Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
M-701-SCHEDULES---MECHANICAL-Rev.0
VAV BOX W/ ELECTRIC COIL SCHEDULE (VVR) VAV HEATING COIL VAV VALVE CFM OLNGE MAX. S.P.D. MAX. MANUFACTURER/MODE NOTES SIZE CO SIZE (IN) IN. W.G. N.C. VOLTS/PH STAGES KW MIN. -MAX. 6 6" 75AOO 0.10 27 480 SCR SEE PLANS SEE SPECIFICATION ALL 8 8" 145-800 0.12 31 480/3 SCR SEE PLANS SEE SPECIFICATION ALL 10 10' 235-1200 0.12 32 480 SCR SEE PLANS SEE SPECIFICATION ALL 12 12, 340-1600 0.15 32 4805 SCR SEE PLANS SEE SPECIFICATION ALL 14 14" 475-2200 0.15 36 480 SCR SEE PLANS SEE SPECIFICATION ALL 16 16' 6252800 0.15 38 480 SCR SEE PLANS SEE SPECIFICATION ALL NOTES: 1. SEE PLANS FOR KW, ACTUAL MAX, COOLING CFM AND MINIMUM CFM. 2. MINIMUM CFM IS ZERO UNLESS NOTED OTHERWISE. KEY: WR SIZE - PRIMARY CFM 3. MAX N.C. RELATES TO S.P. DIFFERENCE BETWEEN INLET AND OUTLET @3.0". XX- KW -MINIMUM CFM 4. PROVIDE 121 CONTROL TRANSFORMER. 5. DISCONNECT SWITCH AND MOTOR STARTER. BOX # REPRESENTS 6. INTERFACE WITH BUILDING AUTOMATION SYSTEM (BMS). RTU #AND SEQUENCE VAV BOX NOTES: NUMBER 1, ALL TERMINAL UNITS SHALL BE LOCATED IN THE CEILING PLENUM, AND SHALL BE SINGLE -DUCT, NON -FAN POWERED TYPE. TERMINAL UNITS SHALL BE OF DOUBLE -WALL CONSTRUCTION WITH NON -POROUS METAL INNER LINER, BOTTOM ACCESS PANEL AND VOLUME DAMPER. TERMINAL UNIT DDC CONTROLS AND ELECTRIC DAMPER ACTUATOR, FURNISHED BY THE CONTROLS CONTRACTOR, SHALL BE FACTORY MOUNTED. AIR DEVICE SCHEDULE MARK SIZE OEID FINISH NECK SIZE MANUFACTURERIMODEL REMARKS $1 24124 NO OFF WHITE (4) 1 TITUS OMNI CEILING SUPPLY AIR DIFFUSER 4 S2 12112 NO OFF WHITE4 1 TITUS OMNI CEILING SUPPLY AIR DIFFUSER 4 S3 NECK SIZE +2" NO OFF WHITE 4 SEE PLANS TITUS 272 HORIZONTAL BLADE SIDEWALL SUPPLY AIR GRILLE 3 4 S4 20/20 NO OFF WHITE 4 18118 TITUS SGSD MAXIMUM SECURITY GRILLE 5 S5 4FEET NO OFF WHITE 4 8" TITUS Ni PLENUM SLOT DIFFUSER, 3/4-SLOT 34 R1 24/24 NO OFF WHITE (4) 2 TITUS PAR CEILING RETURN AIR DIFFUSER (3) 4 R2 12124 NO OFF WHITE (4) 2 TITUS PAR CEILING RETURN AIR DIFFUSER (3) 4 R3 I NECK SIZE NO OFFWHITE4 SEEPLANS TITUS 23RL SIDEWALL RETURN GRILLE 34 R4 20/201 NO OFF WHITE 4 18/18 TITUS SGSD MAXIMUM SECURITY GRILLE 5 Ei 24(24 NO OFF WHITE4 2 TITUS PAR CEILING EXHAUST AIR DIFFUSER 4 E2 12112 NO OFF WHITE4 2 TITUS PAR CEILING EXHAUST AIR DIFFUSER 4 E3 NECK SIZE +2" 1 NO I OFFWHITE 4 SEEPLANS I TITUS 23RL I SIDEWALL EXHAUST GRILLE 3 4 NOTES: (1) 69 1 (2) B/8 0.290 CFM 6'0 0-100CFM 80 130-210 CFM 128 291400 CFM 810 101-180 CFM 11 215-325 CFM 12112 401-550 CFM 10"0 181-2BO CFM 12'0 330-400 CFM 18/12 551-700 CFM 12"0 281400 CFM 14"0 405525 CFM 18/18 701-112D CFM 14"0 401-W CFM 15"0 530730 CFM 21 1121-1680 CFM 16"0 551-700CFM (3) CONTRACTOR TO COORDINATE FRAME STYLE W/ (5) 4" SLEEVE ANGLE MOUNTING FRAME AND SQUARE ARCH. PLANS TO ROUND ADAPTOR SIZED PER NOTE 1. (4) CONTRACTOR TO COORDINATE COLOR SELECTIONS WITH ARCHITECT. UNIT HEATER SCHEDULE MARK SERVES AIRFLOW CFM) (ASE KW ELECTRICAL DATA MANUFACTURERIMODEL NO. REMARKSMOTES MPS DRAWNOLTS/PH FAN HP UH-01 RISER 400 5 6.5 1 480/3 1/40 MODINE HERSO ALL NOTES: (1) ENERGIZE UNIT HEATER TO MAINTAIN WALL MOUNTED THERMOSTAT SET POINT. (2) PROVIDE UNIT WITH THE FOLLOWING FEATURES: AUTOMATIC RESTART THERMAL CUTOUT SWITCH;48OV124V CONTROL VOLTAGE TRANSFORMER AND WALL MOUNT BRACKET. VAV BOX SCHEDULE SIZE INLET SIZE MAX CFM MAX S.P.D. IN W.G. MAX N.C. BASED ON: MANUFACTURER/MODEL REMARKS A 6" 400 0.10 28 SEE SPECIFICATION ALL NOTES B 8" 800 0.08 27 SEE SPECIFICATION ALL NOTES C 10" 1200 0.08 29 SEE SPECIFICATION ALL NOTES D 12" 1600 0.09 29 SEE SPECIFICATION ALL NOTES E 14" 2200 0.09 28 SEE SPECIFICATION ALL NOTES F 16" 2800 0.09 29 SEE SPECIFICATION ALL NOTES NOTES: KEY: O REFER TO PLANS FOR ACTUAL MAX. COOLING CFM AND MINIMUM CFM. VAV SIZE-PRIMARYCFM 2O MINIMUM CFM IS ZERO UNLESS NOTED OTHERWISE. XX-XX MINIMUM CFM(ZERO UNLESS NOTED) 3O MAXIMUM N.C. RELATES TO S.P. DIFFERENCE BETWEEN INLET AND OUTLET @3.0" BOX# REPRESENTS RTU# O PROVIDE 12DV/24V CONTROL TRANSFORMER WHERE ELECTRIC/ELECTRONIC CONTROL IS REQUIRED. AND SEQUENCE NUMBER O DISCONNECT SWITCH AND MOTOR STARTER. © INTERFACE WITH BUILDING AUTOMATION SYSTEM (BMS). RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City d Camel �VT�U1�Da141WML_ DATE: 06/07/19 SPLIT SYSTEM SCHEDULE DESIGNATION I SERVES I CAPACITY (MBH) I SEER NOTES: 1. SUPPORT AND INSTALLATION SHALL BE PER MANUFACTURER. 2. UN IT SHALL BE INVERTER DRIVEN. 3. PROVIDE FOR LOW AMBIENT OPERATION. 4. PROVIDE WITH WALL MOUNTED THERMOSTAT. 5. PROVIDE WITH INTEGRAL CONDENSATE PUMP.TRAP,INSULATE,SLOPE, AND RUN FULL SIZE CONDENSATE DRAIN LINES TO THE NEAREST FLOOR DRAIN OR MOP SINK OR SINK TAIL PIPE UPSTREAM OF P-TRAP. 6. PROVIDE HAIL GUARD FOR CONDENSING UNIT ON ROOF. FILTER SCHEDULE MARK TYPE MAX FACE P.D. OVERALL SIZE SIMILAR TO HOUSING TYPES REMARKSMOTES VELOCITY CLEANIDIRTV (MIN.) MANUFACTUREWMODEL PROVIDE DIFFERENTIAL PRESSURE F-1 HEPA 500 0.410.8 (3)12X24X11.5 CAMFIL-XH ABSOLUTE CAMFIL MAGNA/PACK SENSORS AND MAGNEHELIC GAUGE WITH DIRTY FILTER ALARM AT RECEPTION ELECTRIC HUMIDIFIER SCHEDULE MARK CFM KW VOLTSIPH DUCTSIZE SYSTEMSERVED HUMIDISTAT LOCATION MANUFACTURER/MODEL NO REMARKSMOTES 56-11DO-1 Woo1.9 120/1 14/12 VRH 1-3 TRAUMA/TREATMENT ROOM NORTEC EL 005 ALL NOTES: 1 MODULATING CONTROL 4 AIR FLOW PROVING SWITCH 7 DISCONNECT SWITCH 2 HUMIDISTAT 5 DRAIN TEMPERING VALVE 3 HIGHLIMITSWITCH 6 DISPERSION GRID WITH 12" ABSORBTION DISTANCE FAN SCHEDULE MARK EF-1 EF-2 EF-3 RF-1 TYPE ENTRIFUGAL UPBLAST ENTRIFUGAL UPBLAST CENTRIFUGAL UPBLAST CENTRIFUGAL INLINE SERVICE GENERAL ISOLATION DECONTAM WAITING ROOM CFM 1,590 340 16D 2000 SPIN WC) 1.1 0.75 0.75 1.0 POWER (HP) 0.53 0.1 0.07 0.57 FAN RPM 1,428 1,520 1,725 1172 DRIVETYPE DIRECT DIRECT DIRECT DIRECT APPROX. ROOF OPENING (IN) 16.5'X 16.5' 14.5'X 14.5' 12.5'X 12.5' - APPROX. WEIGHT (LBS) 77 60 40 180 MIN. HP 3/4 114 1/10 1 ELECTRICAL (VOLT/PHASE) 12011 120/1 120/1 120/1 RPM 1725 1725 1725 1300 M STARTER VARIGREEN VARIGREEN VARIGREEN VARIGREEN ON EMERGENCY POWER YES YES YES YES MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK MODEL CUE-141-VG CUE-101HP-VG CUE-080-VG SQ-160-VG NOTES 1.2.3.5.6 1.2.4.5.6 1.2.3.5.6 2.3.5.6 NOTES: 1. ALUMINUM WHEEL CONSTRUCTION, BACKDRAFT DAMPER, FACTORY ROOF CURB. 2. PROVIDE COMBINATION STARTER DISCONNECT WITH WEATHERPROOF ENCLOSURE WHEN MOUNTED OUTSIDE. 3. FAN TO BE INTERLOCKED WITH RTU SERVING THE AREA AND RUNNING WHILE RTU IS RUNNING. 4. FAN TO RUN CONTINUOUSLY. 5. PROVIDE WITH MICROPROCESSOR CAPABLE OF INTERFACING WITH BUILDING AUTOMATION SYSTEM. 6. FAN SELECTED TO ACCOMODATE ACCEPTABLE LEVELS OF DUCT LEAKAGE. ELECTRIC DUCT HEATER SCHEDULE MARK CFM KW VOLTS/PH DUCTSIZE STAGES EMERGENCY MANUFACTURERIMODELNO REMARKS Di 300 3.5 461 1 TiSCR YES INDEECO QUA ALL DH-2 350 3.5 451 11 SCR YES INDEECO QUA ALL DH-3 980 10.5 46013 14114 SCR NO INDEECO QUA ALL NOTES: 1. DISCONNECT, AIRFLOW SWITCH, THERMOSTAT. CONDENSING UNIT SCHEDULE MARK SERVES COOLING ELECTRICAL EER MANUFACTURER MODEL WEIGHT (LBS) NOTES qMB. TEMP. (DBfWB) TOTCAP (MBH) COMPRESSOR FLA CONO FLA MCA MOCP OLTAGE CU-1 AHU-1 9&75 444.2 4 AT 16.7 EA 74 78 90 460/3 11.6 AAON CFA4W0•D-A-3 2409 ALL CU-2 AHU-2 95175 63.64 1 AT 8.1 EA 2.8 13 20 460/3 13.9 AAON CFA-OOSAAJ 462 ALL NOTES: 1. PROVIDE WITH UNIT MOUNTED DISCONNECT RATED FOR 65K All 2. PROVIDE WITH UNIT MOUNTED CONTROLLER CAPABLE OF INTERFACING WITH BUILDING AUTOMATION SYSTEM, 3. PROVIDE WITH UNIT MODULATION DIGITAL SCROLL COMPRESSOR. SW ASSineem ES Consulting Engineers 1700 Pam Ave Suite 21M Dallas, TX 75211 Tel: 214.391.0211 w SWAwgincers.com PRWECT#IM09 AIR HANDLING UNIT SCHEDULE MARK AHU-1 SERVICE CT/EXAMANAITING MAX. CFM 12,500 z EXT. S.P. (-WG) 2.50 FAN RPM 3,930 5 o- FAN MOTOR HP (EACHROTAL) 4.5/18 N VOLT&PH 480/3 MAX CFM 10,400 EXT. S.P. (VG) 1.50 WFAN RPM 3,862 lu FAN MOTOR HP (EACH/TOTAL) 1.516 VOLTS/PH 48013 CFM 12,500 r FACE VEL (FPM) 428.67 o AIR P.D. ("WG) 0.47 00 EAT °F DBANB 77.7164.8 z LAT°F DBANB 54.1/53.0 NET TOTAL CAPACITY (MBH) 444.E U NET SENSIBLE CAPACITY(MBH) 324.6 ROWS/FINS(MIN) 6/8 OUTSIDE AIR CFM 2,100 W w TYPE 2"PLEATED d F EFFICIENCY(%) MERV8 a MAX. VELOCITY(FPM) 500 P.D.(CLEAN/DIRTY) 0.256/0.5 z TYPE 12"CARTRIDGE w n F EFFICIENCY(%) MERV14 o MAX. VELOCITY(FPM) 500 P.D.(CLEAN/DIRTY) 0.320/0.6 MANUFACTURER TEMTROL REMARKSMOTES ALL NOTES: O SUPPLY FAN AND RETURN FAN BANKS PROVIDED WITH VFD RATED FOR 65K AIC. O PROVIDE DOUBLE WALL CONSTRUCTION, SLOPED ROOF, HINGED ACESS DOORS, OUTDOOR RATED. O PROVIDE WITH FULL ECONOMIZER WITH COMPARATIVE ENTHALPY CONTROL AND FAULT DETECTION AND DIAGNOSTICS. O PROVIDE WITH THE FOLLOWING SECTIONS: INLET PLENUM, RETURN FAN, ECONOMIZER, PRE FILTER, COOLING COIL, SUPPLY FAN, FINAL FILTER, DISCHARGE PLENUM. O PROVIDE SLOPED ROOF CURB WITH HEIGHT AS REQUIRED TO ELEVATE OUTSIDE AIR INTAKE 36" ABOVE FINISHED ROOF. © PROVIDE LIGHT WITHIN EACH ACCESSIBLE SECTION OF THE UN IT AND CONVENIENCE OUTLET, COORDINATE 120V POWER. O7 PROVIDE MAGNAHELIC GAUGE ACROSS EACH FILTER BANK WITH REMOTE GAUGE AT NURSE STATION FOR FINAL FILTERS. AIR HANDLING UNIT SCHEDULE MARK (FAN COIL UNIT) AHU-2 SERVES UC EXAM AREA OUTSIDE AIR CFM 40D SUPPLY CFM 2,000 a EXT. S.P. ("WG) 1 a FAN MOTOR HP 8 a VOLTS/PH 460/3 cv z¢ EAT DB/WB(°F) 78.20/65.20 0 o SENS. CAPACITY 150.39 0 TOTAL CAPACITY 6364 KW 21 /j F VOLTS/PH 460/3 s o TOTAL HEAT (MBH) 71.7 ELECTRIC HEAT FLA 25.3 MCA 42 oMOCP 45 w VOLTS/PH 460/3 MANUFACTURER AAON MODEL NO. H3-0RB30161C REMARKSMOTES ALL NOTES: O PROVIDE UNIT MOUNTED DISCONNECT FOR SINGLE POINT POWER RATED FOR 65K AIC. O PROVIDE FINAL FILTER CURB WITH MERV 17 FILTER RATING. PROVIDE REMOTE MAGNAHELIC GAUGE AT NURSE STATION. HEIGHT AS REQUIRED TO ELEVATE OUTSIDE AIR INTAKE 36" A.F.R.. O PROVIDE WITH FULL ECONOMIZER WITH COMPARARTIVE ENTHALPY CONTROL AND FAULT DETECTION AND DIAGNOSTICS. 4O PROVIDE WITH UNIT MOUNTED CONTROLLER CAPABLE OF INTERFACING WITH BAS. SO ELECTRIC HEAT IS TO BE SCR CONTROLLED. l- w -L W =� H~ ZJ QLU pW CCU Zp W LL Q PE 18403 STATE OF Sues r ISSUED FOR BID & PERMIT C CD O cc a No Rewbon Date 241 W a3 i Pmieet Number. 3018082 Date 02/26/2019 Shea[Tit and Number. M-701 SCHEDULES - MECHANICAL