HomeMy WebLinkAboutK2 - 190102ELECTRICAL NOTES
1, RJECIRICALSYSIEM IS DESIGNED FOR 120 VOLTS,I PIA ,4 WIRE AT
60 HERTZ,
2, OUTLETS AND ROUGH INS SHOWN PERTAIN TO AND ARE FOR FOOD
SERVICE RXRIRES AND EQUIPMENT ONLY. SEEARCHITECRIRALAND/OR
ENGINEERING PLANS FOR ANY ADDITIONAL ROUGH IN REQUIREMENTS
3, THIS ELECTRICAL PLAN IS INTENDED TO SHOW ROUGH IN LOCATIONS
AND LOAD REQUIREMENTS ALL DIMENSIONS ARE SHOWN FROM
FINISHED SURFACESTO THE CENTERLINE OF THE ROUGH IN LOCATION
UNLESS OTHERWISE NOTED.
4, UNLESS OTHERWISE NOTED, ALL ELECTRICAL WORK FOR FABRICATED
FOODSERVI CE EQUIPMENT SHALL BE COMPLETELY WIRED BY KITCHEN
EQUIPMENT DIVISION TO AJUN CTION BOX OR PULLBO%MOUNTED ON
THE EQUIPMENTIN AN ACCESSIBLE LOCATION. FINAL CONNECDONSTO
PANEL BOARDS TO BE THE RESPONSIBILITY OF THE E.0
5, FINAL CONNECTIONS TO ALL EQUIPMENT AND ALL REQUIRED MATERIALS
TO BE THE RESPONSIBILIN OF THE E.0
6, E.CTO PURNISH AND INSTALLTHE FOLLOWING'.
A ALLJUNCTION BOXES, RJECTRICALOUOTTS, COVER PLATES, ETC,
NOT BUILT INTO FIXTURES OR EQUIPMENT. ALL OUTLETS, JUNCTION
BOXES, COVER PLATES, ETC., IN DISHROOMS, OR AS INDICATED ON
SCHEDULES, MUST BE VAPOR PROOF.
B. SHUNT TRIP CIRCUIT BREAKERS/CONTACTORS OR DISCONNECTS FOR
FIRE CONTROL SYSTEM SHUTOFF OF FUUDSERVICE EQUIPMENT
BELOW HOODS/VENTRATORS AS REQUIRED BY N.F.P.A. 96 AND
LOCAL CODES
C. DISCONNECTS OR OTHER DEVICES AS REQUIRED BY FEDERAL, STATE,
AND LOCAL CODES
Z WHEN APPUCABLE,EC. TO INSTALL FS.EC.-PROVIDED ELECTRICAL COM-
PONENTS, PROVIDE ALL CONDUIT AND WIRING, AND INTERCONNECT
BETWEEN THE FOLLOWING'.
A REMOTE REFRIGERATION EQUIPMENT TO EVAPORATOR COILS
B. CONTROL PANELS TO WATER- TYPEVENTILATORS AND EXHAUST OR
SUPPLY FANS PER MANUFACTURER'S SPECIFICATIONS
C. KITCHEN EXHAUST HOODUVENTILATORS TO FIRE CONTROL SYSTEM
AND SHUTOFFS
8, ALL ELECTRICAL AMPERAGE NOTED ON ROUGH IN SCHEDULE INDICATES
RILLLOADAMPDRAW NOT RECOMMENDED CIRCUIT BREAKER SII
E.C. 15 RESPONSIBLE FOR PROPER BREAKER SIZING WITH THIS INFORMA-
TION.
9. PEDESTAL RECEPTACLES ARE NOT TO EXCEED 4-1/2"AM,
10, E.C. TO PURNISH AND INSTALL GROUND FAULT RECEPTACLE OR FORM
GROUND FAULT CIRCUIT BREAKER FOR MY RECEPTACLE WITHIN FIVE
FEET IS 0") OF SINK,
ABBREVIATIONS
ELECTRICAL ROUGH -IN PLAN
SCALE'. 1/2"=1'-0"
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City
yof Cainged (\��
�VT�Vt�D*tiYWMC_
DATE: \ 06/17/19
ELECTRICAL ROUGH- IN PLAN
SCALE: 1/2"=1' 0"
ELECTRICAL SCHEDULE
ELECT. HGT.
ITEM NO.
I CITY.
ITEM DESCRIPTION
ELECT.
PS AMPS
WATTS
Hin
VOLTS
i
S
i
UFF)
ELECTRICAL REMARKS
3
1
REACH -IN REFRIGERATOR
E3
2.2
250
114
120
1
%
60"
E.C. TO PROVIDE DO PLE%RECEPTACLE.
4
1 1
POPCORNMACHINE
I E4
1 10.0
1 1.200 I
112D
I 1
I
I %
1
48"
IE.C. TO PROVIDE DUPLEX RECEPTACLE.
ELECTRICAL SYMBOLS
SYMBOL
DESCRIPTION
♦
POWER SUPPLY (DIRECT)
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRAPIE%RECEPTACLE
®
SPECIAL PURPOSE RECEPTACLE
Q�
FLOOR RECEPTACLE MUUSHar PEDESTAO
Q
CEILING RECEPTACLE MUJSHor DROP{ORD)
Q
IUNCRON BOX
A
EMPTYCONDUM
a
DISCONNECTSWRCH
171
FIRE PULLSTATION
V
TELEPHONE ar DATA LINE
oJH`1A4 AND COS)•Oyeq
OG S9i
o r
sty_
a
SINCE 1✓I1
C&T Design and
Equipment Co., Inc.
2750 Tobey Drive
Indianapolis, Indiana 46219
Phone: 317.898.9602
www.o-idealgn.com
D fal sus TOATr_Twls of woo
SI ECh9N S
PROJECT MANAGER:
CHRIS MONICO
EMAIL ADDRESS:
cmonico@c-tdesign.com
i. At pnwmdlw also electoral connections carpentry aunt metal and
beetksecommumuny0 there.ps .schal
em Cmdrracemr ue.haki
2 Thisdaw,N a the properly a CST Design and succeed e0., Inc. a
shall not be copied or reproduced In any reattachment the games con
am d CAT oengn am Equipment Co. Its rumd.,mlNo,wet
on mk other man that furnished by CST Design and equipment Co..
ncWsolve lreserved b make a charge for designing coca.
3 W HIe every amount ha been male In prmar tian m thla plan W Wuld
records the designer am company cannot guarantee agalntl human
error. The mmaclor Lor bulkier must check all blmerslons and dM9k
and note" anydkwepmclesto CAT Design and Tyalpmem CO. Inc
Z
O
U`
w
J
Q
J
0
0
2
U
ISSUE DATE: 01/02/19
Rev.
Lane
Dewnarwn
PROJECT No: 2018-242
DRAWN BY: Mild
SHEET SCALE: AS Indicated
SHEET TITLE:
ELECTRICAL
ROUGH -IN PLAN
SIT _ T NUMBER.
K2