RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Carmel
�N;1�v�tB,AP>ngA�1
DATE: 06/17/19
LIGHTING PLAN
Note:
Unless otherwise noted on plan, connect all
exit signs (fixture types'X1' and/or'X2') to the
room lighting circuit the exit sign is serving
(ahead of any local switching means).
Note:
E.C. shall comply with the IBC in regards
to fire rated membrane penetrations.
Utilize means of fire rated junction boxes,
"putty, pads', fire blocking and offsetting.
General Notes:
A. All 120 volt, 20 amp circuits over 60' in length shall be
#10 AWG, over 95 shall be 418, over 145'shall be it6.
B. Contractor shall coordinate wth all other trades to avoid
conflicts of space.
C. Contractor shall coordinate the exact location of all
devices with all other trades prior to rough -in. Exact
location to be determined in the field.
D. Contractor shall coordinate with the mechanical and
plumbing contractors for exact locations of eW ipment
prior to rough -in.
E. Refer to sheet E7.1 for details and symbols.
F. Refer to sheet EST electrical riser diagram.
G. Refer to sheet EST and E6.2 for electrical scre dule(s).
H. Shared neutrals shall not be permitted
J. Note -H-clips are not acceptable for To ruction box
supporting.
K. Switches shall be a maximum+48' A.F.F.tothetopot
The device unless otherwise noted.
L. Receptacles, telephone cutlets, and television outlets
shall be a minimum of +18' A.F.F. W the botmm of the
device unless otherwise noted.
M. Where devices are installed in fire walls. the boxes shall
be rated and sealed for installation in aline wall.
N. Provide HACR circuit breakers for all HVAC and
refrigeration equipment.
P. No conduit to be supported from the roof back.
Q. All light fixtures marked EM (Emergency) shall be on a
switched circuit and have an emergency battery pack.
Plan Notes:
2O Circuit shall be controlled by photocell 'On' and digital
time switch "OUP'.
3O Existing light fixture to be carefully removed in its entirety
(including all associated hardware) and returned to
Owner's inventory.
4O Existing light fixture to be carefully relocated in its
entirety including all associated hardware. Extend,
adjust and/or modify wiring as required to accommodate
new location.
OProvide and install new swtchbontrol(see Electrical
Symbols Legend for switch/control type). Wire as
required to control existing light fixtures) as shown.
OConnect to existing lighting circuit in this area.
(D Provide and install new swervicontrol(see Electrical
Symbols Legend for switchhontrol type). Wire as
required to control existing and existing relocated light
tixtionds) as shown.
13 Provide and install an emergency micro inverter like
Bodine ELI-S-20 (for emergency operation oPW1 E'type
fixture). Install on nearest interior wall and mount as high
as possible.
14 Provide and install an emergency micro invader like
Bodine ELI-S-Z (for emergency operation oPW2E'type
fixture). Install on nearest interior wall and mount above
accessible ceiling (while still being safely accessible).
Provide appropriate caip able enclosure (maintain
manufacturer required ventilation clearances where
applicable).
146TH STREET
i
c
PROJECT"
LOCATION
IN
l KEY PLAN
CURRAN
ARCHITECTURE
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317. 288. 0681
F :: 317. 288. 0753
\o
STATE OF
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT TE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
O C0PWJCM30ia OIRviNARcHTR7IM
PLAYSCHOOL
AT LEGACY
GYM ADDITION
14454 COMMUNITY DRIVE
CARMEL, INDIANA 46032
REVIEW SET 11.16.18
BID SET 11.26.18
PERMIT SET 02.04.19
1Q ADDENDUM 01 02.04.19
170299
L111cra 2Lem 10aI
E291