HomeMy WebLinkAboutM-001-SYMBOLS-AND-NOTES---MECHANICAL-Rev.0MECHANICAL SYMBOLS
NEW EQUIPMENT
V„•
LIPS -
LOW PRESSURE STEAM,M,L„L,
PEXISTING
EXISTING EQUIPMENT
EQUIPMENT TO BE REMOVED OR RELOCATED
---LPR---
LOW PRESSURE CONDENSATE RETURN
—PCP—
PUMPED CONDENSATE RETURN
—w—
DOMESTIC COLD WATER
NEW DUCT
—+w—
DOMESTIC HOT WATER
—wNw—
DOMESTIC HOT WATER RETURN
EXISTING DUCT
SANITARY WASTE LINE
-�-�
EXISTING DUCT TO BE REMOVED OR RELOCATED
—CD—
CONDENSATE DRAIN
—P—
PUMPED SANITARY LINE
®
NEW SUPPLY DIFFUSER
---
VENT LINE
DIRECTION OF SLOPE
EXISTING SUPPLY DIFFUSER
T
DIRECTION OF FLOW
EXISTING SUPPLY DIFFUSER TO BE REMOVED OR RELOCATED
-per
EXPANSION LOOP
NEW RIA OR EXHAUST GRILLE
GATE VALVE
BUTTERRYVALVE
EXISTING PJAOR EXHAUST GRILLE
BALL VALVE
k_J
EXISTING RIA OR EXHAUST GRILLE TO BE REMOVED OR RELOCATED
GLOBE VALVE
TEMPERATURE AND PRESSURE RELIEF VALVE
NEW CLOT DIFFUSER
0
., .,.�� ..,..,
1 X I AUTOMATIC 3WAY CONTROL VALVE I
SOLENOID VALVE
I —U—. I UNDERCUTDOOR 1
VALVE IN VERTICAL
CONICAL TAP WITH VOLUME DAMPER ----- UNION
VACUUM BREAKER
CONICAL TAP WIO VOLUME DAMPER >D P-TRAP
POOR DRAIN WIP-TRAP
t
PETES PLUG
GAUGECOCK
MOTORIZEDDAMPER
HIFTI
BAROMETRIC DAMPER
F'
'y
THERMOMETER
THERMOMETER WELL
— —
CHILLED WATER SUPPLY PIPE
— —
IF
— —
CUNDi WA I ER SUPPLY
STRAINER WITH BLOW -OFF VALVE
—CR—
CONDENSER WATER RETURN PIPE
FBT STEAM TRAP
— —
RFFRIGFRANT I nI ]in PUFF
CONNECT TO EXISTING
MECHANICAL ABBREVIATIONS
AC ABOVE CEILING CRU COMPUTER ROOM UNIT EUH ELECTRIC U NIT H EATER OBD OPPOSED BLADE DAMPER
AFF ABOVE FINISHED FLOOR CU CONDENSING UNIT FCU FAN COIL UNIT R RELOCATED
At ANALOGINPUT DI DIGITAL INPUT FPS FAN POWERED BOX RA RETURN AIR
AO ANALOG OUTPUT DO DIGITAL OUTPUT FPI FINS PER INCH SA SUPPLY AIR
BF BELOW FLOOR IDS DISCONNECT SWITCH GC GENERAL CONTRACTOR UH UNIT HEATER
BFC BELOW FINISHED CEILING E EXISTING MVD MANUAL VOLUME DAMPER WHIP WATER -SOURCE HEAT PUMP
BIG BELOW GRADE EDH ELECTRIC DUCT HEATER N NEW VAV VARIABLE AIR VALVE
EF EXHAUST FAN WH WATERHEATER
GENERAL SYMBOLS
GENERAL SECTION TARGETS PARTIAL PLAN AND DETAIL TARGETS
SHEET DESIGNATION
OKEYED NOTE$ / —
1 PLAN OR DETAIL DESIGNATION
M-100 M-loci
1
REVISION li
SHEET NUMBER
DETAILTARGETS
DETAIL DESIGNATION SHEET NUMBER
REVISION CLOUD
7
M-100
SHEETNUMBER
MECHANICAL DESIGNATION
EQUIPMENT DESIGNATION CW$ RISERDESIGNATION
(TOP- EQUIPMENT ABBREVIATION, BOTTOM 1 (TOP -RISER ABBREVIATION, BOTTOM -
MARK) MARK)
e AIR DEVICE DESIGNATION
(TOP- EQUIPMENT ABBREVIATION, BOTTOM
MARK)
SIZE OR (E) EXISTING
(R)RELOCATED
E MAXIMUM CFM
FIX - MINIMUM ci-M
DESIGNATION
(TOP - EQUIPMENT ABBREVIATION)
(BOTTOM -AHU#-SEQUENCE(MARK)
—1 RETURNIRELIEREXHAUSTIOUTSIDE
NON CONDITIONED AIR (DIRECTION OF
FLOW)
RELEASED FOR CONSTRUCTION 101 FLOW)
Subject to compliance with all regulations IRECTION OF ROW)
of State and Local Codes
City of Canted
yVT�i�
DATE: 06/07/19
MECHANICAL
SW ASSOCIATES
MECHANICAL GENERAL NOTES I MECHANICAL DESIGN CRITERIA
A. DRAWINGS
I SPECIFICATIONS:
MECHANICAL DRAWINGS I SPECIFICATIONS ARE GENERALLY DIAGRAMMATIC IN
DESIGN CRITERIA:
7ATORFAA61RiER5
T6bESCRIBE AND ILLUSTRATE SYSTEMS THAT WILL NOT INTERFERE WITH THE
LOCATION: 145B5 HAZEL DELL PKVVY, CARMEL, IN 46033
ARCHITECTURAL ISTRUCTURAL CONDITIONS OF THE BUILDING, AND WILL FIT INTO AVAILABLE SPACES. CAREFULLY
LAYOUT ALL WORK TO CONFORM TO THE ARCHITECTURAL, STRUCTU RAL, FINCH CON DITIONS, All FACTURER
LATITU DEILONGTITUDE:40Jq DEGREES NORTH IB6ID DEGREES WEST
EQUIPMENT I FUTURE CUTSHEETS AND WITH OTH ER TRADES, TO AVOID OBSTRUCTIONS, AN D TO ALLOW THE
ELEVATION: 812 FEET
PROPER INSTALLATION OF EACH ITEM CONTRACTOR SHALL OBTAIN ALLARCHITECTURAL DATA LOCATIONS OF
WINTER DB'32 DEGREES F rfSFN)
WALLS, PARTITIONS, FIXTURES, CEILING HEIGHTS, FINISHES, ETC. FROM ARCHITECTURAL DRAWINGS AND STRUCTURAL
SUMMER DB' 887 DEGREES (04%
DATA, LOCATIONS OF PIERS, BEAMS, COLUMNS, JOISTS, ETC. FROM STRUCTURAL DRAWINGS. CONTRACTOR SHALL
SUMMER WB: 74.0 DEGREES F(0.4%)
PROVIDE OFFSETS, RELOCATIONS, ETC.. AS REQUIRED TO MEET THIS INTENT AT NO ADDITIONAL COSTS
B.
C. CONFLICTS: WHEREVER CONFLICTS OCCUR BETWEEN DIFFERENT PARTS OF THE CONTRACT DOCUMENTS, THE
ZREATERIIUANTITY, THE BETTER QUALITY, OR LARGER SEE SHALL PREVAIL UNLESS THE ARCHITECT INFORMS THE
COMPACTOR OTHERWISE IN WRITING.
D. MECHANICAL SYSTEM: CONTRACTOR SHALL PROVIDE A MECHANICAL INSTALLATION THAT IS COMPLETE AND ALL
TTE997NTTP7ORT MCM NECESSARY, REASONABLE INCIDENTAL, OR CUSTOMARILY INCLUDED, EVEN THOUGH
EACH AND EVERY ITEM IS NOT SPECIFICALLY CALLED OUT OR SHOWN. THE CONTRACTOR SHALL PROVIDE ALL
EQUIPMENT, MATERIALS, LABOR, SUPERVISION AND SERVICE NECESSARY SO AS TO PROVIDE ACOMPLETE,
FUNCTIONING MECHANICAL SYSTEM.
E.
EQUIPMENT IN A NEAT WORKMANSHIP -LIKE MANNER. MECHANICAL EQUIPMENT SHALL BE AS SCHEDULED OR
APPROVED EQUAL AND INSTALL IN FULL ACCORDANCE WITH ALL APPLICABLE CODES HAVING JURISDICTION.
COORDINATE BETWEEN ALL TRADES PRIOR TO STARTING ANY WORK. PROVIDE ADEQUATE CLEARANCE FOR PROPER
OPERATION, SERVICE I MAINTENANCE, AIR FLOW, ETC.
F. CODES AND ORDINANCES: EXECUTE ALL WORK FOLLOWING LOCAL, STATE ANDIOR NATIONAL CODES, ORDINANCES,
AND REGOCATIbRSGDVERNING THE PARTICULAR CLASS OF WORK INVOLVED THE GGVERNING CODES ARE MINIMUM
REQUIREMENTS THE DRAWINGS ANDIOR SPECIFICATIONS SHALL PREVAIL WHERE THE DRAWINGS ARDOR
ACCOMPANYING SPECIFICATIONS EXCEED THE CODE REQUIREMENTS.
G. FEESANDPERMIIS: CONTRACTOR IS RESPONSIBLE FOR FILING AND PAYING ALL FEES AND OBTAINING NECESSARY
?77979TR=FICATES OF INSPECTION. THE CONTRACTOR SHALL DELIVER ALL CERTIFICATES OF INSPECTION
TO OWNERICONSTRUCTION MANAGER INCLUDING COPIES WITH MAINTENANCE MANUALS.
H. SHOP I RECORD DRAWINGS: CONTRACTOR SHALL PROVIDE DETAILED AN D DIMENSIONED HVAC DUCTWORK AND
PIPI9G7A;977PjTP0 DRAWINGS FOR APPROVAL BY THE ARCHITECT I ENGINEER. DURING THE INSTALLATION
OF THE WORK, THE CONTRACTOR SHALL KEEP DETAILED RECORDS OF ANY AND ALL CHANGES MADE FROM THE
CONTRACT DRAWINGS. AFTER FINAL COMPLETION REVISE A SET OF CONTRACT DRAWINGS TO ILLUSTRATE THE
WORK AS ACTUALLY INSTALLED, TI ESE RECORD DRAWINGS SHALL BE NOTED'ASBUll AND SUBMITTED TO THE
ARCHITECT I ENGINEER FOR REVIEW WITH ALL 08M MANUALS.
I. EQUIPMENTIPIPING SUPPORTS: PROPERLY SUPPORT ALL MECHANICAL EQUIPMENT AND PIPING WITHIN THE
RmCGIRGhNG'PRb'JIDEADEQIIATE PROVISIONS FOR SLOPE AND ANCHORAGE CONTRACTOR SHALL USE HANGERS,
RODS AND INSERTS APPROVED BY UNDERWRITERS LABORATORIES FOR THE SERVICE INTENDED, SECURELY
SUPPORTED BY STRUCTURAL MEMBERS WHICH IN TURN ARE SUPPORTED DIRECTLY FROM THE BUILDING
STRUCTURE.
J. ELECTRICAL EQUIPMENT: DO NOT RUN DUCTWORK PIPING OR LOCATE EQUIPMENT, WITH RESPECT TO
S7RGF97R657AAECSOARDS, POWER PANELS, MOTOR CONTROL CENTERS OR DRY TYPE TRANSFORMERS, WITHIN
42INCHES IN FRONT OF EQUIPMENT, OVER EQUIPMENT, OR WITHIN 36INCHES HORIZONTALLY OF SAME SPACE.
K. MECHANICALEQUIPMENT DUCTWORK PIPING: DUCTWORK AND PIPING SHALL BE RUN CONCEALED ABOVE CEILINGS,
CATIONS SHOWN, UNLESS NOTED OTHERWISE. CONFORM TO ALL
ARCHITECTURAL, STRUCTURAL, AND FINCH CONDITIONS OF BUILDING. WHEREVER CONDITIONS ARISE WHICH WILL
CAUSE NORMALLY CONCEALED MATERIALS TO BE EXPOSED, IMMEDIATELY CALL THE SITUATION TO TIE ATTENTION
OF THE ARCHITECT AND STOP WORK IN THOSE AREAS UNTIL THE ARCHITECT DIRECTS THE RESUMPTION OF THE
WORK AND TH E PROCEDURES TO BE FOLLOWED.
L. HVAC PIPING: SLOPE AND ARRANGE HVAC PIPING TO ESTABLISH HIGH POINTS FOR AIR ELIMINATION AN D LOW
POINTS70MRMIT PROPER DRAINAGE, PROVIDE AIR VENTS AT HIGH POINTS AND DRAIN VALVES AT LOW POINT.
CONDENSATE PIPE SHALL BE TYPE M, DRAWN -TEMPER COPPER TUBING, WROUGHT -COPPER FIRINGS, AND
SOLDERED JOINTS.
M. THERMOSTATS I SENSORS:Ti ERMOSTATS I SENSORS SHALL BE MOU NTED AT 48 AFF APPROX AS SHOWN, MAX
TFR0MEN607TAC6 ANDIOR DOOR JAMB. COORDINATE EXACT LOCATIONS WITH ARCHITECT AND BETWEEN
TRADES PRIOR TO MOUNTING. DO NOT MOUNT ABOVE DIMMERS.
N. PRE-RREJSMOKE DAMPERS: FIRE AND FIREISMOKE DAMPERS SHALL BE INSTALLED AS INDICATED AND WHERE
MAYBE JI HERWI$EREGOIR'ED BY LOCAL CODESAND ORDINANCES. REFER TO ARCH DWGS I BUILDING CODE
SUMMARY I LIFE SAFETY PLANS FOR LOCATIONS OF ALL FIRE RESISTANT- RATED WALLS, CEILINGS, CHASES I
SHAFTS, SMOKE COMPARTMENTS, AND LOCATIONS OF EGRESS CORRIDORS. PROVIDE MEANS TO ADEQUATELY
SERVICE THE DAMPERS FUSIBLE LINKS, PROVIDE 12 X12 MINIMUM METAL ACCESS DOORS IN ALL GYP BD.
- CEILINGS. INSTALL IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATEINSAND UL LISTING FOR SERVICE
INTENDED. PROVIDE METAL SLEEVES AS REQUIRED.
0. DUCTWORK CONSTRUCTION: DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STANDARDS AND
gl=ND FIRE DAMPER SIZES SHOWN ARE AIRSTREAM DIMENSIONS ALLLONGTUDINALAND
TRANSVERSE SEAMS AND DUCT CONNECTIONS SHALL BE SECURELY FASTENED AND SEALED AIRTIGHT.
P. AIR DEVICES: CEILING -MOUNTED AIR DEVICES SHALL BE LOCATED APPROXIMATELY AS SHOWN, FOR EXACT
L0GATDPT9D FRAME MOUNTING TYPES, REFER TO ARCHITECTURAL REFLECTED CEILING PLAN ALL CEILING
DIFFUSERS TO BE AWAY TYPE, UNLESS NOTED OTHERWISE BY AIRFLOW ARROWS ON FLOOR PLAN (INSULATE TIE
BACK OF CEILING DIFFUSERS UNLESS CEILING SPACE IS USED AS RETURN AIR PLENUM.) REFER TO
ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATIONS, OF ALL CEILING FEATURES, LIGHTS, AIR DEVICES,
FINISHES. CEILING HEIGHTS AND ELECTRICAL DRAWINGS FOR SPEAKERS, DETECTORS, POWER OUTLETS, ETC AND
FIRE PROTECTION SHOP DRAWINGS FOR FIRE SPRINKLER HEADS. COORDINATE EXACT LOCATIONS WITH ARCHITECT
AND BETWEEN TRADES PRIOR TO MOUNTING.
Q. BRANCH DUCT RUN OUTS: BRANCH DUCT RU&OUTS TO CEILINGMOUNTED AIR DEVICES SHALL BE$AME SIZE
ASTECKORCESSAOTE60THERWISE PROVIDE A TWIST -IN FLARED CONICAL TAP WITH MANUAL VOLUME DAMPER
AT MAIN DUCT TAP AND EXTEND AS SHOWN. EXTEND FLEX DUCTWORKA MAXIMUM OF 610 FROM DIFFUSERS.
INSTALL AS STRAIGHT AS POSSIBLE WITH LONG RADIUS BENDS WITH CLAMPS TO BE USED AT BOTH ENDS. ALL
DAMPERS LOCATED ABOVE GYP BD. CEILINGS SHALL BE PROVIDED WITH REMOTE DAMPER ACTUATORS EQUAL TO
YOUNG REGULATORS MODEL
R. TURNING VANES: TURNING VAN ES SHALL BE INSTALLED IN ALL ELBOWS OF SUPPLY AN D RETURN AIR DUCTS AND
ARFQTRACTGR$ OR SPUTTER DAMPERS WITH EXTERNAL ADJUSTMENTS AT ALL RECTANGULAR BRANCH DUCT
TAKEOFFS TO AIR DEVICES. PROVIDE ADEQUATE ACCESS AND MEANS TO ADJUST I BALANCE ALL AIR
EXTRACTORS AND DUCT TAKE -OFFS.
S. MEDIUM PRESSURE DUCT RUN-0UTS: BRANCH MEDIUM PRESSURE DUCT RUN -OUTS TO VAV AIR TERMINALS SHALL
SESK9ESff!7ATVA7TP7SRMFk_NECK, UNLESS NOTED OTHERWISE. INCREASE DUCT SEE BY 2" IF GRATER
THAN 10'-0 FROM MAIN AND I OR MORE THAN 2-90 DEG ELBOWS.
T. EQUIPMENT ACCESS PANEL: ACCESS PANELS SHALL BE PROVIDED FOR EACH LOCATION WHERE MECHANICAL
ELVES, AUTOMATIC CONTROL VALVES, AUTOMATIC DAMPER MECHANISM, FIRE (SMOKE
DAMPER, ETC. ARE INSTALLED BEHIND FURRINGS, CHASES, OR NON REMOVABLE SUSPENDED CEILING. SIZE AND
POSITION EACH ACCESS PANEL SO THAT THE CONCEALED EQUIPMENT CAN BE PROPERLY SERVICED, MINIMUM
SEE SHALL BEN* X 24' UNLESS FIELD CONDITIONS DICTATE OTHERWISE. REFER TO ARCH DWGS.I SPECS AND
COORDINATE WITH GENERAL CONTRACTOR AND FOR EXACT LOCATION, CONDITIONS, SEES, FINISHES, SPECS, ETC.
U. REMOTE DAMPER ACTUATORS: PROVIDE REMOTE DAMPER ACTUATORS FOR EACH LOCATION WHERE VOLUME DAMPE
V. BALANCING AND REGULATING DEVICES: HVAC SYSTEMS SHALL BE INSTALLED COMPLETE WITH ALL BALANCING AND
THE TAB CONTRACTOR TO PERFORM HIS WORK, COORDINATE WITH THE TAB
CONTRACTOR TO DETERMINE THEIR EXACT REQUIREMENTS. ALL EQUIPMENT SHALL BE STARTED PER
MANUFACTURER'S START-UP INSTRUCTIONS. REPLACE FILTERS, BELTS, SHEAVES, DAMPERS, VALVES, STARTERS AND
HEATERS AS NECESSARY PRIOR TO TAB.
W. TESTING ADJUSTING AND BALANCING: CONTRACTOR SHALL PROVIDE ALL TESTING, ADJUSTING, AND BALANCING
RAN libIRIODNEU9101U MPERS, BALANCE AIR DEVICES FOR DRAFT -FREE AIR DETRIBUTION, VERIFY
CORRECT BE 'POINT AND CALIBRATION OF Ti ERMOSTATS, VERIFY ALL SEQUENCE OF OPERATION, STAGING OF
COOLING'HEATING AS APPLICABLE, BALANCE OF CONDENSOR AND HEATING WATER SYSTEMS PUMPS, BOILERS,
COOLING TOWERS, NOTE DEFICIENCIES IN MECHANICAL SYSTEMS, ETC FORA CORRECTLY OPERATING
MECHANICAL SYSTEM CONTRACTOR SHALL REPLACE ALL FILTERS AND CLEAN ALL STRAINERS TESTING AND
BALANCING SUBCONTRACTOR MUST BE MEMBER IN GOOD STANDING OF EITHER AABC OR NEEB AND SUBMIT
REPORT ON NESS, AABC, OR SMACNA FORMS FOR APPROVAL BY THE ENGINEER. PROVIDE ATEST AND BALANCE
REPORT TO THE MECHANICAL INSPECTOR AT TIME OF FINAL INSPECTION.
X. CONTRACTOR SHALL INSURE THE FURNISHING AND INSTALLATION OF ALL BRANCH ELECTRICAL CIRCUIT WIRING,
CONDUITS, PROTECTIVE DEVICES, DISCONNECTS, AND ACCESSORIES FOR ALL ELECTRICAL CONTROL POWER WIRING
TO INCLUDE BUT NOT LIMITED TO; CONTROL PANELS, ACTUATORS, SMOKE DETECTORS, CONTROL IMOTORIZED
DAMPERS, PRESSURE MONITORS FIREISMOKE DAMPERS, VARIABLE FREQUENCY DRIVES, VAV TERMINALS 4V
TRANSFORMER, AND ALL OTHER 120V CONTROLS AS REQUIRED FOR A COMPLETE CONTROL SYSTEM WHE ER
SHOWN TO BE PERFORMED BY OTHERS OR NOT. ALL ELECTRICAL WORK SHALL BE INSTALLED IN FULL
ACCORDANCE WITH THE REQUIREMENTS OF ELECTRICAL SPECIFICATIONS. COORDINATE WITH ELECTRICAL
CONTRACTOR.
BUILDING CODES AND STANDARD
H"- W
o
z
x
5
W =H
p
2E~C.5
JW
a
z
O W.~.
�Cc)
c
Z0�
g
m
a
�
s
w�
z
'
—
p
E
w
Om
_
F
m
CITYOF CARMEL, INDIANk
a`ON`� """ .'
(PER STATE OF INDIANA)
`1Ep15TEq.
STATE OF INDIANA:
No. PE 18403
2014 INDWNA BUILDING CODE
?�:. STATEOF
2014 INDWNA FIRE CODE
!A'OIANl.
E14 IN DIANA PLUMBING CODE
2014 INDIANA FUEL GAG CODE"gSATM1i
,EN
2014 INDWNA MECHANICAL CODE
2010 INDNNA ENERGY CONSERVATION CODE
SODS INDIANA ELECTRICAL CODE
Seale
PROJECT IN FO'
OCCUPANCY/CLASSIFICATION : REFER TO ARCH ITECTURAL DRAWINGS
CONSTRUCTION TYPE: REFER TO ARCHITECTURAL DRAWINGS
BUILDING AREASICALCULATION: REFER TO ARCHITECTU RAL DRAWINGS ISSUED FOR BID &
PERMIT
i
O
O
cc
a
U
C
CU
CU
W
Q�
Cz
a_
U
C
QJ
_U1
QD
0
QJ
N
DO
00
Lf7
7
No Revision Date
Project Number. 3018082
Date 02/26/2019
SheBTide and Number.
M-001
SYMBOLS AND NOTES -