HomeMy WebLinkAboutE-3 Electrical Notes-SS-082318GENSR 4L NOTES: GENERAL REQUIREMENTS: A. ELECTRICAL CONTRACTOR SHALL COORDINATE FULLY WITH OTHER CONTRACTORS ASSOCIATED WITH THIS PROJECT TO VERIFY ALL EQUIPMENT LOCATIONS, CONNECTION REQUIREMENTS, ELEVATIONS AND LOCATIONS OF PIPES, CONDUITS AND DUCTS TO PREVENT CONFLICTS DURING CONSTRUCTION ANY RELOCATION OR REROUTING OF EQUIPMENT, PIPES, CONDUITS, DUCTS OR MATERIALS RESULTING FROM A LACK OF COORDINATION BETWEEN CONTRACTORS WILL BE AT THE CONTRACTORS EXPENSE. B. EQUIPMENT ROUGH -INS SHOWN ARE ACCURATE TO THE BEST OF DESIGNER'S KNOWLEDGE. HOWEVER IN SOME INSTANCES, THE OWNER OR SUPPLIER MAY SUBSTITUTE, OR THE EQUIPMENT ITEM MAY VARY FROM WHAT IS SHOWN. THEREFORE, THE CONTRACTOR SHALL VERIFY ALL CRITICAL DIMENSIONS WITH THE OWNER PRIOR TO CONSTRUCTION. FAILURE OF THE ELECTRICAL CONTRACTOR TO VERIFY THESE DIMENSIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION DIRECTLY UPON THE CONTRACTOR C. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED DISCONNECT SWITCHES AND MOTOR STARTERS TO ALL EQUIPMENT, WITH THE EXCEPTION OF ROOF TOP UNIT DISCONNECT SWITCHES (TO BE INCLUDED IN RTU PACKAGE). D. ELECTRICAL CONTRACTOR SHALL PROVIDE AS -BUILT DRAWINGS AT JOB COMPLETION TO GENERAL CONTRACTOR E. ALL WORK SHALL BE INSTALLED PER ALL GOVERNING CODES. F. ALL LIGHTING CIRCUIT BREAKERS TO BE "SWITCH GRADE". G. ALL JUNCTION BOXES INSTALLED ABOVE OR DIRECTLY BELOW THE SUSPENDED CEILING SHALL BE SUPPORTED IN ACCORDANCE WITH THE NEC. H. COMPUTER AND PHONE WIRING SHALL BE ROUTED IN 3/4" CONDUIT TO PHONE BOARD FROM DEVICE LOCATION. J. ALL ISOLATED GROUND RECEPTACLE CIRCUITS SHALL BE EQUIPPED WITH INSULATED GROUND CONDUCTOR AND SEPARATE NEUTRAL WIRE. K NEUTRAL WIRES FOR ISOLATED GROUND CIRCUITS SHALL NOT BE SHARED WITH OTHER BRANCH CIRCUITS. PROVIDE SEPARATE NEUTRAL WIRE FOR EACH ISOLATED GROUND CIRCUIT. L. ISOLATED GROUND CIRCUITS SHALL NOT BE ROUTED WITHIN SAME CONDUIT AS GENERAL BRANCH CIRCUIT WIRING. PROVIDE SEPARATE CONDUIT FOR SERVICE TO ISOLATED GROUND CIRCUITS. M. ISOLATED GROUND RECEPTACLES SHALL UNDER NO CIRCUMSTANCE BE INSTALLED IN COMMON JUNCTION BOX WITH NON -ISOLATED GROUND TYPE RECEPTACLE. N. USE CIRCUIT BREAKERS UL. LISTED AS HACR TYPE FOR USE WITH HVAC EQUIPMENT HAVING MOTOR GROUP COMBINATIONS AND MARKED FOR USE WITH HACR TYPE CIRCUIT BREAKERS. O. ALL EXIT SIGNS, EMERGENCY EGRESS LIGHTS AND NIGHT LIGHT FIXTURES SHALL BE CONNECTED TO THE BRANCH CIRCUITS INDICATED AHEAD OF RESPECTIVE CONTROL SWITCH, IN ORDER TO PROVIDE UNSWITCHED SOURCE TO FIXTURES. P. ALL 125 VOLT, SINGLE PHASE, 15 OR 20 AMP RECEPTACLES LOCATED IN THE LOUNGE AREA SHALL HAVE GROUND -FAULT CIRCUIT -INTERRUPTER PROTECTION AS REQUIRED BY THE NEC. 1QACrmW,4Y SYSTEMS: A. ALL BRANCH CIRCUIT WIRING SHALL BE ROUTED IN EMT, ELECTRICAL METALLIC TUBING. USE STEEL SET SCREW TYPE FITTINGS ON ALL EMT. FLEXIBLE METAL CONDUIT IS ALLOWED, WHERE APPROVED BY BUILDING/ELECTRICAL CODES. B. CONDUIT SHALL BE SUPPORTED AT INTERVALS PER NEC REQUIREMENTS AND SHALL BE SECURELY FASTENED TO BUILDING WITH AN APPROVED FASTENING SYSTEM. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Camel DATE: 06/05/19 L RING, WIRING DEVICES, PLATES AND GROUNDING: A. ALL WIRING SHALL CONSIST OF COPPER CONDUCTORS WITH THERMOPLASTIC INSULATION RATED FOR SIX HUNDRED (600) VOLTS. ALL WIRING INSULATION SHALL BE HEAT AND MOISTURE RESISTANT TYPES THW, THWN, OR THHN FOR INTERNAL AND DRIVE LOCATIONS. B. MINIMUM CONDUCTOR SIZE SHALL BE NO. 12 AW S FOR ALL POWER CIRCUITS (I.E. RECEPTACLES, LIGHTING, EQUIPMENT POWER, ETC). NUMBER 14 AUG SHALL BE MINIMUM SIZE PERMITTED FOR EQUIPMENT CONTROL CIRCUIT WIRING UNLESS NOTED OTHERWISE, OR SPECIAL REQUIRED FOR SPECIFIC SYSTEMS 0A, COMPUTER DATA SYSTEMS, di C. ALL SPLICES AND CONNECTIONS SHALL BE MADE IN CUTLET BOXES, JUNCTION BOXES OR EQUIPMENT WHERE ACCESSIBLE. D. CONDUCTORS SHALL BE PULLED WITHOUT THE USE OF OIL OR GREASE. WIRE PULLING LUBRICANTS WHICH ARE APPROVED FOR USE WITH CONDUCTOR INSULATION MAY BE USED. CARE SHALL BE TAKEN IN PULLING WIRE TO ASSURE THAT MAXIMUM ALLOWABLE PULLING TENSION OF WIRE IS NOT EXCEEDED. WIRING WITH DAMAGED CONDUCTORS OR INSULATION WILL NOT BE ACCEPTED. E. ALL PLUG-IN DEVICES SHALL BE GROUNDED TYPE. A GROUNDING JUMPER FROM RECEPTACLE TO OUTLET BOX SHALL BE INSTALLED WHERE CONDUIT SYSTEM IS USED FOR GROUND. F. INSTALL INSULATED GREEN GROUNDING CONDUCTOR (NO. 12 AWG MINIMUM) IN RACEWAYS AS INDICATED CN DRAWINGS AND IN ALL NON-METALLIC RACEWAYS PER NEC. G. SWITCHES FOR LIGHTING CONTROL SHALL BE INDUSTRIAL GRADE. COLOR TO MATCH AREA FINISHES, SIDE WIRED ONLY, TWENTY (20) AMP. ONE HUNDRED TWENTY/TWO HUNDRED SEVENTY-SEVEN (120/211) VOLT. H. DUPLEX RECEPTACLES SHALL BE INDUSTRIAL GRADE, THREE (3) WIRE GROUNDING, COLOR TO MATCH AREA FINISHES, FINDER GROOVE, TWENTY (20) AMP, NEMA 5-20R 125 VAC. RECEPTACLE COLOR SHALL BE WHITE WHEN MOUNTED IN CEILING. I. PLATES SHALL BE FURNISHED AND INSTALLED FOR ALL WIRING DEVICES, TELEPHONE OUTLETS, JUNCTION BOXES, ETC. J. PLATES FOR FLUSH MOUNTED DEVICES SHALL BE STAINLESS STEEL. PLATES FOR SURFACE MOUNTED BOXES SHALL BE GALVANIZED STEEL. PLATE COLOR SHALL BE WHITE WHEN MOUNTED IN CEILING. K WIRING 4 CONDUIT TO BE RUN ABOVE CEILING TO BE PLENUM RATED. LIGHTING FIXTURES: A. PROVIDE LIGHTING FIXTURES, OF SIZES, TYPES AND RATINGS INDICATED -COMPLETE WITH, BUT NOT LIMITED TO, HOUSINGS, ENERGY - EFFICIENT LAMPS, LAMP HOLDERS, REFLECTORS, ENERGY EFFICIENT BALLASTS, STARTERS AND WIRING. SHIP FIXTURES FACTORY ASSEMBLED, WITH THOSE COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION. DESIGN FIXTURES WITH CONCEALED HINGES AND CATCHES, WITH METAL PARTS GROUNDED AS COMMON UNIT, AND SO CONSTRUCTED AS TO DAMPEN BALLAST GENERATED NOISE. B. ALL LIGHT FIXTURES SHALL BE U.L. LISTED. C. INSTALL INTERIOR LIGHTING FIXTURES AT LOCATIONS AS INDICATED, N ACCORDANCE WITH FIXTURE MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE REQUIREMENTS OF NEC, NECA'S "STANDARD OF INSTALLATION", NEMA STANDARDS, AND WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT LIGHTING FIXTURES FULFILL REQUIREMENTS. D. PROVIDE AND INSTALL ALL LIGHT FIXTURES INDICATED COMPLETE AS SPECIFIED LAMPS. SEE LIGHT FIXTURE SCHEDULE FOR FIXTURE INFORMATION. E. FASTEN LIGHTING FIXTURES SECURELY TO STRUCTURAL SUPPORTS, AND ENSURE THAT FIXTURES ARE PLUMB AND LEVEL. F. FIXTURES INSTALLED IN LAY-N CEILINGS SHALL BE SUPPORTED BY ADDITIONAL WIRE SUPPORT AT TWO CORNERS (UNLESS OTHERWISE INDICATED BY MANUFACTURER'S INSTRUCTIONS / ELECTRICAL CODE). ATTACHED TO CEILING GRID, AND ANCHORED TO STRUCTURAL MEMBER THIS ADDITIONAL WIRE SUPPORT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR AND IS NOT CONSIDERED PART OF GENERAL GRID LAYOUT. G. PROVIDE EQUIPMENT GROUNDING CONNECTIONS FOR INTERIOR LIGHTING FIXTURES AS INDICATED. TIGHTEN CONNECTION TO COMPLY WITH TIGHTENING TORQUES SPECIFIED IN UL Si 486A TO ASSURE PERMANENT AND EFFECTIVE GROUNDS. G &Ao4 h AP . s if . . Xd� 9� Es+WA" 5142 Madison Avenue, Suite 4 Indianapolis, IN 46227 )317) 783-2343 r.*AR ' eB f�Qej���iy TEpe �q'G�. o. 033778 ROBERT E. BEAMAN N AROD033778 PROJECT NO.: 1801 A DRAWN BY: rboi CHIC BY: DATE: JUNE 25, 2018 REVISIONS: E11111111111111113