIDE CUTOUT/OPENING IN WALL SYSTEM FOR
LOW WALL RETURNS.
10. COMPOUNDING AREA WORK BY OTHERS. INFORMATION FOR
SYSTEMS/EQUIPMENT/MATERIAL SHOWN FOR INFORMATION ONLY. ALL WORK
INDICATED IN THE AREA SHALL BE (UON) FURNISHED AND INSTALLED BY
BIOLOGICS MODULAR. CONTACT JULIAN KARRAS, VP OF OPERATIONS, AT
(317-456-9191) FOR PRICING/PROVISIONS OF THEIR EQUIPMENT.
11. ALL DUCTWORK WORK TO RUN IN ATTIC SPACE ABOVE COMPOUNDING AREA WITH
THE EXCEPTION OF WHERE DIFFUSERS, LOW WALL RETURNS, AND EXHAUST DUCT
ARE SHOWN. AT DIFFUSERS, LOW WALL RETURNS, AND EXHAUST DUCT DUCTWORK
TO DROP STRAIGHT DOWN THROUGH ATTIC SPACE AND CEILING (WHEN NECESSARY)
TO RESPECTED CONNECTION.
12. FOR CONTINUATION OF DUCTWORK IN COMPOUNDING AREA (SUPPLY AND RETURN)
REFER TO ENLARGED PLAN ON SHEET M1.0.
MODULAR COMPOUNDING MECHANICAL WORK (SUPPLY/RETURN)
SCALE: 1/2" = 1'.0"
7S
31
Ia
.1 D. ARCHITECTS PC
a]84 TECHNOLOGY DRIVE
FISHERS, IN 4W38
TEL 517568.2822
FAX S17,MIT S27
vrnmderchimcre.am
Sr= NC=R
�NGINEE2ING_
1533 EAST NORTHFIELD DRIVE
SUITE 400
DW W SPENCCERMEP CON
�Iw
a14
NC03982
STATE OF
a�
ate+
O
J
Q 0
f♦
V
LLQ
V
f
Y
LL
0
J
U_
Z
a
2
tU
w
Z
a
J
IL
w
0
0
J
LL
DATE: 05/30/19