HomeMy WebLinkAbout190523 PURE Pharmacy Permit 24-P60SECTION 15B: PLUMBING CONTINUED:
15B 2-3 PIPING JOINTS
COPPER TUBING: JOINTS IN HARD TEMPER TUBING SHALL BE SOLDERED JOINTS USING LEAD—
FREE 95/5 SOLDER EXCEPT WHERE TUBING IS INSTALLED BELOW GRADE OR BELOW THE BASE
SLAB, IN WHICH CASE JOINTS SHALL BE SOLDERED WITH SILVER SOLDER (SILFOS). JOINTS IN
SOFT TEMPER COPPER TUBING SHALL BE OF THE FLARED TYPE INSTALLED IN COMPLIANCE WITH
THE FITTING MANUFACTURER'S RECOMMENDATIONS.
THREADED STEEL PIPE: THREADED JOINTS SHALL BE FULL AND CLEAN, CUT WITH NOT MORE
THAN THREE (3) THREADS EXPOSED BEYOND THE FITTINGS. MAKE JOINTS TIGHT WITH GRAPHITE
BASE PIPE JOINT COMPOUND AND PAINT EXPOSED THREADS OF FERROUS PIPE WITH ACID —
RESISTING PAINT AFTER PIPING HAS BEEN TESTED AND PROVEN TIGHT. NO CAULKING, LAMP —
WICK OR OTHER MATERIAL WILL BE PERMITTED FOR CORRECTION OF DEFECTIVE JOINTS.
WELDED STEEL PIPE. WELDED JOINTS SHALL BE OF THE BUTT WELDED SINGLE 'VEE" TYPE.
BEVEL PIPE AT A 45 DEGREE ANGLE TO WITHIN 1/16" OF THE INSIDE WALL, AND BUILD UP THE
WELD TO ONE FOURTH GREATER DEPTH THAN THE PIPE WALL THICKNESS. WELDING SHALL BE
EITHER ELECTRIC OR OXY—ACETYLENE, PERFORMED IN CONFORMANCE WITH THE ASME CODE
FOR PRESSURE PIPE WELDING, AND ONLY BY EXPERIENCED CERTIFIED WELDERS.
CAST IRON PIPE BELOW GRADE: JOINTS IN BELL AND SPIGOT CAST IRON WASTE AND VENT PIPE
SHALL BE NEOPRENE COMPRESSION GASKETS, TYSEAL OR EQUAL.
CAST IRON PIPE ABOVE GRADE: JOINTS IN HUBLESS PIPE SHALL BE STANDARD CISPI 310-85
COUPLING BY ANACO HUSKY OR APPROVED EQUAL. JOINTS IN STORM PIPING 6" AND LARGER
SHALL BE HEAVY DUTY COUPLINGS MEETING ASTM C564 AND FM 1680, ANACO HUSKY #SD-4000
OR CLAMP —ALL "HI TORQUE" 80 IN. LB.
PVC PIPE: CLEAN JOINTS FREE FROM DEBRIS AND MOISTURE. APPLY PVC PRIMER MEETING
ASTM F656 TO EACH JOINT. APPLY SOLVENT CEMENT MEETING ASTM D2564 AND MAKE JOINT
WHILE WET AND IN ACCORDANCE WITH ASTM D2855.
PIPE ADAPTERS: MAKE CONNECTION OF NEW WASTE PIPE TO NEW OR EXISTING DISSIMILAR
WASTE PIPE USING ADAPTER COUPLINGS. PROVIDE FERNCO, PROFLEX 3000 SERIES OR MISSION
FLEXSFAL MR56 SERIES WITH NEOPRENE ADAPTER GASKET WITH STAINLESS STEEL SHIELD AND
HOSE CLAMPS FOR CONNECTING DISSIMILAR PIPES ABOVE GRADE. PROVIDE FERNCO, 1056
SERIES OR MISSION SEWER COUPLINGS WITH NEOPRENE ADAPTER GASKET AND HOSE CLAMPS
FOR CONNECTING DISSIMILAR PIPES BELOW GRADE AND COAT STAINLESS STEEL BANDS WITH
MASTIC.
15B 2-4 PIPING INSTALLATION
GENERAL: CLEAN PIPE THOROUGHLY PRIOR TO INSTALLATION. REAM ENDS OF PIPE TO
REMOVE BURRS. CUT PIPE ACCURATELY TO MEASUREMENTS TAKEN ON THE JOB. INSTALL WITH
ADEQUATE CLEARANCE FOR INSTALLATION OF COVERINGS WHERE REQUIRED. PIPE SHALL NOT
BE SPRUNG OR BENT. NEATLY ALIGN PIPE, CONNECT IT SECURELY, AND SUPPORT IT FROM THE
BUILDING STRUCTURE WITH HANGERS AS SPECIFIED BELOW. PROVIDE CHROME —PLATED
ESCUTCHEONS ON PIPES PASSING THROUGH CEILINGS, FLOORS OR WALLS OF FINISHED
SPACES. RUN PIPES FREELY THROUGH FLOOR AND WALL PENETRATIONS USING PIPE SLEEVES.
DO NOT GROUT IN PLACE UNLESS REQUIRED FOR STRUCTURAL FIRE INTEGRITY. INSTALL PIPE
CONCEALED IN FINISHED SPACES WHEREVER POSSIBLE. USE A DIELECTRIC UNION WHERE
FERROUS AND COPPER PIPE CONNECT. DIELECTRIC UNION SHALL HAVE A ZINC —PLATED STEEL
BODY, A THREADED NYLON INSERT, AND INSULATING PRESSURE GASKET. NO FERROUS METAL —
TO —COPPER CONNECTION MADE WITHOUT INSULATING UNIONS WILL BE ALLOWED.
HANGER & SUPPORTS: PIPE HANGERS SHALL BE AS DESCRIBED IN THE SPECIFICATIONS BY B—
LINE OR EQUAL BY ANVIL, MICHIGAN, TRUSCON, OR UNISTRUT. CONNECT HANGERS TO THE
STRUCTURE WITH SIDE BEAM CONNECTORS AND ALL THREAD HANGER RODS. PROVIDE
ENGINEERED SUPPORT STRUTS BETWEEN JOISTS AND OTHER STRUCTURAL MEMBERS AS
REQUIRED TO PROVIDE A RIGID HANGING INSTALLATION. DO NOT HANG PIPES FROM OTHER
PIPES, CONDUIT OR DUCTWORK. PROVIDE HANGER RODS AND SPACE HANGERS AT INTERVALS
AS SPECIFIED IN "HANGER SPACING PROVIDE SUPPORT WITHIN V OF EACH ELBOW AND TEE.
PROVIDE SUPPORTS WITHIN 1' OF EACH EQUIPMENT CONNECTION. INSTALL HANGER TYPES OR
SUPPORTS FOR VARIOUS PIPING AS FOLLOWS:
COPPER TUBE: ADJUSTABLE BAND HANGERS FOR BARE COPPER TUBE 3" AND SMALLER SHALL
BE B—LINE #B3170 CT COPPER PLATED ADJUSTABLE BAND SWIVEL RING TYPE. ADJUSTABLE
BAND HANGERS FOR INSULATED COPPER TUBE AND 3" SMALLER SHALL BE B—LINE #B3170 NF
ADJUSTABLE BAND SWIVEL RING TYPE. CLEVIS HANGERS FOR INSULATED COPPER TUBE 4" AND
LARGER SHALL BE B—LINE #B3100 GALVANIZED STEEL CLEVIS TYPE. SUPPORT EXPOSED COPPER
TUBE 2" AND SMALLER TO WALLS OR IN CHASES WITH B—LINE #B3198RCT COPPER COATED
EXTENSION SPLIT RING PIPE CLAMPS, 3/8" THREADED ROD AND B—LINE #B3199CT CEILING
FLANGES. SUPPORT COPPER TUBE IN CHASES AND WALLS AT PLUMBING FIXTURES WITH
PLASTIC OR COPPER BRACKETS SECURED TO STRUCTURE AND U—BOLTS SIZED TO BARE ON THE
PIPE. RISER CLAMPS TO SUPPORT VERTICAL COPPER TUBE SHALL BE B—LINE #B3373CT COPPER
COATED STEEL, CUT INSULATION, SEAL VAPOR BARRIER, AND ATTACH TO BARE TUBE.
STEEL PIPE: ADJUSTABLE BAND HANGERS FOR 2" AND SMALLER SHALL BE B—LINE #B3170 NF
ADJUSTABLE BAND SWIVEL RING TYPE. CLEVIS HANGERS FOR 2-1/2" AND LARGER SHALL BE B—
LINE #B3100 GALVANIZED STEEL CLEVIS TYPE. RISER CLAMPS TO SUPPORT VERTICAL PIPE
SHALL BE B—LINE #B3373 GALVANIZED STEEL.
CAST IRON PIPE: ADJUSTABLE BAND HANGERS FOR 2" AND SMALLER. CLEVIS HANGERS FOR 3"
AND LARGER SHALL BE B—LINE #B3100 GALVANIZED STEEL CLEVIS TYPE. RISER CLAMPS TO
SUPPORT VERTICAL PIPE SHALL BE B—LINE #B3373 GALVANIZED STEEL.
PVC PIPE: ADJUSTABLE BAND HANGERS FOR 3" AND SMALLER. CLEVIS HANGERS FOR 4" AND
IARGER SHALL BE B—LINE #B3100 GALVANIZED STEEL CLEVIS TYPE. RISER CLAMPS TO SUPPORT
VERTICAL PIPE SHALL BE B—LINE #133373 GALVANIZED STEEL.
INSULATION PROTECTION SHIELDS: B—LINE #83151 OF 18 GAUGE GALVANIZED SHEET METAL.
SHIELD SHALL COVER HALF OF THE CIRCUMFERENCE OF THE PIPE AND SHALL BE OF LENGTH
INDICATED BY MANUFACTURER FOR PIPE SIZE AND THICKNESS OF INSULATION.
HANGER SPACING, ROD SIZES & CONNECTORS: CONNECT RODS TO STEEL BEAMS OR JOISTS
WITH B—LINE #B3031 OR #B3033BEAM CLAMPS AS REQUIRED. CONNECT RODS TO CONCRETE
WITH B—LINE #3014 MALLEABLE IRON SINGLE TYPE INSERTS WITH MALLEABLE IRON NUT.
CONNECT RODS IN WOOD CONSTRUCTION WITH B—LINE #B3058 SIDE BEAM CONNECTORS. HANG
AND SUPPORT PIPING WITH SPACING AND ROD SIZES AS FOLLOWS:
COPPER TUBE: 1-1/2" AND SMALLER — EVERY 6' WITH 3/8-HANGER RODS; 2" — EVERY 10' WITH
1/2"HANGER RODS; 2-1/2" AND 3" — EVERY 10' WITH 1/2" HANGER RODS, 4" — EVERY 10' WITH 5/8"
HANGER RODS. SUPPORT VERTICAL COPPER TUBE EVERY 10'.
STEEL PIPE: 1" AND SMALLER — EVERY 8' WITH 3/8" HANGER RODS; 1-1/4" TO 2" — EVERY 10' WITH
3/8" HANGER RODS; 2-1/2" AND 3" — EVERY 10' WITH 1/2" HANGER RODS, 4' — EVERY 10' WITH 5/8"
HANGER RODS. SUPPORT VERTICAL STEEL PIPE EVERY 10'.
CAST IRON PIPE: EVERY 10' AND WITHIN 1' OF EACH JOINT. 2" AND SMALLER WITH 3/8" HANGER
RODS; 3" WITH 1/2' HANGER RODS; 4" WITH 5/8' HANGER RODS; 6" WITH 3/4' HANGER RODS; 8"
AND LARGER WITH 7/8" HANGER RODS. SUPPORT VERTICAL CAST IRON PIPE EVERY 15'.
PVC PIPE: SUPPORT ALL PIPES SIZES EVERY 4'. 1-1/2" AND SMALLER WITH 3/8" HANGER RODS; 2"
WITH 1/2"HANGER RODS; 2-1/2" AND 3" WITH 112" HANGER RODS, 4" AND LARGER WITH 5/8"
HANGER RODS. SUPPORT VERTICAL PVC PIPE EVERY 4'.
SUPPORTS ON ROOF: SUPPORT PIPING ON ROOF WITH 4" X 4" X 12" LONG CCA ROT -PROOF
WOOD BLOCKS. SET WOOD BLOCKS ON 18" X 18" X 3/16" THICK ROOF WALKWAY MATERIAL.
CONNECT PIPE TO WOOD BLOCKS WITH GALVANIZED STEEL PIPE CLAMP AND 1/4" X 1-1/2" LONG
CADMIUM PLATED LAG SCREWS. STACK BLOCKS AND NAIL THEM TOGETHER AS REQUIRED
AND SUPPORT PIPE AS REQUIRED TO CHANGE PIPE ELEVATION. SUPPORT PIPE WITH SPACING
AS DESCRIBED ABOVE AT A MINIMUM 7" ABOVE THE ROOF. SET BLOCKS ON 18" X 18" X 3/16"
THICK ROOF WALKWAY MATERIAL COMPATIBLE WITH ACTUAL ROOF MATERIAL.
BELOW GROUND INSTALLATION FOR WASTE: INSTALL WASTE PIPING TO A UNIFORM SLOPE OF
NOT LESS THAN 1/8" PER FOOT FOR PIPING 4" OR LARGER, AND NOT LESS THAN 1/4" PER FOOT
FOR PIPING 3" OR SMALLER. LAY PIPE AT UNIFORM SLOPE, FREE FROM SAGS, WITH HUB END
UPSTREAM. MAKE CHANGES IN DIRECTION FROM HORIZONTAL TO VERTICAL, AT FIXTURE
BRANCHES AND OTHER BRANCH CONNECTIONS WITH SANITARY "TEES" OR SHORT SWEEP
"ELLS". MAKE CHANGES IN DIRECTION FROM VERTICAL TO HORIZONTAL OR HORIZONTAL TO
HORIZONTAL WITH LONG RADIUS FITTINGS, LONG SWEEPING "ELLS", COMBINATION "Y AND 1/8
BEND" FITTINGS, OR 45 DEGREE "ELLS' (1/8 BEND FITTINGS), 1/6 BEND OR 1/16 BEND AND "-
FITTINGS. INSTALL PIPE WITH THE BARREL OF THE PIPE ON FIRM, SOLID EARTH FOR ITS ENTIRE
LENGTH, AND EXCAVATE HOLES FOR THE PIPE BELLS. LAY PIPE IN A STRAIGHT LINE AND
INSTALL WITH UNIFORM GRADE TO LINE WITH BATTEN BOARDS SET NOT MORE THAN 24'-0"
APART. CLOSE OPEN ENDS OF PIPE WITH A STOPPER WHEN PIPE LAYING IS NOT IN PROGRESS.
CENTER SPIGOTS ACCURATELY IN BELLS FOR UNIFORM CAULKING. PROVIDE A SMOOTH AND
UNIFORM INVERT IN THE SYSTEM. DRILLING OR TAPPING OF SOIL AND WASTE LINES, AND
SADDLE HUBS AND BANDS ARE NOT PERMITTED. LOCATE AND INSTALL SOIL AND WASTE LINES
AS INDICATED ON THE DRAWINGS. DETERMINE EXACT LOCATIONS IN SUCH A MANNER AS TO
TION OF ANYPIPE, VERIFY
RELEASED FOR CONSTRUCTION L�EWER, SERVICEUAIN LINE OR ILDING REXISTING TENANT
Subject to compliance with all regulations IF THE INSTALLATION WILL NOT TIE INTO THE
of Sete and local Codes NTAINING PROPER FALL, NOTIFY ARCHITECT SO
,Y BE DETERMINED.
City off Cannel
�Nq�\D.kMWA�
PLUMBING VENT: CONNECT PLUMBING VENT PIPES TO FIXTURE DRAIN PIPES AS INDICATED ON
THE DRAWINGS OR AS REQUIRED BY THE INSTALLATION PRACTICES ADOPTED AND ENFORCED
BY LOCAL CODES OFFICIAL, AND EXTEND VENT PIPES FULL SIZE THROUGH THE ROOF LINE.
GRADE PIPE TO A UNIFORM SLOPE SO AS TO DRAIN BACK BY GRAVITY TO THE DRAINAGE PIPING
SYSTEM. VENTS PASSING THROUGH THE ROOF SHALL BE MINIMUM 3" SIZE EXCEPT IN TROPICAL
CLIMATES, PER LOCAL CODES. TURN FLASHING DOWN INTO STACKS AT LEAST 2", AND EXTEND
FLASHING 24" IN ALL DIRECTIONS FROM THE PIPE AT THE ROOF LINE. APPLY WHITE LEAD PIPE
DOPE ON MALE STEEL PIPE THREADS. VENT LINES SHALL BE AIR AND WATER TIGHT. VENT
FLOOR DRAINS INDIVIDUALLY OR CONNECT THEM TO A HORIZONTALLY VENTED LINE AS SHOWN
ON THE DRAWINGS.
DOMESTIC WATER: ARRANGE COLD, HOT, AND HOT WATER RECIRCULATION PIPING TO DRAIN AT
THE LOWEST POINT IN EACH SYSTEM. INSTALL AT LEAST ONE PIPE UNION ADJACENT TO ALL
SHUTOFF VALVES, AT CONNECTION POINTS OF EACH PIECE OF EQUIPMENT, AND ELSEWHERE IN
THE SYSTEM WHERE REQUIRED TO ALLOW PROPER MAINTENANCE. PROVIDE UNIONS OF THE
GROUND JOINT TYPE. MAKE ALLOWANCE FOR EXPANSION AND CONTRACTION WHERE
REQUIRED BY THE INSTALLATION. WHERE WATER PIPING OCCURS IN EXTERIOR WALLS, HOLD
PIPE AS CLOSE AS POSSIBLE TO THE INTERIOR FACE OF WALL AND INSTALL INSULATION BAIT
OR OTHER INSULATION (MINIMUM R8) BETWEEN PIPING AND THE EXTERIOR WALL FACE
NATURAL GAS: PITCH NATURAL GAS PIPING,
AND PROVIDE ACCESSIBLE DIRT LEGS AT THE LOW
POINTS. TAKE BRANCH PIPES
OFF THE
TOP OR SIDES OF MAIN PIPES,
TO PREVENT
ACCUMULATION OF WATER IN THE
BRANCHES.
INSTALL GAS PIPING VALVES AND
UNIONS ONLY
IN ACCESSIBLE LOCATIONS.
DO NOT
INSTALL GAS PIPE BELOW THE
BASE SLAB.
15B 2-5 PIPING SANITIZATION
SANITIZE THE ENTIRE DOMESTIC WATER PIPING SYSTEM (COLD, HOT, AND HOT WATER RETURN)
WITH A SOLUTION CONTAINING NOT LESS THAN 50 RPM AVAILABLE CHLORINE. KEEP SOLUTION
IN THE SYSTEM FOR A MINIMUM OF 24 HOURS, WITH EACH VALVE BEING OPERATED SEVERAL
TIMES DURING THE PERIOD. AFTER COMPLETION, FLUSH SYSTEM WITH CITY WATER UNTIL
CHLORINE RESIDUAL IS LOWERED TO INCOMING CITY WATER LEVEL.
15B 2-6 PIPE AND VALVE MARKERS
PROVIDE MANUFACTURER'S STANDARD PRE—PRINTED, SEMI —RIGID SNAP —ON OR PERMANENT
ADHESIVE, PRESSURE —SENSITIVE VINYL PIPE MARKERS. PIPE MARKERS SHALL BE COLOR —
CODED COMPLYING WITH ANSI A13.1.
INSTALL PIPE MARKERS ON EACH PLUMBING PIPING SYSTEM AND INCLUDE ARROWS TO SHOW
NORMAL DIRECTION OF FLOW.
LOCATE PIPE MARKERS AND COLOR BANDS WHEREVER PIPING IS EXPOSED TO VIEW IN
OCCUPIED SPACES, MACHINE ROOMS, ACCESSIBLE MAINTENANCE SPACES (SHAFTS, TUNNELS,
PLENUMS) AND EXTERIOR NON —CONCEALED LOCATIONS.
PROVIDE PLASTIC LAMINATE OR BRASS VALVE TAG ON EVERY VALVE, COCK AND CONTROL
DEVICE IN EACH PLUMBING PIPING SYSTEM; EXCLUDE CHECK VALVES, VALVES WITHIN FACTORY —
FABRICATED EQUIPMENT UNITS, PLUMBING FIXTURE FAUCETS, CONVENIENCE AND LAWN —
WATERING HOSE PIPES, AND SHUT—OFF VALVES AT PLUMBING FIXTURES AND SIMILAR ROUGH —IN
CONNECTIONS OF END —USE FIXTURES AND UNITS.
15B 2-7 HEAT TRACE
PROVIDE HEAT TRACE SYSTEM AS INDICATED ON THE DRAWINGS MANUFACTURED BY RAYCHEM,
CHROMALOX, NEXTRON, NELSON OR APPROVED EQUAL.
HEAT TRACE CABLES: PAIR OF PARALLEL NO. 16 AWG TINNED —COPPER BUS WIRES EMBEDDED IN
CROSS LINKED CONDUCTOR POLYMER CORE, WHICH VARIES POWER OUTPUT IN RESPONSE TO
TEMPERATURE ALONG ITS LENGTH; LINE VOLTAGE AS INDICATED ON THE DRAWINGS. PROVIDE
OUTER JACKET MATERIAL AS INDICATED ON THE DRAWINGS. CABLE SHALL BE CAPABLE OF
CROSS OVER ITSELF WITHOUT OVERHEATING. CABLE SHALL CAPABLE OF A HEAT OUTPUT OF
90% OF RATING OVER A TEMPERATURE RANGE OF 40'F TO 150'F PIPE TEMPERATURE. PROVIDE
FIELD —APPLIED POWER CONNECTION KITS, END SEAL KITS AND ANY TEE KITS AS REQUIRED.
HEAT TRACE CONTROL PANEL: FOR "ON —OFF" CONTROL OF HEAT TAPE CIRCUIT WITH NEMA 4X
FIBERGLASS REINFORCED PLASTIC ENCLOSURE FOR OUTDOOR INSTALLATION WITH HINGED
ACCESS DOOR WITH WINDOW AND FURNISHED WITH THE FOLLOWING: MICROPROCESSOR
BASED CONTROLLER WITH LED DISPLAY WITH KEYPAD INTERFACE AND NON—VOLATILE MEMORY.
GROUND FAULT CIRCUIT PROTECTION CAPABLE OF CHECKING HEATING CABLE CIRCUIT FAULTS.
LED INDICATOR LIGHTS: CURRENT MODE, HEATER ON, ALARM CONDITIONS AND RECEIVE /
TRANSMIT DATA. ALARM CONDITIONS: RTD FAILURE, HIGH/LOW TEMPERATURE, HIGH/LOW
CURRENT, HI/LOW RESISTANCE AND HIGH/LOW VOLTAGE, GROUND FAULT ALARM, TRIP, LOSS OF
PROGRAMMED VALUES AND ELECTROMECHANICAL RELAY FAILURE. ALARM CONTACTS: ONE
SINGLE POLE SINGLE THROW RATED AT 0.75 AMP 120 TO 277 VOLT RELAY AND ONE DRY PILOT
DUTY ONLY RELAY RATED AT 48 VAC / DC 50 MILIAMPS, 10VA MAXIMUM RESISTIVE SWITCHING.
POWER STRIP FOR CONNECTING 277 VOLT SINGLE PHASE AT 30 AMPS MAXIMUM. TEMPERATURE
CONTROL SENSORS: TOTAL OF TWO THREE WIRE 100 OHM RTD'S WITH 10 FOOT LONG
STAINLESS STEEL SHEATH, AMBIENT TEMPERATURE RANGE OF —76'F TO 10580F WITH AN
ACCURACY OF t3'F AND A REPEATABILITY OF t30F.
THERMOSTATS: SHALL BE AS SCHEDULED ON THE DRAWINGS AND OF THE SAME
MANUFACTURER AS THE HEAT TRACE CABLE.
15B 3-3 VALVES, STRAINERS, HOSE BIBBS, AND UNIONS
PLUMBING SYSTEM VALVES SHALL BE CRANE COMPANY OR NIEGO OF MODELS HEREIN
SPECIFIED, OR APPROVED EQUAL BY HAMMOND, WALWORTH, STOCKHAM OR MUELLER VALVES.
VALVES SHALL BE OF THE BEST QUALITY, DESIGNED FOR 125 PSI STEAM WORKING PRESSURE.
INSTALL VALVES ON THE HOT AND COLD WATER LINES AT THE WATER HEATER CONNECTIONS
AND OTHER ITEMS OF EQUIPMENT, AT BRANCHES FROM MAINS SERVING GROUPS OF FIXTURES,
AND AT OTHER PLACES INDICATED OR REQUIRED BY THE INSTALLATION TO ALLOW EASE OF
FUTURE MAINTENANCE.
GATE VALVES: CLASS 125, SIZE 2-1/2" AND SMALLER SHALL BE CRANE #1701 OR NIBCO 1113,
NON —RISING STEM, SCREWED BRASS BODY AND PARTS, WITH WEDGE DISC. GATE VALVES 3"
AND LARGER SHALL BE CRANE #465-1/2 OR NIBCO #617-0, O.S. & Y., IRON BODY FLANGED WEDGE
GATE WITH BRASS SEATS AND STEM.
BALL VALVES (MAY
BE USED
IN LIEU OF
GATE VALVES UP
TO 2P:
2" AND SMALLER, NIBCO #T580;
TWO PIECE BRONZE BODY,
WITH SCREWED ENDS,
CHROME
PLATED BRONZE BALL WITH
CONVENTIONAL
PORT,
400 PSI,
BLOW—OUT
PROOF
STEM.
GLOBE VALVES: GLOBE VALVES SHALL BE CLASS 125. GLOBE VALVES 2-1/2" AND SMALLER
SHALL BE CRANE #1310 OR NISCO #T-211, SCREWED BRASS BODY AND BRASS DISC. GLOBE
VALVES 3" AND LARGER SHALL BE CRANE #351 IRON BODY FLANGED VALVE WITH BRASS TRIM.
CHECK VALVES: CHECK VALVES SHALL BE CLASS 125. CHECK VALVES FOR INSTALLATION IN
HORIZONTAL PIPE RUNS SHALL BE OF THE "SWING DISC" DESIGN. HORIZONTAL CHECK VALVES
2-1/2" AND SMALLER SHALL BE CRANE #137 OR NIBCO #T-413 WITH SCREWED BRONZE BODY AND
BRONZE DISC. HORIZONTAL CHECK VALVES 3" AND LARGER SHALL BE CRANE #373 OR NIBCO F-
918 IRON BODY FLANGED VALVE WITH BRASS TRIM. CHECK VALVES FOR INSTALLATION IN
VERTICAL PIPE RUNS SHALL BE OF THE 'VERTICAL LIFT" DESIGN. VERTICAL CHECK VALVES 2-1/2"
AND SMALLER SHALL BE CRANE #29 OR NIEGO #T-480 WITH SCREWED BRONZE BODY AND
BRONZE DISC. VERTICAL CHECK VALVES 3" AND LARGER SHALL BE CENTER GUIDED.
GAS COCKS: GAS COCKS 2-1/2" AND SMALLER SHALL BE HOMESTEAD #611, SCREWED IRON
BODY WITH BRASS TRIM AND FLAT HEAD. GAS COCKS 3" AND LARGER SHALL BE HOMESTEAD
#612 FLANGED SEMI -STEEL BODY WITH IRON TRIM AND SQUARE HEAD. APPROVED EQUAL ARE
MCDONALD, ROCKWELL- NORDSTROM OR DEZURIK.
THERMOSTATIC MIXING VALVES: THERMOSTATIC MIXING VALVES SHALL BE POWERS AS
DESCRIBED ON THE DRAWINGS OR EQUAL BRADLEY, LEONARD, LAWLER, SYMMONS OR WATTS
MEETING ASSE 1016 WITH BRASS BODY, NON —CORROSIVE INTERNAL PARTS, TAMPER RESISTANT
TEMPERATURE ADJUSTMENT, UNION INLETS AND CHECK STOPS WITH STRAINERS. SET
TEMPERATURE AT 100OF FOR HAND WASHING.
EMERGENCY MIXING VALVES: EMERGENCY MIXING VALVES SHALL BE POWERS AS DESCRIBED
ON THE DRAWINGS OR EQUAL BY BRADLEY, LEONARD, LAWLER, SYMMONS OR HAWS MEETING
ASSE 1071 COMPLETE WITH CHROME PLATED BRONZE BODY CONSTRUCTION, FULL FLOW COLD
WATER BY—PASS, NON —CORROSIVE INTERNAL PARTS, TAMPER RESISTANT TEMPERATURE
ADJUSTMENT, DIAL THERMOMETER, UNION INLETS WITH STRAINERS, CHECKS, AND STOPS.
GAS LINE PRESSURE REGULATORS: GAS LINE PRESSURE REGULATORS SHALL BE BY
EQUIMETER, FISHER, MAXITROL OR AMERICAN METER COMPANY WITH CAPACITIES AS
SCHEDULED ON THE DRAWINGS. REGULATORS SHALL BE SINGLE STAGE, STEEL JACKETED,
CORROSION —RESISTANT TYPE WITH INTERSTITIAL RELIEF VALVE WITH ATMOSPHERIC VENT,
ELEVATION COMPENSATOR; WITH THREADED ENDS, FOR INLET AND OUTLET.
SANITARY POST HYDRANTS: HOEPTNER "FREEZE —FLOW EXECUTIVE" OR EQUAL BY WOODFORD
MEETING ASSE #1057.
UNIONS: FERROUS UNIONS SHALL BE CRANE OR EQUAL, COMBINATION IRON AND BRASS,
GROUND JOINT WITH SCREWED ENDS. COPPER UNIONS SHALL BE STREAMLINE OR EQUAL, CAST
BRONZE SWEAT TYPE WITH GROUND JOINT. FERROUS TO COPPER UNIONS SHALL BE
UNIVERSAL CONTROLS OR EQUAL, DIELECTRIC TYPE WITH THREADED NYLON INSERT.
FLOW CONTROL VALVES: FOR INSTALLATION IN HOT WATER RECIRCULATION LINES, SHALL BE
BELL & GOSSETT #RF-1/2S "CIRCUIT SETTER" OR EQUAL BY ARMSTRONG OR NIBCO WITH BRONZE
BODY, BRASS BALL, TEE SEAT RINGS, CALIBRATED ORIFICE, MEMORY STOP, READOUT VALVES
WITH INTERNAL CHECK VALVES, DRAIN PORT AND SWEAT CONNECTIONS. PROVIDE BALL VALVE,
STRAINER AND CHECK VALVE UPSTREAM AND UNION AND BALL VALVE DOWNSTREAM OF EACH
FLOW CONTROL VALVE. SET THE FLOW CONTROL VALVES TO THE FLOWS AS INDICATED ON THE
DRAWINGS.
15B 3-4 GREASE TRAPS AND INTERCEPTORS
GREASE INTERCEPTORS SHALL BE PRECAST CONCRETE OF LOCAL MANUFACTURE SIMILAR TO
DETAIL ON THE DRAWINGS, CONFORMING TO REQUIREMENTS OF THE LOCAL SEWER DISTRICT
FOR CONFIGURATION AND CAPACITY. PROVIDE SAMPLING PORT AND VENT FOR GREASE
INTERCEPTOR AS SHOWN ON THE DRAWINGS.
fl7IItII.�rdGtl7 Z7>IK�Q9��IL•7_11[N�9dt`I llJ�� 7>f�PI�➢d[e17��>I�U7:iSgC/y4P�7
PREVENTER
PROVIDE A BACKFLOW PREVENTER (BFP) OF TYPE REQUIRED BY LOCAL CODE, AND A PRESSURE
REDUCING VALVE (PRV) IF REQUIRED BY EXCESSIVE WATER PRESSURE, ON THE DOMESTIC
WATER SERVICE IMMEDIATELY DOWNSTREAM FROM THE POINT OF WATER SERVICE ENTRY.
DOUBLE CHECK VALVE (DCV) SHALL BE AS SPECIFIED ON THE DRAWINGS, WATTS OR
EQUIVALENT BY FEBCO, CONBRACQ, OR WILKINS. 2" AND SMALLER SHALL BE BRONZE BODY
WITH STAINLESS STEEL TRIM, BRONZE BALL VALVE SHUT —OFFS ON INLET AND OUTLET, AND
BRONZE STRAINER WITH STAINLESS STEEL SCREEN AND CLEANOUT. FOR 2-1/2" AND LARGER
PROVIDE IRON BODY WITH FUSED EPDXY COATING, RESILIENT WEDGE AWWA C509 IRON GATE
VALVES ON INLET AND OUTLET, IRON STRAINER WITH FUSED EPDXY COATING, ALL FLANGE
CONNECTED. UNIT SHALL BE SUITABLE FOR 175 PSI WORKING PRESSURE.
REDUCE PRESSURE ZONE ASSEMBLY (RPZ) SHALL BE AS SPECIFIED ON THE DRAWINGS, WATTS
OR EQUIVALENT BY FEBCO, CONBRACO, OR WILKINS. FOR 2" AND SMALLER PROVIDE BRONZE
BODY WITH STAINLESS STEEL TRIM, BRONZE BALL VALVE SHUT —OFFS ON INLET AND OUTLET,
AND BRONZE STRAINER WITH STAINLESS STEEL SCREEN AND CLEANOUT. FOR 2-1/2" AND
LARGER PROVIDE IRON BODY WITH FUSED EPDXY COATING RESILIENT WEDGE AWWA C509 IRON
GATE VALVES ON INLET AND OUTLET, IRON STRAINER WITH FUSED EPDXY COATING, ALL FLANGE
CONNECTED, BRONZE TRIM, EPDM ELASTOMERS AND STAINLESS STEEL SPRING. UNIT SHALL BE
RATED FOR 175 PSI WORKING PRESSURE. PROVIDE AIR GAP FITTING ON INTERMEDIATE VENT
AND PIPE IT TO DISCHARGE OVER NEARBY FLOOR DRAIN.
PROVIDE A PRESSURE REDUCING VALVE (PRV) ONLY WHEN STATIC DOMESTIC WATER
PRESSURE DOWNSTREAM OF THE BFP EXCEEDS 80 PSI. PRV SHALL BE AS SPECIFIED ON THE
DRAWINGS, WATTS OR EQUIVALENT CASH —ACME OR WILKINS. FOR 2" AND SMALLER PROVIDE
WITH BRONZE BODY WITH STAINLESS STEEL TRIM, DIRECT ACTING, SPRING LOADED DIAPHRAGM
TYPE, SUITABLE FOR 300 PSI INLET PRESSURE. FOR 2-1/2" AND LARGER PROVIDE IRON BODY
WITH FUSED EPDXY COATING. OUTLET PRESSURE SHALL BE 50 PSI.
il7�IIa)EyXy1�i�CKyiXYK 71i.
THERMOMETERS SHALL BE AMERICAN 3" BI—METAL DIAL TYPE WITH SEPARABLE SOCKET, AND
SHALL BE INSTALLED WHERE INDICATED OR REQUIRED.
PRESSURE GAUGES SHALL BE ASHCROFT 3" DIAL TYPE WITH SHUT—OFF COCK, AND SHALL BE
INSTALLED WHERE INDICATED OR REQUIRED.
TRAP PRIMERS SHALL BE AS SPECIFIED ON THE DRAWINGS, PRECISION PLUMBING PRODUCTS
"PRIME RITE" OR EQUAL BY MIFAB OR SIOUX CHIEF WITH BRASS BODY AND INTEGRAL VACUUM
BREAKER. PROVIDE DISTRIBUTION BOX WHERE MORE THAN ONE TRAP IS INDICATED TO BE
PRIMED ON THE DRAWINGS. PROVIDE ACCESS PANEL WHERE REQUIRED.
ICE MAKER CONNECTION BOXES SHALL BE AS SPECIFIED ON THE DRAWINGS, GUY GRAY
#BIM875 OR APPROVED EQUAL, WITH 20 GAUGE STEEL BODY BODY, WALL FLANGE AND WATER
CONNECTION.
15B4 PLUMBING FIXTURES AND EQUIPMENT
15B 4-1 PLUMBING FIXTURES
FURNISH AND INSTALL COMMERCIAL GRADE PLUMBING FIXTURES, SEE THE DRAWINGS FOR
QUANTITIES AND DESCRIPTIONS.
FIXTURES SHOWN ON THE DRAWINGS OR SPECIFIED HEREIN SHALL BE FURNISHED AND
INSTALLED, SET FIRM AND TRUE, CONNECTED TO REQUIRED PIPING SERVICES, THOROUGHLY
CLEANED, LEFT CLEAN AND READY FOR USE. EXPOSED FITTINGS AND PIPING AT THE FIXTURES
SHALL BE CHROME —PLATED, AND WATER SUPPLY PIPING SHALL BE VALVED AT EACH FIXTURE.
15B 4-2 WATER HEATER
WATER HEATER PER PLUMBING FIXTURE SCHEDULE ON SHEET P1
Ia
,rc. ARCHITECTS , PC
as4 TECHNOLOGY DRIVE
FISHERS, IN 46039
EL : 517!iSS a22
FAX S17,MS.A27
mormdwchimcm.am
SP_ NC=R
�NGINEEFING_
1533 EAST NQRTHFIELD DRIVE
SUITE 400
DW W SPENCQERMEP CON
D4C3982
STATE OF
1
Zw
m
io
O
JW
dU
�
o
fa
w
"Im
ZO
ZIP 66 0�o
<,G= w _<
8 o3W woo 0E1
zzw3w l LZ V¢a
o a V3.Wg< mom ogLL
ova �y
DATE: 05/30/19