HomeMy WebLinkAboutM-802-DETAILS---MECHANICAL-Rev.0SW ASSOCIATES
cn
Consulting Engineers
W
G
o
Z e
QJ
1700 Pam Ave
x
LLISUW
@
Dallas?TX 75ZI
=�
O
d
Tel. 214.391.0211
�.SWAengineen.corn
d
ZJw
PROJECT#IW09
Owl 4
AIR COOLED
C=
WALL
—Tn
1" MINIMUM OPENING OVERLAP
CONDENSER UNIT
NCO c
j
ON ALL
SIDES OF DAMPER
g
on
FAN DISCHARGE
TRANSITION AS REQUIRED
WOW ¢ a
NOTE:
DUCT
FUSIBLE R00
1. PROVIDE ACCESS DOOR FORALL FIRESMOKE DAMPERS.
SIZE& INSTALL REFRIGERANT LINES PER
VAV TERMINAL UNIT
z
'o
2. FOR DUCTS 12112 AND SMALLER REQUIRING A FIRESMOKE CONDENSER UNIT MANUFACTURER'S
r
g
DAMPER, TRANSITION TO A DUCT A TOTAL OF 2"LARGER RECOMMENDATIONS
Ell
ON EACH SIDE PRIOR TO DAMPER CONNECTION.
E
TRANSITION BACK TO ORIGINAL DUCT SIZE AFTER EXITING
—
Ca
E
DAMPERFRAME
DAMPER. LARGER SIZE DUCT SHALL BE USED TO SIZE
z
w
REQUIRED DAMPER.
PRIMARY AIR DUCT SIZED TO MATCH
OPERATORIACTUATOR
EQUIPMENT SUPPORTS
LOW PRESSURE SUPPLY AIR DUCT,
PLAN VIEW UNIT CONNECTION. PROVDETWOTO�
PATE CO. STYLE "ES-1 A"
'- SEE PLANS FOR SIZE
FIVE DUCT DIAMETERS OF STRAIGHT
m
AUXILIARY OPERATING
OPERATION: OR APPROVED EQUAL
DUCT WITHOUT ELBOWS IMMEDIATELY
JACKSHAFT
A FIRE DAMPER MODE: HIGH TEMPERATURE MELTS FUSIBLE
-
UPSTREAM OF THE UNIT
LINK. CLOSING FIRE DAMPER.
1111ppnnJpJe11
o" N G. P/ ��i�
a ey.
RUN ROOFING MEMBRANE
B. SMOKE DAMPER MODE: SMOKE DETECTOR UPON SENSING UP TO FLASHING
�•'p15TEy'.•.,
.`�•'fr. Epy �,
HEATISMOKE ACTUATES DAMPER MOTOR TO CLOSE
CALKING MATERIAL
PIPE CURB ASSEMBLY
DAMPER. PATE CO. STYLE "PCA-1"
MOPE 10403225:
= c
C. PROVIDE INTEGRAL NO FLOWSENSOR WITH REMOTE OR APPROVED EQUAL
=a STATE OF
�.,
SLEEVE
RESETISTATUS.
16 GAUGE SHEET METAL STRAPS
'o�i.M'UL\M1.'" 4�0
'oEdJfpMA...... �
SJOINT.
SLEEVE TO DUCT
BUILT UP ROOF, EXISTING
D. PROVIDE END SWITCHES TO MONITOR DAMPER POSITION.
S
ROOF DECK, EXISTING
TRANSITION AS REQUIRED
Q p
E. PROVIDE REMOTE TEST SWITCH FOR TESTING PURPOSES
AT GROUND LEVEL.
MOUNTING ANGLES
7" NEOPRONE PADS OR
VAV TERMINAL UNIT
Seals 8226119
RESTRAINED SPRING ISOLATORS
MAX.)
n—
�1 FIRE WE DAMPER INSTALLATION DETAIL
SCALE: N.T.S.
SUPPLY DUCT
CONICAL SPIN -IN TAP WITH
SQUARE DAMPER ROD& DAMPER
OPERATOR WITH LOCKING
QUADRANT. PROVIDE SHEETMETAL
STANDOFF TO CLEAR INSULATION.
CEILING
SURFACE MOUNT TYPE
LAY -IN TYPE
GRILLE OR DIFFUSER
NOTES:
1. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING
TYPES AND COORDINATION OF CEILING DIFFUSER
LOCATIONS.
2. USE BOTTOM TAP CONNECTION ONLY IF SIDEWALL
BRANCH RUNOUT CONNECTION METHOD IS NOT POSSIBLE.
%1 BOTTOM TAP SUPPLY AIR DEVICE CONNECTION DETAIL
SCALE: N.T.S.
SUPPLY AIR DUCT
STEAM DISPERSION MANIFOLD
LOW PRESSURE STEAM LINE
DOMESTIC COLD WATER
MAKE-UP FOR STEAM.
REFER TO PLUMBING FOR
CONNECTION.
HUMIDIFIER
L PAD MOUNTED CONDENSING UNIT
SCALE: N.T.S.
NOTE:
1. PROVIDE DOOR WITH I" THICK INSUATON.
2. PROVIDE REMOVABLE DOOR WITH CAM LATCHES.
3. IN ROUND DUCTS, PROVIDE TAP TO TRANSITIONS TO SQUARE DOOR.
4. REFER TO PLANS FOR DOOR SIZE WHEN DOOR IS LOCATED IN
HORIZONTAL PLANE.
5. DOOR HEIGHTTO BE 2" LESS THAN DUCT HEIGHT.
6. BASIS OF DESIGN: AIR BALANCE FSA-101-H FOR DOORS IN MEDIUM
PRESSURE DUCTWORK AND AIR BALANCE FSA-101 FOR DOORS IN LOW
PRESSU RE DUCTWORK.
SHEET METAL DUCT ACCESS DOOR
SCALE: N.T.S.
CONDENSATE DRAIN LINE
HUMIDIFIER TANK I
A
SLOWDOWN
DRAIN
will
314" TO FLOOR DRAIN. TERMINATE WITH AIR GAP.
SECONDARY DRAIN PAN
UNION (TYP.)
STEEL SPRING VIBRATION
DOMESTIC COLD WATER FOR
ITYP
ISOLATOR ICAL(MN. 4)
ROD, SECURE TO S
STRUCTURE WITH
TEMPERED
CONDENSATE TEMPERING.
DOUBLE NUTS,TYPICAL.(MIN. OF 4).
CONDENSATE TO
REFER TO PLUMBING FOR
DISCONNECT—
DRAIN (MAX. 1200F)
CONNECTION.
THERMOSTATIC TEMPERATURE
CONTROL VALVE (BY
FLEXIDLECONECTION,
AFTERCOOLER MFR.)
TYPICAL
MANUAL DRAIN VALVE
(NORMALLY CLOSED)
CONDENSATE
AFTERCOOLER (BY
FULL SIZE OF AFTERCOOLER
HUMIDIFIER
DO INNCCN CONNECTION, ROUTE
MANUFACTURER)
/
AIRFLOW
NOTE:
STEAM CONDENSATE, WATER AND DRAIN LINES
SIZED PER MANUFACTURER'S INTAKE DUCT,
RECOMMENDATIONS. INSULATE STEAM, ISCHARGE DUCT, FOR SIZE
CONDENSATE AND DRAIN LINES AS SPECIFIED. SEE PLANS FOR SIZE.
RELEASED FOR CONSTRUCTION 8 INLINE FAN DETAIL
Subject to compliance with all regulations �J SCALE: N.T.S.
of State and local Codes TEAM HUMIDIFICATION SYSTEM DETAIL
City of Camel
�VT�'�Da141WML
DATE: 06/07/19
SUPPLYAIRDUCT
ELEVATION
VAV TERMINAL UNIT INSTALLATION DETAIL
�J SCALE: N.T.S.
(6" MAX. TYP.)
SLEEVE
WRAP NTH 1"- MIN. OR EQUAL TO EXTERNAL J�L �
INSULATION. TAPE& SEAL (TVP.)
EXTERNALLY WRAPPED DUCT N�
AIRFLOW
FIRE DAMPER
PRIMARY AIR DUCT
METAL NOSING ON
DOWNSTREAM SIDE
U.L. APPROVED SLIP JOINT(TYP. 4 SIDES) DUCTACCEESDOOR. REF4I108.02
RETAINING ANGLE PER MANUFACTURERS EXTERNALLY WRAPPED DUCT
LISTED INSTRUCTIONS
THERMAL EXPANSION SPACE TO BE AS RECOMMENDED SLEEVE INSULATE TO PREVENT CONDENSATION
BY MANUFACTURER TO INSURE ILL. APPROVAL
NOTE:
1. STYLE-B, DYNAMIl
2. STYLE -A, DYNAMIC RATED ALLOWED AT GRILLES.
3. SEE SPECS FOR DETAILS.
4. PROVIDE INTEGRAL SQUARE TO ROUND TRANSITION WHERE ROUND DUCT IS SHOWN
ON PLANS.
�1 FIRE DAMPER INSTALLATION DETAIL
~J SCALE: N.T.S.
DIRTY FILTER PANEL
INCHES OF WATER INCHES OF WATER
F_ E I
f RTU-1 AHU-1
MANOMETER LOCATE AT
NURSE STATION
DIRTY FILTER PANEL DETAIL
�J SCALE: N.T.S.
ISSUED FOR BID &
PERMIT
F—
O
0
cc
M
U
C
o
Z
Q�
E
J
W
W
C
Q
03
U
s_
(T5
C-)
�
Y
QD
C
I1
�
J
QJ
W
J
_
QJ
N
CD
p
¢
2
_
_
aJ
U0
NJ
00
E7
�
=
r
No
Rewbon
Date
Project Number. 3018082
One 0226/2019
SheETide and Number.
M-802
DETAILS - MECHANICAL