HomeMy WebLinkAboutM0.1 - 190204RELEASEOI
Subject to con
of St;
Mechanical Symbols and Abbreviations
Abbreviations
Drawing Symbols
Sheet Metal Symbols
ACC
air cooled condenser
GC
General Contractor
Denotes section Section number
Fire damper
1Pn
ACCU
air cooled condensing unit
GPM
gallons per minute
r
AFF
above finish floor
H
humidifier
Volume damper
OR T
BCC
branch circuit controller
HDR
heavy duty register or grille
S 1
Supply .
Supply diffuser
OR
ROD
backdraft damper
PRO
heat recovery box
M1
BOD
bottom of duct CC cabinet convector
HRU
variable refrigerant heat recovery unit
Sheet number
Where
Supply duct riser
CD
ceiling diffuser (supply air)
HP
heat pump
Arrow indicates Direction section
CEF
ceiling exhaust fan
HWP
hot water pump
in which Section is cut Islocated
t
Return dud riser
0
CFM
cubic feet per minute
HWR
hot water return
CUH
cabinet unit heater (electric or hw)
HWS
hot water supply
Supply register
CEO
CHWP
CHWR
chilled water pump
chilled water return
HX
IN
heat exchanger
inch
Denotes detail Detail number
Linear diffuser
g
CHWS
chilled water supply
KEC
kitchen equipment contractor
CT
cooling tower
LAT
leaving au temperature
D 1
Flexible connection
CP
condensate pump (steam)
LS
linear slot diffuser
CW
cold water
MAN
manual
M1 E—Sheet number
Return au grille
IDS
dry bulb
MAU
make up air unit
Where detail
DOAS
dedicated outdoor air system
MFR
Manufacturer
Denotes Is located
Exhaust grille
0
DSAC
ductless split air conditioner
MBH
1000 BTUh
Construction
0
diameter
MC
Mechanical Contractor
Start point
Exhaust tan
0
EDB
entering air dry bulb
O/A
outside air
EWB
entering ai r wet bulb
DAL
outside air louver
Square Elbow with Turning Vanes
EBR
electric baseboard radiation
PD
plaque diffuser
EC
Electrical Contractor
PSI
pounds per square inch
Rectangular to round ductlransNon
ECR
eggcrate grille
RA
return air
EDC
electric dud coil
RD
round diffuser
Note Designation
Temperature Control Symbols
EF exhaust fan
Ireturn air grille
EG
exhaust grille
RPM
revolutions per minute
Room thermostat or sensor
OT
EH
exhaust hood
I
roof top unit
Plan Ni Specific information as indicated on a
ER
exhaust register
SA
supply air
drawing
Room homeland or sensor
Qo^®
ERV
energy recovery ventilator
SBCC
sub branch circuit controller
ESP
external static pressure
SDG
spiral dud grille
m Leader linete plan note referenced
Motorized damper
EVC
evaporative cooler
SP
Staticpressure
directed item of plan note
CO2 Sensor
EWH
electric wall heater
SR
ter
supply register
upi supply
reference
F
furnace
SVK
solenoid valve kit
FD fire damper
TOO Temperature Control Contractor
1 Circle with number indicates a plan
SO
fire and smoke damper
TSP
total static pressure
note reference, with the number
Design Conditions:
FLA
full load amps
UH
unit heater
indicating the item number of the plan
Outdoor:
FIRM
feet per minute
VAV
variable air volume box
note referenced
Summer 89-75F
FPVAV
fan powered variable air volume box
VD
volume damper
General Plan Notes: General information as it pertains
Winter:-3F
Indoor:
FT
foot
WB
wet bulb
only to the drawing it is on
Summer 75F and 50%RH
G
gas
WT
weight
Winter: 70 F and 20%RH
XT
expansion tank
General Notes: General information pertaining
fo all the drawings of the
disdpline it is on
APPLICABLE CODES AND ORDINANCES:
Provide all materials and equipment and perform all labor requiredto install complete
and operable mechanical systems as indicated on the drawings, as specified and as
required by code.
Entire installation shall be in strict accordance with applicable codes and ordinances.
Secure and pay for all required permits.
Provide a minimum of 10'-0' between exhaust outlets, plumbing veins and all outside
air intakes.
Provide a minimum o, 3'-0' between exhaust outlets and operable windows or doors
Contractor shall not locate any duct or piping directly over any electrical panel,
switchgear, transformer, etc. Coordinate locations of tlucts and piping with the
Electrical Contractor to avoid these conflicts.
AS -BUILT DRAWINGS:
Contractor shall maintain a set of drawings that document field changes to these
drawings, and shall submit them to the Arch sect/Engineer as part of the project close
out.
ARCHITECT:
Contractor shall be guided by the Architect's reflected ceiling plan for exact location
of diffusers, registers and grilles unless otherwise noted.
Coordinate diffuser, register, and grille locations with architectural reflected ceiling
plans, lighting, and other ceiling items and make minor dud modifications to sul.
Exterior louvers are indicated for information only. Detailed descriptions are provided
in the architectural specifications.
Furnish all material and equipment as specified except where specific approval for
substitution is given by the Architect/Engineer.
GENERAL:
Do not operate new HVAC systems until drywall sanding is complete and primed,
and jobslte dust is no longer significant. Construction dust is extremely detrimental to
the longterm operation o, the HVAC system. Provide temporary heating or
coolingndeh umidifi cation systems during construction if it is desired or required.
These drawings indicate required sizes and points of termination for piping,
ductwork, conduit, etc. The equipment shown I ustretes suggested routing, but all
necessary offsets and fittings may not be shown. Contractor shall install his work in
a manner that will conform with the structure. Contractor shall avoid obstructions,
preserve head room and maintain maximum clearance without additional cost to the
Owner.
All dimensions shown on these plans are in feet and/or inches unless otherwise
noted.
Mechanical work shall be complete in every detail and all miscellaneous Items of
material and labor necessary to complete the work described, shown or reasonably
implied on drawings or specifications, shall be included in the contract.
Proposal shall be based on specifi ad material and equipment. In order to promote
competition, however, bidders may submit alternate proposals on any alternate
materials and/or equipment they wish to propose, including any price changes
affected by acceptance of alternatives. These must be provided in addition to the
base bid not in place of the base bid.
Contract document drawings for mechanical work are diagrammatic and are intended
to convey scope and general arrangement only.
Install all mechanical equipment and appurtenances in accordance with
Manufacturers'recommendations, contract documents, and applicable codes and
regulations.
OR CONSTRUCTION isolation as specified for all mechanical equipmentto prevent
fibration to building Structure.
pliance with all regulations Rusting underground utilities is shown in an approximate way only.
e and Local Codes
Lity 0 Lateral
DATE: 06/17/19
Mechanical General Notes
The Contractor shall determine the exact location of all existing utilities before
commencing work. The Contractor shall pay for and repair all damages caused by
failure to exactly locate and preserve any and all underground utilities unless
otherwise indicated.
Coordinate construction of all mechanical work with Architectural, Structural, Civil,
Elecrical work, etc., shown on other contract document drawings.
Each respective contractor shall be responsible for coordinating the installation of his
work with the work of other contractors and Trades prior to the installation.
Maintain a minimum of 6'-8' clearance to underside of pipes, ducts, conduits,
suspended equipment, etc., throughout access routes in mechanical rooms.
All tests shall be completed before any mechanical equipment or piping insulation is
applied.
Locate all temperature, pressure, and flow measuring devices in accessible locations
with straight section of pipe or duct up and downstream as recommended by the
Manufacturer for appropriate accuracy.
Work shall include startup of all systems, furnishing of operating and maintenance
instructions and one (1) year guarantee, commencing on data of acceptance by the
Owner or as otherwise specified.
Testing, adjusting, and balancing agency shall be by a member of the Associated Air
Balance Council (AABC) or the National Environmental Balancing Bureau (NEBB).
Testing, adjusting, and balancing shall be performed in accordance with the AABC
standards.
Where two or more items of the same type of equipment are required, the product of
one Manufacturer shall be used unless otherwise noted.
Coordinate all equipment connections with Manufacturerscertified drawings.
Coordinate and provide all dud and piping transitions required for final equipment
connections b furnished equipment. Field verity and coordinate all duct and piping
dimensions before fabrication.
The locations of all items shown on the drawings or called for in the specifications
that are not definitely fixed by dimensions are approximate only.
The exact locations necessary to secure the best contlltions and results must be
determined by the project site conditions and shall have the approval of the Engineer
before being installed. Do not scale drawings.
All miscellaneous steel required to ensure proper installation and/or as shown in
details for piping, ductwork, and equipment shall be furnished and installed by the
Mechanical Contractor.
Provide access panels for installation in walls and ceilings, where required to service
dampers, valves, smoke detectors, and other concealed mechanical equipment.
Access panels shall be turned over b General Contractor for installation.
All equipment, piping, ductwork, etc., shall be supported as detailed, specified
and/or required to provide a vibration free installation.
All ductwork, piping, and equipment supported from structural steel shall be
coordinated with the General Contractor. All attachments to steel bar joists, trusses,
or joist girders shall beat the upper member. Provide beam clamps meeting MSS
standards. Welding to Structural members shall not be permitted. The use of
c-clamps shall not be permitted.
Mechanical equipment, ductwork, and piping shall not be supported from metal deck.
All roof mounted equipment curbs for equipment provided by the Mechanical
Contractor shall be furnished by the Mechanical Contractor and installed by the
General Contractor.
Locations and sizes o, allfloor, wall, and roof openings shall be coordinated with all
othertrades.
All openings in fire walls due to ductwork, piping, conduit, etc., shall be fire Mopped
with a product similarto 3M or equal. Product shall be listed by ILL or FM and meet
the requirements of local and state codes.
All air conditioning condensate drain lines from each air handling unit or rooftop unit
shall be piped full size of the unit drain outlet, with 'P'trap, and piped tothe neared
drain or roof deck. See details shown on the drawings or the contract specifications
for depth of air conditioning condensate traps.
Refer to typical details for ductwork, piping, and equipment installation
All valves, coils, dampers, etc. Shall be installed allowing easy access to them.
Areas adjacent to the access panels shall be clear of obstruction.
Furnish and install all equipment and material required to complete the installation as
shown on the drawings.
Equipment sizes, weights, power, geometry and service space requirements may
vary between different Manufacturers. Consult approved Manufacturer drawings as
submitted and coordinate with these drawings. h shall be the Contractor's
responsibility to bear the cost associated with this coordination.
All air handling units shall operate without moisture carryover.
Locate all mechanical equipment fill single duct, variable volume, constant
volume and fan powered boxes, fan coil units, cabinet heaters, unit heaters, unit
ventilators, coils, steam humidifiers, etc.) for unobstructed access to unit access
panels, controls, and valving.
Refer to mechanical details for additional equipment requirements.
HVAC /SHEETMETAL:
Certain items such as rises and drops in ductwork, access doors, volume dampers,
etc., are indicated on the contract document drawings for clarity for a specific location
requirement and shall not be interpreted as the extend of the requirements for these
items.
All ductwork dimensions, as shown on the drawings, are internal clear dimensions.
Keep all ductwork, dud system and equipment openings covered with adhesive duct
protective wrap like VentureTape 1512, until system start-up. This is to prevent
intrusion of construction dirt and debris into the dud system, and HVAC equipment.
Provide flexible connections in all ductwork systems (supply, return, and exhaust)
degraded to air handling units, fans, and other equipment which require vibration
isolation. Flexible connections shall be provided at the point of connection to the
equipment unless otherwise noted.
Unless otherwise noted, all ductwork is overhead, tight to the underside of the
structure, with space for insulation and below any required piping.
Runs of flexible duct shall not exceed 5'-0'. Flexible duct shall not be used as an
elbow. Provide sheet metal elbow at diffuser neck where tap is not out of the bottom
of the supply main. Refer to details.
All ductwork shall be coordinated with all trades involved. Offsets in duds, inc using
divided duds and transitions around obstructions, shall be provided at no additional
cost to the Owner.
Provide access doors in ductwork to provide access for all smoke defectors, fire
dampers, smoke dampers, volume dampers, humidifiers, coils, and other items
located in the ductwork which require service anchor inspection.
Smoke detectors shall be furnished by Unit Manufacturer and wired by the Electrical
Contractor. The Mechanical Contractor shall be responsible for mounting the smoke
detector in ductwork as shown on the drawings and in accordance with
Manufacturer's printed instructions.
See specifications for ductwork gauges, bracing, hangers, and other requirements.
Contractor shall not locate any duct or piping directly over any electrical panels,
switchgear, transformer, etc. Coordinate locations of tlucts and piping with the
Electrical Contractor to avoid these conflicts.
All duds penetrating shaft walls shall be sealed airtight with firestop.
Provide volume dampers upstream of all air inlets/outlets unless otherwise noted.
All rooftop units shall be accessed from the roof.
Power for all rooftop units shall be wired by the Elecrical Contractor and shall be
placed on a dedicated circuit.
Locate rooftop units on roof. Coordinate with structural plans. Set units as required to
allow supply and return openings to clear roof structure.
Furnish and install rain hoods on flues and intake ducts above roof
Provide companion opposed blade volume dampers with all diffusers mounted in
drywall ceilings. Do not provide companion volume dampers with diffusers mounted
in lay -in tile ceilings. Provide manual volume dampers in the branch duds serving
diffusers located above lay in tile ceilings.
Diffusers, registers, and grilles mounted in drywall ceilings shall have plaster frames.
Unless otherwise noted all ductwork above ceilings shall be insulated with 1$'
dudwrap. Dudwrap shall be.751b / cu ft. density.
Unless otherwise noted all ductwork in unconditioned spaces shall be insulated with
2' ductwap (Min 116). Ductwap shall be 751b / cu ft. density.
Install volume damper at each branch takeoff from main supply ducts.
Mechanical Contractor shall furnish and install a 3'x3'x%' steel angle frame around
each rooftop unit roof opening. Field weld frames to top of joists.
Locate rooftop units on roof so that the dud drops will clear the roof structure.
Refer to Mechanical Detail Sheets for additional equipment requirements.
Phenolic dud by Pal -Dud or Kool-Duct is an acceptable alternative to sheetmetal
dud and insulation in concealed spaces. Use flanged joints. Submit detailed dud
drawings for engineer revi ew.
REFRIGERANT EQUIPMENT AND PIPING:
Conceal all refrigerant piping unless otherwise noted. Conrad Engineer for
alternatives if concealment is not possible.
Slope refrigerant piping one percent in the direction of oil return. Liquid lines may be
installed level.
Install horizontal refrigerant hot gas discharge piping with %' per 10 feet downward
slope away from the compressor.
Install horizontal refrigerant suction lines wlthy' per 10 feet downward slope tothe
compressor, with no long traps or dead ends which may cause oil to separate from
the suction gas and return to the compressor in damaging slugs.
Provide line size liquid indicators in main liquid line leaving condenser or receiver.
Install moisture -liquid indicators in liquid lines between filter dryers and thermostatic
expansion valves and in liquid line to receiver.
Provide line size strainer upstream of each automatic valve. Provide shutoff valve on
each side of strainer.
Provide permanent filter dryers in low temperature systems and systems using
hermetic compressors.
Provide replaceable cartridge filter dryers with three valve bypass assembly for
solenoid valves, adjacent to receivers.
Provide refrigerant charging valve connections in liquid line between receiver shutoff
valve and expansion valve.
Insulate all interior linesets with 1v' thick, flexible elastomeric insulation. Insulate
exterior linesets with 1- thick flexible elastomeric insulation with external .020'
aluminum protective jacket.
RELATED ELECTRICAL AND PLUMBING:
Unless otherwise noted all low voltage wiring (24 volts) shall be provided and
installed by the Mechanical Contractor. This includes fans, radiant heaters, rooftop
units, etc.
Unless otherwise noted line voltage wiring (120 volts or greater) shall be provided
and installed by the Electrical Contractor. Wiring should be concealed at all times
unless otherwise noted on the plans. Contact the Engineer if concealment is not
possible.
All control wire and conduit shall comply with the National Electric Code (NEC) and
Division 16/26 of the specifications.
Condensate drain pipe run out shall be full size to the nearest drain. Refer to'P'
sheets for nothing.
Coordinate installation of gas piping for HVAC units with Plumbing Contractor.
Furnish and install a gas cock at each unit connection.
Refer fo electrical and plumbing drawings for additional coordination with these
drawings.
Any unit supplied with natural or LP gas shall be furnished with pressure regulators
by Unit Manufacturer.
APPEARANCE:
All equipment should be installed with great regard to a neat finished product.
Whenever possible, wiring should be routed in such a way as to minimize visibility.
Piping should be tight to structure whenever possible, and orthogonal.
Eliminate the need for condensate pumps if possible.
Contact the Engineer prior to installing any equipment that will not be able to be
installed in a neat, first class manner, consistent with the Manufacturer's installation
instructions.
RELATED GENERAL CONSTRUCTION:
Unless otherwise noted flashing of roof openings will be done by the General
Contractor. Deliver rooftop unit and exhaust fan cubs b General Contractor for
installation. Conrad General Contractor to coordinate this portion of the work.
Concrete housekeeping pads to suit mechanical equipment shall be sized and
located by the Mechanical Contractor. Minimum concrete pad thickness shall be 3;6'
unless otherwise noted. Pad shall extend beyond the equipment a minimum of 6'on
each side. Concrete housekeeping pads shall be provided by the Mechanical
Contractor. It shall be the responsibility of the Mechanical Contractor to coordinate
size and location of concrete housekeeping pads with the General Contractor.
Exterior louvers are indicated for information only. Louver sizes, locations, and
details shall be coordinated with the General Contractor.
SUBSTITUTIONS:
Cost of any changes required by this, or other trades, due to substitution of
equipment other than the basis of design, shall be included in the Mechanical
Contractor's proposal.
UTILITIES:
Unless otherwise notedthe local gas company shall provide gas tothe building and
furnish and install the meter. Connection to the meter and extension of the piping
shall be made in accordance with the utility company requirements.
Contact local utility company fo arrange for gas meter installation. Furnish and install
piping and specialties as required to receive meter.
Verify local conditions at the site.
RELATED CONTROLS:
Unless otherwise noted, locate all roomthermostats and humitlistats 4'-0'
(centerline) above finish floor. Notify the Engineer prior fo installation of any rooms
wherethe above location cannot be maintained or wherethere is a question on
location.
All control wiring and related control components should be concealed unless
otherwise noted on the plans. Contact the Engineer if concealment is not possible.
TEMPORARY SERVICE:
Equipment provided as part of this contract should not be used for
heating/cool ingNernii lati on of the project prior to all sanding being complete, and at
least 1 coat of paint on all su hates. The intent of this is to prevent the infiltration of
construction dust into the heating / cool l ng coils and causing longterm performance
or reliability issues.
CURRAN
ARCHITECTURE
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317. 288. 0681
IF :: 317. 288.0753
GOLLAB9R4
TJ
$G
p
F
ti
V
-
4
W
—
2x
_.
3��
41
...a...a.
\o
STATE OF
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTIMUCTUAL PROPERTY
OF CURRAN AACHITECRRE, AND ARE NOT
TO BE USE) OR REPRODUCE), WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
o CWW 20iA(URP4NARCMTERINE
PLAYSCHOOL
AT LEGACY
GYM ADDITION
14454 COMMUNITY DRIVE
CARMEL, INDIANA 46032
REVIEW SET 11.16.18
BID SET 11.26.18
PERMIT SET 02.04.19
1Q ADDENDUM 01 02.04.19
170299
HVAC GENERAL NOTES
Moo I