Rooftop Unit Schedule
External
Cooling Performance
Heating
Electrical Connection
Air
Outside
Performance
Nominal
Static
Supply Duct
Return Duct
Weight
Mark
Space
Bryant Model
Volume
Air
Net
Net
Remarks
Tons
Pressure
Connection
Connection
(Ibs)
CFM
(CFM)
( CFM)
EDB EWB LWB sensible
LDB (°F)
Total
EDB LDB Gas Input
Voltage
Phase stayer
MCA MOCP
Disconnect
(w g)
(°F) (°F) (°F) Cooling
Cooling
(°F) (°F) (MBH)
(V)
(0) By:
By:
(MBH)
(MBH)
RTU -1
118(Basketball
Court)
581JP09M224
7.5
3000
900
0.6
Horizontal
Vertical
817
687
58.4
57.9
73.34
104.83
48.1
106.6
224
208
3
46
50
MFR
MFR
925
1,2,3,4,5,6,8
RTU -2
Various
581JP07J150
5
2000
450
0.6
Vertical
Vertical
81.7
68.7
58.2
57.1
49.34
74.52
48.1
105.3
150
208
3
37
50
MFR
MFR
765
1,2,3,4,5,67
Notes:
1. Gas pressure regulator suitable for site gas pressure.
Acceptable Manufacturers:
2. Provide Stainless Steel Heat Exchangers.
1. Bryant
3. Provide hot gas reheat for dehumidification cycle, and appropriate controls.
2. Carrier
4. Provide Demand Control Ventilation. Provide 002 sensors in each space for DCV control.
3. Trans
5. Provide digital 7-Day programmable, Witt enabled T-state with occupied and unoccupied cycles and hurridistat like Honewell Vson Pro 6000.
4. Aeon
6. Provide 14' full parameter roof curb.
5. Johnson Controls
7. Vertical supply and return for unit.
6. catkin
B. Horizontal supply and vertical return for unit.
Notes:
1. DCV option included for code compliance.
2. Schedule describes only RTU types and not RTU count. Refer to plans for quantities and locations
Dedicated Outdoor Air System
ernal
External
DX Cooling Performance
Heating Performance
Hot
Electrical Connection
Outside
Gas Reheat Coil
Nominal
Static
Weight
Net
Net
Mark
Space
AAON Model
Air
Remarks
Tons
Pressure
Ibs
(CFM)
EWB
OF)
e
EDB
LDB
Gas
Voltage
Phase
Starter
Disconnect
(w g)
fO�
F)
(°
(F)
Cooling
Cooling
9
(°)
(°)
BHut
( )
(MBH)
( )
LDB (°F)
O
(0)
MCA
MOCP
By:
By:
(MBH)
(MBH)
DOAS-1
All
BIN - 015 - 8 - 0
- E A 0
15
2400
0.75
95
78
54.89
54.30
98.62
184.59
-3
87.3
292.5
41
70
208
3
74
90
MFR
MFR
1884
See Notes
9-30B
Notes:
foam insulation.
Acceptable Manufacturers:
1. R410A Refrigerant.
8. Stainless steel drain pan.
1. Aeon
2. Direct Drive fan with VFD.
9. Provide remote, wall mounted
2. Addison
3. Gas pressure regulator suitable for
system manager.
3. Dailtin/McQuay
site gas pressure.
10. O/A Temp reset.
4. Trans Horizon
4. 14- roof curb.
5. 10:1 Modulating, stainless steel,
natural gas fired furnace.
6. 2' Pleated, MERV 7 filters.
T Double wall construction with RI
Ductless Split Air Conditioner
Electrical Connection
Mark
Cooling
Heating
Indoor
Outdoor
Nominal
Airflow
Area Served
Manufacturer
Capacity
Capacity
MCA
MocP
Disconnect
Remarks
Model
Model
Tons
(CFM)
voyage (v)
Phase (o)
outdoor
(BTU/hr)
(BTU/hr)
(Amps)
(Amps)
mdoorunh
wh
FCD-110
DSHP-110
Olfice(110)
Bryant
40MBC009
38MAO
9000
10W0
3/4
320
20B
1
9
15
MFR
2,3,4,5
FCD-111
DSHP-111
fTStorage
Bryant
619PE0018
38MAO
10000
17OW
1.5
600
20B
1
18
25
MFR
See Notes
Notes:
Acceptable Manufacturers:
1. Provide integral drain pan mounted condensate pump.
1. Bryant
2. Provide flooded drain pan interlock.
2. Dal
3. Line voltage to outdoor unit.
3. Trans
4. Provide locking disconnect.
4. Johnson
Controls
5. Follow manufacturers instructions on installation
Terminal Outlets
Mark
Function
Price
Model
Airflow
Range
(CFM)
Face Size
(in.)
Neck Size
(in.)
Color
Remarks
PD-1
Plaque off user
SPD
50-180
24x 24
so
White
1,2,3
PD-2
Plaque Diffuser
SPD
181300
24x 24
BO
White
1,2,3
PD-3
Plaque Diffuser
SPD
301450
24x 24
100
White
1,2,3
SR-1
Supply Register
520S
0-100
7a%x 73/
6x6
White
1,2,3
ER-1
I Exhaust Register
1 530
1 0-100
1 7a%x73/
6x6
I White
1,2,3
RG-1
Return Grille
535
15013500
39 Yi x 27 Yi
36x 24
White
1,2,3
RG-2
Return Grille
535
101-450
13%x 13J
12x 12
White
1,2,3
ECR-2
Eggcrate Return
80
1 1501 -2000
1 24 x 24
22 x 22
White
1,2,3
Notes: Acceptable Manufacturers:
1. Provide factory extended panel for any diffuser which is smaller than the grid in which his 1. Price
installed. 2. Thus
2. Sound baffle by Sheet Metal Contractor. 3. Naicor
3. Provide plaster frame for riffusers, registers and grilles installed in gypsum board. 4. Metalaire
Electric Wall
LEASED
Heater Schedule
Electrical Connection
Mark
Area
Type
Disconnect
Remarks
SewedModel
Power(Wa16)
EWH-1
Vedas
wal
R0 Series 3
a Seri
Wall Heater
1500
120
1
12.5
MFR
1,2
Acceptable Manufacturers:
Notes:
1. Raywall
FOR CONSTRUCTION
2. coa
3. Madcaell
rbiectto compliance Whh all tabulations
of State and Local Codes
City of Carmel
\\
` mt,-blbi
DATE: 06/17/19
Sequence of Operations
DOAS-1
The DOAS shall run continuously when the building is occupied.
Heating Mode:
Stage 1:
• Modulating Heat pump shall be enabled when O/A temperature is <60 F(adj) and >40 (adj).
• Dischargw air temperature shall be adjustable between 55 F and 85 F.
• Refer to Stage 2 for operation below 40 F O/A temperature.
• Enable Stage 1 heat at 45 F when O/A temperature is increasing.
Stage 2:
• Shall be enabled when O/A temperature is below 40 F (adj).
• Modulating natural gas furnace shall utilize full modulation to maintain desired discharge air temperature.
• The discharge air temperature shall be adjustable from 55 F to 85 F.
• Disable stage 2 heat at 45 F when O/A temperature is increasing
Cooling mode:
• Refrigerant compressors shall be enabled when O/A temperature is >63 F (adj).
When coolly Is enabled the O/A should be cooled to 55 F utilizing a digital scroll compressor for load
9 9 9 P
matching and shall supply it using the following supply air reset schedule. The unit shall use modulating hot
as reheat to reheat supply air as needed. (Supply Air Reset curve shall initially be linear).
9 PP Y ( PP Y Y )
A. If CIA temperature is 63 F (adj), reheat supply to 70 F (adj).
B. If CIA temperature is 90 F (adj), reheat supply to 55 F (adl
Monitoring points
The following monitoring points shall be visible from the DOAS-1 controller.
• Supply Air Temperature (DB)
• Outdoor Air Temperature(DB)
• Outdoor Air Humidity (RH)
DOAS shall have a remote mounted (coordinate mounting location with engineer prior to installation) equipment
controller provided by the equipment manufacturer must be capable of meeting the sequence of Operations, with
occupied/unoccupied cycles, and 7 day programmability.
RTU-1, 2
RTUs shall operate when there is a call for heating or cooling from the thermostat. See plans for locations of
thermostats _ . - - - - - - _ _ _ _ _
EF-1
The exhaust fan shall operate from timer and will run continuously when the building is occupied
DSFCU-111
This unit will operate via wall mounted thermostat. See plans for location of thermostat.
DSFCU-110
This unit will operate via wall mounted thermostat. See plans for location of thermostat.
120------r---T--�---
L--J--J---IL
100 -(b b
ag--- ---I--T--T---T--T
60_-------+--�--- w a
`m
E
9_J---L_-J
< 40
20 r
-20 0 20 40 60 w 1(
Outdoor Air Temperature (°F)
D A DOAS S/A Reset Temperature Graph
M 6.1 Scale: None
CURRAN
ARCHITECTURE
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317. 288. 0681
F :: 317. 288.0753
G01,LABOROff
1.1
�G
p
F
C
w
-
w
-
11561
STATE OF
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCWSIVE INTELLECTUAL PROPERTY
OF CURRAN AACHITEC E, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
o C0fWJCM301ACAeANARCMTERINE
PLAYSCHOOL
AT LEGACY
GYM ADDITION
14454 COMMUNITY DRIVE
CARMEL, INDIANA 46032
REVIEW SET 11.16.18
BID SET 11.26.18
PERMIT SET 02.04.19
1Q ADDENDUM 01 02.04.19
170299
M691