CONSTRUCTION DESIGN RELEASE
State Form 41191 (R9/5-98)
Report Printed on:May 13, 2019
Project number Release date
406493 05/06/19
Construction type Occupancy classification
Scope of release
II-B, SPK I-2
Type of release
Project name
Street address
City County
ARCH ELEC FDN MECH
PLUM STR
Standard
Hazel Dell Urgent Care & Emergency Room
14585 Hazel Dell Pkwy
CARMEL HAMILTON
To: Owner / Architect / Engineer
E4H Environment for Health LLC
Rodney L Booze AR11800066
1217 8th Ave Ste 301
Fort Worth TX 76104
Note :(A1A & A1B): In accordance with the affidavit sworn under penalties of perjury in the application for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission. Providing false information constitutes an act of perjury, which is a Class D felony punishable by a prison term and a fine up to $10,000.
The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed below. THIS IS NOT A BUILDING PERMIT. All required local permits and licenses must be obtained prior to beginning construction work. All
construction work must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications must be filed with
and released by this Office before any work is altered. This release may be suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and
void, if the work authorized is not commenced within one (1) year from the above date.
CONDITIONS:
14B
14B0601IIB
14B07037
14B0707310A
14B071659
14W5306
14B11092
This project has been reviewed under the 2014 Indiana Building Code.
The minimum construction type permitted for this building is Type II-B. Building elements shall be
protected as specified in Chapters 5, 6, and Table 601, IBC (675 IAC 13-2.6).
Fire walls and vertical fire barriers shall be effectively and permanently identified with signs or
stenciling. Such identification shall: 1. Be located in accessible concealed floor, floor-ceiling or attic
spaces; 2. Be located within 15 feet of the end of each wall and at intervals not exceeding 30 feet
measured horizontally along the wall or partition; and 3. Include lettering not less than 3 inches in
height with a minimum 3/8 inch stroke in a contrasting color incorporating the suggested wording,
"FIRE WALL or FIRE BARRIER PROTECT ALL OPENINGS" or similar wording in accordance with
Section 703.7, IBC (675 IAC 13-2.6).
One or more fire barriers or horizontal assemblies are being provided for the purpose of separating
a single occupancy into different fire areas in accordance with Section 707.3.10, IBC (675 IAC 13-
2.6).
Fire doors shall be self-closing or automatic-closing in accordance with Section 716.5.9, IBC (675
IAC 13-2.6).
Medical gas systems shall be designed and installed in accordance with Section 5306, IFC (675 IAC
22-2.5).
Each toilet room and bathing room shall be handicapped accessible in accordance with Section
1109.2, IBC (675 IAC 13-2.6). (Clear turning radius, Door Swing, Grab Bars, Fixture Clearances,
Fixture Mounting Heights, Shower/Bathtub seats)
NOTE: Flexible air ducts, both metallic and nonmetallic, shall comply with Sections 603.6.1,
603.6.1.1, 603.6.3 and 603.6.4, IMC. Flexible air connectors, both metallic and nonmetallic, shall
comply with Sections 603.6.2 through 603.6.4, IMC, in accordance with Section 603.6, IMC.
Indiana Department of Homeland Security
DIVISION OF FIRE & BUILDING SAFETY
PLAN REVIEW DIVISION
402 W. Washington St., Room E245
Indianapolis, IN 46204
Fax & e-mail:
SUPPORT HOOSIER SAFETY
Available At Your Local Licence Branch
In accordance with Section 19 of the General Administrative Rules (675 IAC 12-6-19) a complete set of plans and specifications that conform
exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
8172261919, rbooze@e4harchitecture..com
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 2/2
4G0603AE
4G0603AK2
4G0603AQ
AREL
Detailed plans and specifications of the fire suppression system shall be filed with the required
application and appropriate fees in accordance with 675 IAC 12-6-3(a), 675 IAC 12-6-7(g)(17), and
675 IAC 13-1-8. (N.F.P.A. 13)
This release does not include the fire alarm system installation. Plans and specifications for adding
or remodeling this system shall be filed as a new project or as a partial before commencing work, in
accordance with 675 IAC 12-6-3.
This release does not include tank and or dispenser installation work. Plans and specifications for
adding or remodeling the tank and piping system shall be filed as a new project before commencing
work in accordance with 675 IAC 12-6-3.
Pursuant to 675 IAC 12-6-21, the issuance of a design release does not relieve the owner from
required compliance with all applicable rules of the commission, even if noncompliant conditions
appear in the plans and specifications that have been filed with the division. The owner is
responsible for correcting any and all areas of noncompliance even if they are discovered
subsequent to the issuing of this design release.
Please be advised that if an administrative review of this action is desired, a written petition for review must be filed at the above address with the
Fire Prevention and Building Safety Commission identifying the matter for which a review is sought no later than eighteen (18) days from the above -
stated date, unless the eighteenth day falls on a Saturday, a Sunday, a legal holiday under State statute, or a day in which the Department of Fire
and Building Services is closed during normal business hours. In the latter case, the filing deadline will be the first working day thereafter. If you
choose to petition, and the before-mentioned procedures are followed, your petition for review will be granted, and an administrative proceeding will
be conducted by an administrative law judge of the Fire Prevention and Building Safety Commission. If a petition for review is not filed, this Order will
be final, and you must comply with its requirements.